Chapter IX Functional Code List
Group P02: Basic Operation Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
Ones place: Motor 1 control mode
option
0: Vector control without PG
1: Vector control with PG
2: V/F control without PG
3: V/F control with PG
Tens place: Motor 1 type option
0: Asynchronous motor
Motor and mode
Motor and mode
1: Synchronous motor
P02.00
1
0002
×
option
option
Hundreds place: Motor 2 control
mode option
0: Vector control without PG
1: Vector control with PG
2: V/F control without PG
3: V/F control with PG
Thousands place: Motor 2 type option
0: Asynchronous motor
1: Synchronous motor
0: Motor 1
P02.01
Motor option
Motor option
1
0
×
1: Motor 2
0: Operation panel control
Operation command
Command channel
1: Terminal control
P02.02
1
0
○
channel option
option
2: Comm. control
3: Reserved
0: Digit given1: operation panel▲,▼
given
1: Digit given2: Terminal UP/DOWN
Main setting
given
Main given source
P02.03
frequency source
2: Digit given3: Serial port comm.
1
0
○
option
option
given
3: AI analog given
4: Terminal PULSE given
5: Reserved
Main setting
Main setting
P02.04
frequency digital
P02.07~P02.06
0.01Hz
50.00
○
frequency set
setting
Max output
Max output
MAX{50.00, Upper frequency
P02.05
0.01Hz
50.00
×
frequency
frequency
limitP02.06}~1000.0Hz
Upper limit
Upper limit
P02.06
P02.07~P02.05
0.01Hz
50.00
○
frequency
frequency
Lower limit
Lower limit
P02.07
0.00~P02.06
0.01Hz
0.00
○
frequency
frequency
0: no assistance given
1: Digit given1: operation panel▲,▼
given
2: Digit given2: Terminal UP/DOWN
Auxiliary setting
given
Auxiliary frequency
P02.08
frequency source
3: Digit given3: Serial port comm.
1
0
○
source option
option
given
4: AI analog given
5: Terminal PULSE given
6: Reserved
7: Process closed-loop output
P02.09
Auxiliary given
Auxiliary given
0.00~9.99
0.01
1.00
○
120
Chapter IX Functional Code List
Group P02: Basic Operation Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
coefficient
coefficient
For P02.08=4~7 only
Auxiliary given
Auxiliary given
P02.10
0.00~1000.0Hz
0.01Hz
0.00
○
digital setting
digital setting
0:
+
1:
-
2: *
Main and Auxiliary
Main and Auxiliary
3: MAX(main given, Auxiliary given)
P02.11
1
0
○
given caculation
given caculation
4: MIN(main given, Auxiliary given)
5: sqrt(main given)+sqrt(Auxiliary
given)
6: sqrt(main given+Auxiliary given)
0: No action
Setting frequency
frequency
1: Relative maximum output
P02.12
proportion
proportion
frequency P02.05 adjustment
1
0
○
adjustment option
adjustment
2: Relative current frequency
adjustment
Setting frequency
coefficient for
P02.13
adjustment
proportion
0.0%~200.0%
0.1%
100.0%
○
coefficient
adjustment
0.1(Unit
1.5~22: 6.0S
P02.14
acceleration time1
acceleration time1
0.0~3600.0
takes
30~45: 20.0S
○
P14.09)
Other: 30S
0.1
1.5~22: 6.0S
(Unit
P02.15
deceleration time 1
deceleration time 1
0.0~3600.0
30~45: 20.0S
○
takes
Other: 30S
P14.09)
P02.16
Jog frequency
Jog frequency
0.10~50.00Hz
0.01Hz
5.00
○
Jog acceleration
P02.17
Jog acceleration time
0.1~60.0S
0.1s
6.0
○
time
Jog Deceleration
P02.18
Jog deceleration time
0.1~60.0S
0.1s
6.0
○
time
P02.19
Jog time interval
Jog time interval
0.0~100.0s
0.1s
0.0
○
Run direction
0: Forward
P02.20
Run direction setting
1
0
○
setting
1: Reverse
P03: Motor 1 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
Decided
Asynchronous motor
by
P03.00
rated power
0.4~999.9kW
0.1
×
rated power
Machine
Type
Decided
Asynchronous motor
0~Servo driver’s rated voltage(P97.04)
by
P03.01
rated voltage
1
×
rated voltage
2 series: 220V; 4 series: 380V
Machine
Type
Decided
Asynchronous motor
by
P03.02
rated current
0.1~999.9A
0.1A
×
rated current
Machine
Type
121
Chapter IX Functional Code List
P03: Motor 1 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
Decided
Asynchronous
rated
0.01H
by
P03.03
motor’s rated
1.00~1000.0Hz
×
frequency
z
Machine
frequency
Type
Asynchronous motor
rated rotation
P03.04
0~60000RPM
1RPM
1440RPM
×
rated rotation speed
speed
Decided
0.001~1.000
Asynchronous motor
by
P03.05
power factor
Used when calculation motor parameters as per
0.001
×
power factor
Machine
nameplates
Type
Decided
Asynchronous motor
stator
by
P03.06
0.00%~50.00%
0.01%
×
stator resistance%R1
resistance%R1
Machine
Type
Decided
Asynchronous motor
leakage
by
P03.07
leakage inductance
inductance
0.00%~50.00%
0.01%
×
Machine
resistance %X
resistance %X
Type
Decided
Asynchronous motor
rotor
by
P03.08
0.00%~50.00%
0.01%
×
rotor resistance%R2
resistance%R2
Machine
Type
mutual
Decided
Asynchronous motor
inductance
by
P03.09
mutual
0.0%~2000.0%
0.1%
×
resistance %X
Machine
inductance
%Xm
m
Type
Decided
Asynchronous motor
No-load
by
P03.10
0.1~999.9A
0.1A
×
no-load current I0
current I0
Machine
Type
0: No action
Asynchronous motor
Parameter self
1: Action(Motor static)
P03.11
1
0
×
parameter self tunning
tunning
2: Action(Motor rotating)
3: Reserved
20.0%~110.0%
Set work level(%)=Motor
rated
