Dubai Building Code Part K: Villas K 69 Regulations (2010), Approved Document Part K, 2013 Edition. Contains public sector information licensed under the Open Government Licence v3.0) In accordance with Section 5, Ch. 1 of UAE FLSC [Ref. K.1] , safety glazing for use in critical locations shall conform to the minimum classifications in either Table K.16 or Table K.17. Critical location Height Classification in test standard BS EN 12600 Low-level areas All height Class 1 Doors Below 900 mm from FFL Class 2 Above 900 mm from FFL Class 3 Table K.16 Minimum classification for safety glazing requirements Table K.17 Minimum classification for safety glazing requirements Area of glazing in critical location (m 2 ) Classification in test standard ANSI Z97.1 CPSC 16 CR 1201 [Ref. K.13] ≤0.9 A I >0.9 B I K.7.6.2 Containment Glazing at areas lower than 800 mm from FFL and protecting a change in level greater than 760mm shall provide containment, as shown in Figure K.54. Figure K.54 Examples of glazed areas that need to provide containment Key 01: Internal FFL 02: External FFL 800 01 >760 01 02 800 Key 01:Floor level |