1. AXIS CONTROL
B-64693EN-1/01
- 98 -
- When a A1000S sensors which is separate pulsecoder is used as a separate detector.
- A scale without rotary data
For the following detectors, these are "a scale without rotary data". The following detectors are not all of the detector which is "a scale without rotary data".
- HEIDENHAIN
RCN223F / RCN727F
- Magnescale
RU77
- MITSUBISHI HEAVY INDUSTRIES
MPRZ Series
- RENISHAW
RESOLUTE (rotary encoder)
NOTE Please make sure to confirm the using detector to the detector manufacturers.
- Coordinate systems at power-on (1) The machine and workpiece coordinate systems are automatically set. When bit 3 (PPD) of parameter No. 3104 is set to 1, the relative position display is preset. When parameter PPD is set to 0, it is also possible to preset relative coordinates with machine coordinates by setting bit 5 (PWR) of parameter No. 11277 to 1. (2) The amount of shift by coordinate system setting (G92 for the M series or G50 for the T series) or local coordinate system setting (G52) is cleared.
- Setting the zero point of an absolute position detector In the following cases, set the zero point of an absolute position detector (bring the counter value of the absolute position detector into correspondence with the reference position): •
Primary adjustment is performed (after the reference position is determined). •
The reference position is changed. •
An absolute position detector is replaced with another. •
A servo motor is replaced with another. •
Alarm DS0300 is issued. •
The file memory is replaced with another. •
Parameter data is cleared. To set the zero point of an absolute position detector, the following two methods are available: One method using manual reference position return and the other using MDI operation.
- Manual reference position return Follow the procedure below to perform manual reference position return. (1) Set bit 4 (APZ) of parameter No. 1815 to 0. Alarms PW0000 and DS0300 are displayed. (2) Turn the power off, then on again. Alarm DS0300 is displayed. (3) Perform manual reference position return. When manual reference position return is completed, bit 4 (APZ) of parameter No. 1815 is automatically set to 1. (4) Press the reset button to release alarm DS0300. Operation in step (3) can also be performed by reference position setting without DOG, reference point setting with mechanical stopper, or reference point setting with mechanical stopper by grid method.
- Setting the zero point using MDI operation Follow the procedure below to set the zero point using MDI operation. (1) Set bit 4 (APZ) of parameter No. 1815 to 0. Alarms PW0000 and DS0300 are displayed. (2) Turn the power off, then on again. Alarm DS0300 is displayed. (3) Move the tool to the reference position in jog, manual handle, or manual incremental feed. (4) Set bit 4 (APZ) of parameter No. 1815 to 1. Alarm PW0000 is displayed. |