current/Servo driver’s rated current×100
Asynchronous motor
Protection
Low-speed compensation & actual work level
P03.12
overload protection
0.1%
100.0%
×
coefficient
= set work level×(Output frequency/30HZ
parameter setting
×45+55)
Overload protection actual current= sampled
current/overload protection work level
Decided
Synchronous motor
by
P03.13
rated power
0.4~999.9kW
0.1kW
×
rated power
Machine
Type
122
Chapter IX Functional Code List
P03: Motor 1 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
Decided
Synchronous motor
by
P03.14
rated voltage
0~Servo driver’s rated voltage(P97.04)
1V
×
rated voltage
Machine
Type
Decided
Synchronous motor
by
P03.15
rated current
0.1~999.9A
0.1A
×
rated current
Machine
Type
Decided
Synchronous motor’s
Motor rated
0.01H
by
P03.16
1.00~1000.0Hz
×
rated frequency
frequency
z
Machine
Type
Synchronous motor
Motor pole
P03.17
1~40
1
2
×
pole pairs
pairs
Synchronous motor
rated rotation
P03.18
0~60000RPM
1RPM
1500RPM
×
rated speed
speed
Decided
Synchronous motor
stator
by
P03.19
0.00%~50.00%
0.01%
×
stator resistance
resistance%R1
Machine
Type
Decided
Synchronous motor
d-axis
0.1m
by
P03.20
0.0~999.9mH
×
d-axis inductance
inductance
H
Machine
Type
Decided
Synchronous motor
q-axis
0.1m
by
P03.21
0.0~999.9mH
×
q-axis inductance
inductance
H
Machine
Type
Synchronous motor
Back-EMF
P03.22
1000V/1000rpm
1
150
×
back-EMF constant
constant
Synchronous motor
position
Identify from 0→1, and change to 0 after
P03.23
1
0
×
position identification
identification
ending
Synchronous motor
Identify
P03.24
0~30%Motor rated current
1
10
×
identify current
current
Synchronous motor
P03.25
initial angle
0~FFFFH
1
0
×
initial angle
P03.26
Z pulse initial angle
Z pulse angle
0~FFFFH
1
0
×
20.0%~110.0%
Setting work level(%)=Motor rated
current/Servo driver’s rated current×100
synchronous motor
protective
Low-speed compensation & actual work level
P03.27
overload protection
0.1%
100.0%
×
coefficient
=Setting work level×(Output
coefficient setting
frequency/30HZ×45+55)
Overload protection and actual current=
sampled current/overload protection work level
P04: Motor 2 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
123
Chapter IX Functional Code List
P04: Motor 2 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
Decided
Asynchronous motor
by
P04.00
rated power
0.4~999.9kW
0.1kW
×
rated power
Machine
Type
Decided
0~Servo driver’s rated voltage(P97.04)
Asynchronous motor
by
P04.01
rated voltage
2 series: 220V
1V
×
rated voltage
Machine
4 series: 380V
Type
Decided
Asynchronous motor
by
P04.02
rated current
0.1~999.9A
0.1A
×
rated current
Machine
Type
Decided
Asynchronous
rated
0.01H
by
P04.03
motor’s rated
1.00~1000.0Hz
×
frequency
z
Machine
frequency
Type
Asynchronous motor
rated rotation
P04.04
0~60000RPM
1RPM
1440RPM
×
rated speed
speed
Decided
0.001~1.000
Asynchronous motor
by
P04.05
power factor
Used when calculating motor parameters as per
0.001
×
power factor
Machine
nameplates
Type
Decided
Asynchronous motor
Stator
by
P04.06
0.00%~50.00%
0.01%
×
stator resistance%R1
resistance%R1
Machine
Type
Decided
Asynchronous motor
Leakage
by
P04.07
leakage inductance
inductance
0.00%~50.00%
0.01%
×
Machine
resistance %X
resistance %X
Type
Decided
Asynchronous motor
Rotor
by
P04.08
0.00%~50.00%
0.01%
×
rotor resistance%R2
resistance%R2
Machine
Type
Decided
Asynchronous motor
mutual
by
P04.09
mutual inductance
inductance
0.0%~2000.0%
0.1%
×
Machine
resistance %Xm
resistance %Xm
Type
Decided
Asynchronous motor
no-load current
by
P04.10
0.1~999.9A
0.1A
×
no-load current I0
I0
Machine
Type
0: No action
Asynchronous motor
Parameters self
1: Action(Motor static)
P04.11
parameters self
1
0
×
tunning
2: Action(Motor rotation)
tunning
3: Reserved
124
Chapter IX Functional Code List
P04: Motor 2 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
20.0~110.0%
Setting work level(%)=Motor rated
Asynchronous motor
Protective
current/Servo driver’s rated current×100
P04.12
overload protection
0.1%
100.0%
×
coefficient
Low-speed compensation & actual work level
coefficient setting
=Setting work level×(Output
frequency/30HZ×45+55)
Asynchronous motor
Protective
Overload protection and actual current=
P04.12
overload protection
0.1%
100.0%
×
coefficient
Sampled current/overload protection work level
coefficient setting
Decided
Synchronous motor
by
P04.13
Rated power
0.4~999.9kW
0.1kW
×
rated power
Machine
Type
Decided
Synchronous motor
by
P04.14
rated voltage
0~Servo driver’s rated voltage(P97.04)
1V
×
rated voltage
Machine
Type
Decided
Synchronous motor
by
P04.15
rated current
0.1~999.9A
0.1A
×
rated current
Machine
Type
Decided
Synchronous motor’s
Motor rated
0.01H
by
P04.16
1.00~1000.0Hz
×
rated frequency
frequency
z
Machine
Type
Synchronous motor
Motor pole
P04.17
1~40
1
2
×
pole pairs
pairs
Synchronous motor
rated rotation
P04.18
0~60000RPM
1RPM
1500RPM
×
rated speed
speed
Decided
Synchronous motor
stator
by
P04.19
0.00%~50.00%
0.01%
×
