Dubai Building Code Part K: Villas K 101 Figure K.69 Typical arrangement for tariff metering cabinet recessed within compound wall Type of kWh metering Dimensions (mm) B C D E F G H I Direct connected metering 600 800 250 200 60 60 800 (min.) 1,600 (max.) 1,800 (max.) CT. Operated metering to 400/5 A) 800 1,000 300 250 80 80 800 (min.) 1,600 (max.) 1,800 (max.) Key 01: Compound wall. 03: Hinged door with provision for wire sealing and pad locking (hole size: min. 10 mm diameter). 04: Cable (gland) box. 05: Transparent meter viewing window (min. 5 mm thickness, size: 150 mm × 150 mm). 07: Position of incomer breaker. For CT operated meters, VT fuses shall be sealed type, located in a sealable enclosure. All tariff metering shall be smart meters, normally provided by DEWA and restricted to one for each consumer installation, unless otherwise approved/specified by DEWA. K.9.1.5.2 CT metering requirements Metering by means of current transformers (CTs) shall be installed where the circuit breaker rating at the point of supply is 160 A and above. NOTE 1: DEWA provides the smart kWh meter(s) and associated CTs for all tariff metering. In some circumstances the consumer might be permitted to provide the kWh meter and CTs as private check meters for energy monitoring purposes. Refer to G.4.5 for further details and requirements for CT metering. |