stator resistance
resistance%R1
Machine
Type
Decided
Synchronous motor
d-axis
0.1m
by
P04.20
0.0~999.9mH
×
d-axis inductance
inductance
H
Machine
Type
Decided
Synchronous motor
q-axis
0.1m
by
P04.21
0.0~999.9mH
×
q-axis inductance
inductance
H
Machine
Type
Synchronous
Synchronous
P04.22
back-EMF
1000V/1000rpm
1
150
×
back-EMF constant
constant
Synchronous motor
position
Identify from 0→1, and change to 0 after
P04.23
position
1
0
×
identified
ending
identification
Synchronous motor
current
P04.24
0%~30%Motor rated current
1
10
×
identify current
identified
P04.25
Synchronous motor
initial angle
0~FFFFH
1
0
×
125
Chapter IX Functional Code List
P04: Motor 2 Parameters
Functio
Min
Chang
nal
Name
LCD Display
Setting Scope
Default
Unit
e
Code
initial angle
Synchronous motor
P04.26
Z pulse angle
0~FFFFH
1
0
×
Z pulse initial angle
20.0%~110.0%
Setting work level(%)=Motor rated
current/Servo driver’s rated current×100
Synchronous motor
protective
Low-speed compensation & actual work level
P04.27
overload protection
0.1%
100.0%
×
coefficient
=Setting work level×(Output
coefficient setting
frequency/30HZ×45+55)
Overload protection and actual current=
Sampled current/overload protection work level
Motor 2 PI
PI Parameters
0: The same as motor 1 PI Parameters
P04.28
1
0
×
Parameters option
option
1: Taken from P04.29~P04.32
P04.29
Motor 2 ASR-P
ASR1-P
0.1~200.0
0.1
20.0
○
P04.30
Motor 2 ASR-I
ASR1-I
0.010~1.000S
0.001s
0.200s
○
P04.31
Motor 2 ACR-P
ACR-P
1~5000
1
1000
○
P04.32
Motor 2 ACR-I
ACR-I
0.5~100.0ms
0.1
8.0
○
Motor 2 encoder
Motor 2 encoder
0: Local encoder
P04.33
1
1
×
option
option
1: Expansion encoder
P05: Start/close Control Parameters
Functio
Min
Defaul
Chang
nal
Name
LCD Display
Setting Scope
Unit
t
e
Code
0 Starting from starting frequency
1 First brake, then start from starting
P05.00
Start mode
Start mode
frequency
1
0
×
2 Rotation speed track, including direction
judgment before start
0.00H
P05.01
Start frequency
Start frequency
0.00~60.00Hz
0.01Hz
○
z
Start frequency holding
Start frequency
P05.02
0.00~10.00s
0.01s
0.00s
○
time
holding time
Start DC brake
P05.03
Start DC brake current
0.0%~100.0%Servo driver’s rated current
0.1%
0.0%
○
current
Start DC brake
0.00(No action)
P05.04
Start DC brake time
0.01s
0.00s
○
time
0.01~30.00s
0: deceleration stop
P05.05
Stop Mode
Stop Mode
1: Free to stop
1
0
×
2: deceleration stop+DC brake
Stop DC brake initial
Stop brake initial
0.00H
P05.06
0.00~60.00Hz
0.01Hz
○
frequency
frequency
z
Stop DC brake waiting
Stop brake
P05.07
0.00~10.00s
0.01s
0.00s
○
time
waiting time
Stop DC brake
P05.08
Stop DC brake current
0.0%~100.0%Servo driver’s rated current
0.1%
0.0%
○
current
Stop DC brake
0.0(No action)
P05.09
Stop DC brake time
0.01s
0.00s
○
time
0.01~30.00s
P05.10
Restart after power
Restart after
0: No action
1
0
×
126
Chapter IX Functional Code List
P05: Start/close Control Parameters
Functio
Min
Defaul
Chang
nal
Name
LCD Display
Setting Scope
Unit
t
e
Code
fault
power fault
1: Action
Waiting time for
Waiting time for restart
P05.11
restart after power
0.0~10.0s
0.1s
0.0s
○
after power fault
fault
0: Allow reverse
Anti-reverse
P05.12
Anti-reverse option
1: Forbid reverse(apply reverse run command
1
0
×
option
for 0-frequency run)
Forward-Reverse dead
Forward-Reverse
P05.13
0.00~360.00s
0.01s
0.00s
○
zone time
dead zone time
Forward -Reverse
Forward -Reverse
0: 0 frequency switch
P05.14
1
0
×
switch mode
switch mode
1: Over starting frequency switch
0.10H
P05.15
Stop speed
Stop speed
0.00~150.00Hz
0.01Hz
×
z
0: Speed value set(only the method for V/F
P05.16
Stop speed test
Stop speed test
mode)
1
0
×
1: Speed measure value
Stop speed delay
P05.17
Stop speed delay time
0.00~10.00S
0.01s
0.05s
×
time
Energy
Energy consumption
0: No action
P05.18
consumption
1
0
×
brake option
1: Action
brake option
Energy consumption
Brake service
P05.19
0.0~100.0%
0.1%
80.0%
○
brake service rating
rating
P06: V/F control Parameters
Functio
Chang
nal
Name
LCD Display
Setting Scope
Min Unit
Default
e
Code
0: User defines V/F curve
Motor 1V/F curve
Motor 1V/F curve
1: Square curve
P06.00
1
0
×
setting
setting
2: One point seven power curve
3: One point two power curve
Motor 1V/F frequency
Motor 1V/F frequency
P06.01
P06.03~P02.05
0.01Hz
0.00Hz
×
3
3
P06.02
Motor 1V/F voltage 3
Motor 1V/F voltage 3
P06.04~100.0%
0.1%
0.0%
×
Motor 1V/F frequency
Motor 1V/F frequency
P06.03
P06.05 ~P06.01
0.01Hz
0.00Hz
×
2
2
P06.04
Motor 1V/F voltage 2
Motor 1V/F voltage 2
P06.06~P06.02
0.1%
0.0%
×
Motor 1V/F frequency
Motor 1V/F frequency
P06.05
0.00~P06.03
0.01Hz
0.00Hz
×
1
1
P06.06
Motor 1V/F voltage 1
Motor 1V/F voltage 1
0~P06.04
0.1%
0.0%
×
P06.07
Motor 1 torque lift
Motor 1 torque lift
0.0%~30.0%
0.1%
0.0%
○
Motor 1 torque lift
Torque lift cut-off
P06.08
0.0%~50.0%(relative to P06.09)
0.1%
10.0%
○
cut-off point
point
Motor 1 base
P06.09
Base frequency
1.00~1000.0Hz
0.01Hz
50.00
×
frequency
Rated
Motor 1Max Output
value of
P06.10
Max Output voltage
0~480V
1V
×
voltage
servo
driver
127
Chapter IX Functional Code List
P06: V/F control Parameters
Functio
Chang
nal
Name
LCD Display
Setting Scope
Min Unit
Default
e
Code
P06.11
Motor 1 stable factor
Motor 1 stable factor
0~255
1
10
○
0: User defines V/F curve
Motor 2V/F curve
Motor 2V/F curve
1: Square curve
P06.12
1
0
×
setting
setting
2: One point seven power curve
3: 1.2 power curve
Motor 2V/F frequency
Motor 2V/F frequency
P06.13
P06.15~P02.05
0.01Hz
0.00Hz
×
3
3
P06.14
Motor 2V/F voltage 3
Motor 2V/F voltage 3
P06.16~100.0%
0.1%
0.0%
×
Motor 2V/F frequency
Motor 2V/F frequency
P06.15
P06.17 ~P06.13
0.01Hz
0.00Hz
×
2
2
P06.16
Motor 2V/F voltage 2
Motor 2V/F voltage 2
P06.18~P06.14
0.1%
0.0%
×
Motor 2V/F frequency
Motor 2V/F frequency
P06.17
0.00~P06.15
0.01Hz
0.00Hz
×
1
1
P06.18
Motor 2V/F voltage 1
Motor 2V/F voltage 1
0~P06.16
0.1%
0.0%
×
P06.19
Motor 2 torque lift
Motor 2 torque lift
0.0%~30.0%
0.1%
0.0%
○
Motor 2 torque lift
Torque lift cut-off
P06.20
0.0%~50.0%(relative to P06.21)
0.1%
10.0%
○
cut-off point
point
Motor 2 base
P06.21
Base frequency
1.00~1000.0Hz
0.01Hz
50.00
×
frequency
Rated
Motor 2Max Output
value of
P06.22
Max Output voltage
0~480V
1V
×
voltage
servo
driver
P06.23
Motor 2 stable factor
Motor 2 stable factor
0~255
1
10
○
0: No action
P06.24
AVR function
AVR function
1: Always action
1
1
×
2: No action in deceleration only
P07: Speed Control Parameters
Functi
onal
Name
LCD Display
Setting Scope
Min Unit
Default
Change
Code
Speed feedback
Speed feedback
0: Local encoder
P07.00
1
0
×
option
option
1: Expansion encoder
P07.01
ASR1-P
ASR1-P
0.1~200.0
0.1
20.0
○
P07.02
ASR1-I
ASR1-I
0.000~10.000S
0.001s
0.200s
○
P07.03
ASR1 output filter
ASR1 output filter
0~8(relative 0~2^8/10ms)
1
0
○
P07.04
ASR2-P
ASR2-P
0.1~200.0
0.1
20.0
○
P07.05
ASR2-I
ASR2-I
0.000~10.000S
0.001s
0.200s
○
P07.06
ASR2 output filter
ASR2 output filter
0~8( relative0~2^8/10ms)
1
0
○
ASR1/2 switch
ASR1/2 switch
P07.07
0.0%~100.0%
0.1
10.0%
○
frequency
frequency
0: forward limit value from channel 1, Reverse limit
value from channel 2
P07.08
Speed limit mode
Speed limit mode
1
0
×
1: Use channel 1 for normal/reverse limit
2: Reserved
Speed limit channel
Speed limit
0: Speed limit value 1
P07.09
1
0
×
1
channel 1
1: AI given
Speed limit channel
Speed limit
0: Speed limit value 2
P07.10
1
0
×
2
channel 2
1: AI given
128
Chapter IX Functional Code List
P07: Speed Control Parameters
Functi
onal
Name
LCD Display
Setting Scope
Min Unit
Default
Change
Code
P07.11
Speed limit value 1
Speed limit value 1
0.0%~100.0%
0.1%
100.0%
○
P07.12
Speed limit value 2
Speed limit value 2
0.0%~100.0%
0.1%
100.0%
○
0: Deceleration stop
Speed deviation
P07.13
DEV action select
1: Free to stop, report E034
1
2
×
(DEV) action select
2: Continue to action
P07.14
DEV test value
DEV test value
0%~50.0%
0.1%
20.0%
×
P07.15
DEV test time
DEV test time
0.0~10.0S
0.1S
10.0
×
Overspeed action
Overspeed action
0: Deceleration stop
P07.16
1
1
×
select
select
1: Free to stop, report E035
2: Continue to run
Over speed(OS)
Over speed test
P07.17
0.0%~130.0%
0.1%
120.0%
×
test value
value
Over speed(OS)
Over speed test
P07.18
0.0~2.00
0.01s
0.10
×
test time
time
P07.19
Pre-excitation time
Pre-excitation time
0.0~10.0s
0.1
0.0
×
P07.20
Reserved
Reserved
10~400
1
100
×
P07.21
Reserved
Reserved
0~2
1
0
×
P07.22
Reserved
Reserved
10~100
1
10
×
Field weaken
Low magnetic
P07.23
500~1200
1
1024
○
control coefficient
control coefficient
Min flux given
Min flux given
P07.24
10%~80%
1%
10%
×
value
value
P07.25
Reserved
Reserved
10~100
1
50
×
P08: Torque Control
C
Functio
Min
ha
nal
Name
LCD Display
Setting Scope
Default
Unit
ng
Code
e
Speed/torque
Speed/torque
0: Speed control mode
P08.00
1
0
×
control mode
option
1: Torque control mode
Torque instruction
Torque
0: Torque given
P08.01
1
0
×
option
instruction option
1: Torque current given
0: AI given
1: Terminal PULSE given
Torque given
P08.02
Torque given option
2: Serial port comm. given
1
0
×
option
3: Process close-loop output
4: Reserved
Given torque filter
Given torque
P08.03
0~65535ms
1
0
×
time
filter time
Speed→torque
Speed/torque
P08.04
0~300.0% initial torque
0.1%
100.0%
×
switch point
switch point
Speed torque switch
Speed torque
P08.05
0~1000ms
1
0
×
delay
switch delay
0: Limit invalid: current limit only, limit to the max
overload current allowed of drive;
Torque limit
1: Torque limit: Torque limit for constant torque area,
P08.06
Torque limit mode
1
3
×
mode
current limit for constant power area;
2: Power limit: Current limit for constant torque area,
output capacity limit for constant power area;
129
Chapter IX Functional Code List
3: Torque current limit: Torque limit for constant
torque area, output capacity limit for constant power
area;
0: Limit channel 1, same limit for 4 quadrants
1: Motor mode use channel 1,regen mode use channel
2
Torque limit
Torque limit
P08.07
2: Upper limit use limit channel 1, lower limit use
1
1
×
channel option
channel option
channel 2
3: Same limit for 4 quadrants, torque limit channels 1
and2 are switched by terminal
0: Torque limit value 1
Torque limit
Torque limit
1: AI given
P08.08
1
0
×
channel 1
channel 1
2: Terminal PULSE given
3: Process close-loop output
0: Torque limit value 2
Torque limit
Torque limit
1: AI given
P08.09
1
0
×
channel 2
channel 2
2: Terminal PULSE given
3: Process close-loop output
Torque limit value
P08.10
Torque limit value 1
0.0%~+300.0%
0.1%
180.0%
○
1
Torque limit value
P08.11
Torque limit value 2
0.0%~+300.0%
0.1%
180.0%
○
2
Mechanical loss
Mechanical loss
P08.12
-20.0%~+20.0%
0.1%
0.0%
×
compensation value
compensation
P08.13
Torque bias T1
Torque bias T1
-300.0%~+300.0%
0.1%
0.0%
×
P08.14
Torque bias T2
Torque bias T2
-300.0%~+300.0%
0.1%
0.0%
×
P08.15
Torque bias T3
Torque bias T3
-300.0%~+300.0%
0.1%
0.0%
×
Torque bias start
Torque bias
P08.16
0.00~1.00S
0.01S
0.00
×
time delay
start time delay
0: Over torque/less torque: invalid test
1: With consistent speed, after over torque detection,
continue to action;
2: During the run after torque detection, continue to
run;
3: With consistent speed, after over torque detection,
cut off the output;
Over torque/less
4: During the run, after over torque detection, cut off
Torque detection
P08.17
torque detection
the output;
1
0
×
action 1
action option1
5: With consistent speed, after over torque detection,
continue to run;
6: During the run, after less torque detection,
continue to run;
7: With consistent speed, after less torque detection,
cut off the output;
8: During the run, after less torque detection,
continue to run;
0.0%~300.0%
Over torque/Less
Torque test
0.0%~300.0%
P08.18
0.1
0
×
torque test value1
value1
SVC: Relative to motor rated torque
V/F: Relative driver rated current
P08: Torque control
C
Functio
Min
ha
nal
Name
LCD Display
Setting Scope
Default
Unit
ng
Code
e
130
Chapter IX Functional Code List
Over torque/Less
P08.19
Torque test time1
0.0~10.0s
0.1
0.0s
×
torque test time 1
0: Over torque/Less torque detection: invalid
1: With consistent speed, after over torque detection,
continue to work;
2: During the work, after less torque detection,
continue to work;
3: With consistent speed, after less torque detection,
cut off the output;
Over torque/Less
4: During the work, after less torque detection,
Torque detection
P08.20
torque detection
continue to work;
1
0
×
option 2
option 2
5: With consistent speed, after less torque detection,
cut off the output;
6: During the run, after less torque detection,
continue to run;
7: With consistent speed, after less torque detection,
cut off the output;
8: During the run, after less torque detection,
continue to run;
0.0~300.0%
Over torque/Less
Torque test
P08.21
SVC: Relative motor rated torque
0.1%
0.0%
×
torque test value2
value2
V/F: Relative driver rated current
Over torque/Less
P08.22
Torque test time2
0.0~10.0s
0.1
0.0s
×
torque test time2
P09: Servo Control
Functio
Chang
nal
Name
LCD Display
Setting Scope
Min Unit
Default
e
Code
0: Non-Servo control
Servo control switch
1: Speed/Torque←→Servo control
P09.00
Servo control option
1
0
×
option
2: Servo←→Speed/Torque control
3: Servo control
0: Normal run
P09.01
Servo run mode option
Servo run mode option
1: Reserved
1
0
×
2: Spindle run
Ones place: Position zero point
option
0: Z pulse position
1: Photoswitch position
Tens place:
Accelerating/Deceleration time
option
0~3: Accelerating /Deceleration
Orientation mode of
Orientation mode of
P09.02
time 1~4
1
0010H
×
spindle
spindle
Hundreds place: Run after position
completion
0: Keep at the position point
1: Keep within the position scope
Thousands place: position
calculation mode
0: Position loop
1: Position loop+ feedforward
0: Terminal pulse given
1: Reserved
P09.03
Position given source
Position given source
1
0
×
2: Expansion PG given
3: Position digital given
131
Chapter IX Functional Code List
4: Reserved
Pulse given input mode
Pulse given input mode
0: A/B phase pulse
P09.04
1
0
×
option
option
1: PLUS+SIGN pulse
Position digital given
P09.05
High position given
0~150
1
0
○
high position
Position digital given
P09.06
Low position given
0~65535
1
0
○
low position
P09.07
Reserved
Reserved
Reserved
1
0
○
Position given filtering
Position command
P09.08
0.0~3000.0ms
0.1ms
10.0ms
○
time constant
filtering time
P09.09
Reserved
Reserved
Reserved
○
Numerator of position
P09.10
Numerator of position
1~65535
1
1024
×
instruction ratio
Denominator of
P09.11
position instruction
Denominator of position
1~65535
1
1024
×
ratio
Position completed
Command
P09.12
Position completed range
0~10000
10
○
range
unit
Width of position
Width of position
Command
P09.13
1~32767
100
○
approach
approach
unit
Position
Position out-of-tolerance
Command
P09.14
out-of-tolerance
0~32767
1000
○
detection range
unit
detection range
Position
Position out-of-tolerance
P09.15
out-of-tolerance alarm
0: Valid; 1: Invalid
1
0
○
alarm option
option
Spindle transmission
Spindle transmission
P09.16
0.000~30.000
0.001
1.000
×
ratio
ratio
P09.17
Reserved
Reserved
Reserved
0.01
5.00
○
P09.18
Reserved
Reserved
Reserved
1
0
P09.19
Orientation speed
Orientation speed
0.00~200.00Hz
0.01
5.00
×
Starting position of
Starting position of
P09.20
0~30000
1
0
spindle orientation
spindle orientation
Orientation
Orientation Deceleration
P09.21
0~3000.0
0.1s
10.0
×
Deceleration time
time
Orientation positioning
Orientation positioning
P09.22
0~30000
1
0
×
1
1
Orientation positioning
Orientation positioning
P09.23
0~30000
1
0
×
2
2
Orientation positioning
Orientation positioning
P09.24
0~30000
1
0
×
3
3
Orientation positioning
Orientation positioning
P09.25
0~30000
1
0
×
4
4
P09.26
Position loop gain 1
Position loop gain 1
1~8000
1Hz
50
○
P09.27
Position loop gain 2
Position loop gain 2
1~8000
1Hz
200
○
0: No switch ;
Position gain 1 and
1~2: Reserved
P09.28
Gain 1/2 switch mode
1
0
○
gain 2 switch mode
3: Position DEV
4: External terminal switch
P09.29
Reserved
Reserved
Reserved
○
P09.30
Reserved
Reserved
Reserved
○
132
Chapter IX Functional Code List
Position gain switch
Gain switch Position
1 command
P09.31
0~10000
100
○
Position DEV level
DEV
unit
Gain switch smoothing
Gain switch smoothing
P09.32
0~100ms
1ms
1
○
time
time
Speed feedforward
100.00
P09.33
Speed feedforward gain
0.00~120.00%
1.00%
○
gain
%
Position controller
P09.34
Position loop limit
0~100.0%Max frequency
0.1%
0.0%
○
output limit
0: Emergency stop by torque limit
P09.35
Servo stop mode
Servo stop mode
1: Stop by switching to speed
1
0
○
control
P10: Switch Input /Output Terminal
Functio
Chang
nal
Name
LCD Display
Setting Scope
Min Unit
Default
e
Code
0: No function
1: Multiplex frequency Terminal 1
2: Multiplex frequency Terminal 2
3: Multiplex frequency Terminal 3
4: Multiplex frequency Terminal 4
5: Accelerating/Deceleration time
Terminal 1
6: Accelerating /Deceleration time
Terminal 2
X1 Terminal
7: External fault normally open Input
function
8: External fault normally closed Input
X2 Terminal
9: External reset(RESET) Input
function
10: External Jog Forward Run control
X3 Terminal
Input
function
11: External Jog Reverse Run control
X4 Terminal
Input
P10.00
function
Input Terminal X1~X8
12: Free stop Input (FRS)
~P10.0
X5 Terminal
function option
13: Frequency increase instruction(UP)
7
function
14: Frequency decrease instruction
X6 Terminal
(DOWN)
function
15: Simple PLC pause instruction
X7 Terminal
16: Accelerating/Deceleration disable
function
instruction
X8
Terminal
17: Three-line operation control
function
18: External break normally open
contact input
19: External break normally closed
contact input
20: Stop DC break Input instruction
21: Process close-loop disable
22: PLC disable
23: Main setting frequency source
option1
24: Main setting frequency source
133
Chapter IX Functional Code List
option2
25: Main setting frequency source
option3
26: Main setting frequency switch to
AI
27: Command switch to terminal
28: Command source option1
29: Command source option2
30: Multiplex Process close-loop given
Terminal 1
31: Multiplex Process close-loop given
Terminal 2
32: Multiplex Process close-loop given
Terminal 3
33: Multiplex Process close-loop given
Terminal 4
34: Traverse frequency input
35: Traverse frequency reset
36: External Stop command(valid for
all control modes, stop under current
stop mode)
37: Servo driver run disable
38: Forward disable
39: Reverse disable
40: Auxiliary setting frequency clear
41: PLC stop memory remove
42~44: Reserved
45: Main setting frequency pulse input
1
00
×
(for X8 setting only)
46: Auxiliary setting frequency pulse
input )(for X8 setting only)
47: PG speed measuring input (for X8
setting only)
48: Reserved
49: Reserved
50: Reserved
51: Pre-excitation command terminal
52: Reserved
53: Reserved
54: Speed control and torque control
switch terminal
55: Reserved
56: Torque limit channel1, 2 option
57: Reserved
58: Torque bias option Terminal 1
59: Torque bias option Terminal 2
Combination of status switch’s three
torque bias values
60: AI torque bias hold
Hold torque bias AI input value
61: Torque limit 1 pulse input
Terminal (for X8 setting only)
62: Torque limit 2 pulse input
Terminal (for X8 setting only)
63: Torque given pulse input Terminal
(for X8 setting only)
134
Chapter IX Functional Code List
P10: Switch Input/Output Terminal
Functi
onal
Name
LCD Display
Setting Scope
Min Unit
Default
Change
Code
64~70: Reserved
71: Position pulse direction( for X7 only)
72: Position pulse Input (for X8 only)
X1 Terminal
73: Position DEV counter clear
function
74: Given pulse disable
X2 Terminal
75: Reserved
function
76: Reserved
X3 Terminal
77: Spindle orientation start
function
78: Position option Terminal 1
X4 Terminal
79: Position option Terminal 2
P10.00
Input Terminal
function
80: Reserved
~P10.
X1~X8 function
1
00
×
X5 Terminal
81: Servo control switch Terminal
07
option
function
82: Reserved
83: Position reference point input terminal
X6 Terminal
(for X6,X7 X8 only)
function
84: Spindle orientation return to zero
X7 Terminal
85~87: Reserved
function
88: Motor 1 and 2 switch terminal
X8 Terminal
Display only under shortcut menu function
function
numbers:
0,7,8,9,10,11,12,13,14,17,18,19,20,26,27,3
5,37,45,46,47,48
0: Two-line control mode 1
1: Two-line control mode 2
2: Three-line operation control 1-self
FWD/REV
holding function(Add any terminal from
P10.08
operation mode
Run control mode
1
0
×
X1~X8 )
setting
3: Three-line operation control 2-self
holding function(Add any terminal from
X1~X8 )
Terminal UP
Terminal UP
P10.09
0.01~99.99Hz/s
0.01
1.00
○
accelerated speed
accelerated speed
Terminal DOWN
Terminal DOWN
P10.10
Deceleration
Deceleration
0.01~99.99Hz/s
0.01
1.00
○
speed
speed
X8 pulses per
X8 pulses per
P10.11
1~9999
1
1024
×
revolution
revolution
Terminal filtering
Terminal filtering
P10.12
0~500ms
1
10
○
time
time
0.1~100.0(Max 100k)
Max Input pulse
P10.13
Max Input pulse
Valid only for X8 option high-speed pulse
0.1kHz
10.0
○
frequency
input
0: No center
1: With center, center: (P10.13)/2,
frequency if less than center, shall be
Pulse given center
P10.14
Pulse given center
positive
1
0
○
option
2: With center, center: (P10.13)/2,
frequency, if more than center, shall be
positive.
Pulse given
Pulse given
P10.15
0.00~10.00s
0.01s
0.05
○
filtering time
filtering time
135
Chapter IX Functional Code List
Binary system setting
0: Normal logic, valid onstate
1: Adverse logic, valid break
LED Ones place:
Input terminal
Input terminal
P10.16
BIT0~BIT3: X1~X4
1
000
○
valid state setting
valid state setting
LED Tens place:
BIT0~BIT3: X5~X8
LED Hundreds place:
BIT0~BIT1: FWD,REV
P10: Switch Input/Output Terminal
Functi
onal
Name
LCD Display
Setting Scope
Min Unit
Default
Change
Code
Binary system setting
0: Invalid
1: Valid
LED Ones place:
P10.1
Virtual Input
Virtual Input
BIT0~BIT3: X1~X4
1
000
○
7
Terminal setting
Terminal setting
LED Tens place:
BIT0~BIT3: X5~X8
LED Hundreds place:
BIT0~BIT1: FWD,REV
0: Servo driver run signal (RUN)
1: Frequency arrival signal (FAR)
2: Non-zero speed signal
Output terminal
Output terminal
P10.1
3: Frequency level test signal (FDT1)
Y1 of open
Y1 of open
1
00
×
8
collector
collector
4: Frequency level test signal (FDT2)
5: Overload detection signal (OL)
6: Stop due to under voltage (LU)
7: External fault stop(EXT)
8: Frequency upper limit (FHL)
9: Frequency lower limit (FLL)
10: Servo driver run at zero speed
Output terminal
Output terminal
P10.1
11: Simple PLC stage running completion
Y2 of open
Y2 of open
1
01
×
9
collector
collector
indices
12: PLC recycle completion indication
13: Traverse frequency upper/lower limit
14: Encoder direction output
15: Servo driver run prepared (RDY)
16: Servo driver fault
17: Upper computer switch signal
18: Reserved
Output function
19: Torque limit
P10.2
BR function
option of relay
1
15
×
0
option
Torque command value limited by torque
BR
limit value 1 or 2 limit
20: Flux test signal
Flux test value over P10.37 shall be valid
21: Reserved
136
Chapter IX Functional Code List
22: Valid analog torque bias
23: Over torque/Less torque output1
24: Over torque/Less torque output2
25: Position completed
26: Position accessed
1
16
×
27: Reserved
28: Position out of tolerance warning
P10.2
Output function
29: Reserved
T function option
1
option of relay T
30: Reserved
31: Reserved
32: Reserved
33: Reserved
34: Servo driver normal/reverse indication
terminal
1
16
×
35: Motors 1 and 2 indication terminal
Display only under shortcut menu function
numbers: 0,1,4,5,6,7,8,9,15,16
Binary system setting
0: Valid onstate
P10.2
Output terminal
Output terminal
1: Valid break
1
0
○
2
valid state setting
valid state setting
LED Ones place:
BIT0~BIT3: Y1,Y2,BR,T
P10.2
Relay BR output
BR output time
0.1~10.0s
0.1s
0.1
○
3
time delay
delay
P10.2
Relay T output
T output time
0.1~10.0s
0.1s
0.1
○
4
time delay
delay
Frequency
P10.2
Frequency arrive
arrive(FAR)detect
0.00~1000.0Hz
0.01Hz
2.50Hz
○
5
detection width
ion width
0: Speed setting
P10.2
FDT1 detection
FDT1 detection
value(accelerated/decelerated frequency
1
0
○
6
mode
mode
command)
1: Speed test value
P10.2
FDT1 level
FDT1 level
0.00~1000.0Hz
0.01Hz
50.00Hz
○
7
P10.2
FDT1 lag
FDT1 lag
0.00~1000.0Hz
0.01Hz
1.00Hz
○
8
0: Speed setting
P10.2
FDT2 detection
FDT2 detection
value(Accelerated/decelerated frequency
1
1
○
9
mode
mode
command)
1: Speed test value
P10.3
FDT2 level
FDT2 level
0.00~1000.0Hz
0.01Hz
25.00Hz
○
0
P10.3
FDT2 lag
FDT2 lag
0.00~1000.0Hz
0.01Hz
1.00Hz
○
1
137
Chapter IX Functional Code List
0: No function
1: Output frequency
2: Setting frequency(0~Max Output
frequency)
3: Output current(0~2*Iei)
4: Output current(0~3*Iem)
5: Output torque(0~3*Tem)
6: Output Torque current(0~3*Tem)
7: Motor rotation speed(0~Max Output
frequency)
8: Output voltage(0~1.5*Ve)
9: Adjusted AI1(-10~10V/4~20mA)
P10.3
DO Terminal
Digit output
10: Adjusted AI2(-10~10V/4~20mA)
1
00
○
2
output
11: Adjusted AI3(-10~10V)
12: Output power(0~3*Pe)
13: Torque limit value 1(0~3Tem)
14: Torque limit value 2(0~3Tem)
15: Torque bias (0~3Tem)
16: Torque given(0~3Tem)
17:
Host
machine
expanded
function(0~65535)
18: Encoder frequency division output
19: Expansion percent output
Display only under shortcut menu function
numbers: 0~8
P10.3
Max output
Max output
0.1~100.0(Max 100.0k)
0.1kHz
10.0
○
3
pulse frequency
pulse
0: No center
1: With center, center: (P10.33)/2,
frequency if less than center, shall be
P10.3
Pulse output
Pulse output
positive
1
0
○
4
center option
center option
2: With center, center: (P10.33)/2,
frequency if more than center, shall be
positive
P10.3
Pulse output
Pulse output
0.00~10.00s
0.01s
0.05
○
5
filtering time
filtering time
P10.3
Flux test value
Flux test value
10.0%~100.0%
0.1%
100.0%
○
6
P10.3
Zero speed
Zero speed
0.0%~100.0%Max frequency
0.1%
1.0%
○
7
threshold
threshold
P10.3
Reserved
Reserved
-
-
-
8
P11: analog Input /output Terminal
Functio
nal
Name
LCD DISPLAY
Setting Scope
Min Unit
Default
Change
Code
Ones place: AI1
0: voltage Input
1: Current Input
Analog input type
Analog input type
P11.00
Tens place: AI2
0: voltage Input
1
00
×
option
option
1: Current Input
AI3: differential voltage Input
0: No function
AI1 function
P11.01
AI1 function option
1: Main setting frequency given
1
00
×
option
2: Auxiliary setting frequency setting
138
Chapter IX Functional Code List
P11:
analog Input /output Terminal
Functio
nal
Name
LCD DISPLAY
Setting Scope
Min Unit
Default
Change
Code
3: Torque bias
4: Speed limit value 1
5: Speed limit value 2
6: Torque limit value 1
7: Torque limit value 2
8: Torque command( given)
9~11: Reserved
12: Output voltage bias (V/F mode)
13: Output voltage(V/F mode)
Display only under shortcut menu
function numbers: 0,1,9
P11.02
AI1 zero bias
AI1 zero bias
-100.0%~100.0%
0.1%
0.0%
○
P11.03
AI1 gain
AI1 gain
-10.00~10.00
0.01
1.00
○
P11.04
AI1 filtering
AI1 filtering
0.01~10.00s
0.01s
0.05
○
0: Center at bias
AI1 zero bias
AI1 zero bias
1: Lower than bias, equal to bias
P11.05
1
0
×
correction mode
correction mode
2: Higher than bias, equal to bias
3: Take absolute value centered at bias
AI2 function
P11.06
AI2 function option
As given in P11.01
1
00
×
option
P11.07
AI2 zero bias
AI2 zero bias
-100.0%~100.0%
0.1%
0.0%
○
P11.08
AI2 gain
AI2 gain
-10.00~10.00
0.01
1.00
○
P11.09
AI2 filtering
AI2 filtering
0.01~10.00s
0.01s
0.05
○
AI2 zero bias
AI2 zero bias
P11.10
As given in P11.05
1
0
×
correction mode
correction mode
AI3 function
P11.11
AI3 function option
As given in P11.01
1
00
×
option
P11.12
AI3 zero bias
AI3 zero bias
-100.0%~100.0%
0.1%
0.0%
○
P11.13
AI3 gain
AI3 gain
-10.00~10.00
0.01
1.00
○
P11.14
AI3 filtering
AI3 filtering
0.01~10.00s
0.01s
0.05
○
AI3 zero bias
AI3 zero bias
P11.15
As given in P11.05
1
0
×
correction mode
correction mode
LED Ones place: AO1 option
0: 0~10V
1: 0~20mA
2: 2~10V
3: 4~20mA
P11.16
Analog output type
Analog output type
1
00
○
LED Tens place: AO2 option
0: 0~10V
1: 0~20mA
2: 2~10V
3: 4~20mA
139
|
||
|
|
|