39

SPECIFICATIONS

Polaris Lubricants and Maintenance 
Products  

ENGINE OIL

PART NUMBER

DESCRIPTION

2879383

Polaris 5W-30 Generator Oil
(1 Quart) (32 oz.)

GREASE / SPECIALIZED LUBRICANTS

2871329

Dielectric Grease (Nyogel™)

ADDITIVES

2871326

Premium Carbon Clean / Fuel Stabilizer 
(12 oz.) (12 count)

40

SPECIFICATIONS

Modified coefficient table of ambient condition power 

The conditions of generator rated output:

Altitude: 0 m Ambient temperature: 25°C Relative humidity: 30%

Ambient modified coefficient: C (Relative humidity 30%)

Altitude

(m)

Ambient temperature (

°

C)

25

30

35

40

45

0

1

.98

.96

.93

.90

500

.93

.91

.89

.87

.84

1000

.87

.85

.82

.80

.78

2000

.75

.73

.71

.69

.66

3000

.64

.62

.6

.58

.56

4000

.54

.52

.5

.48

.46

Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P

N

 =5KW, altitude is 1000m, ambient N

temperature is 35°C relative humidity is 80%, the rated power of generator is:
P=P

N

 X (C-0.02) = 5 X (0.82-0.02) = 4KW

41

WIRE DIAGRAM

43

TROUBLESHOOTING

TROUBLESHOOTING

Troubleshooting Symptoms

Engine Will Not Turn Over

Engine Turns Over, but Will Not Start

Engine Lacks Power

POSSIBLE CAUSE

SOLUTION

Starter recoil damage

Take the generator to an authorized Polaris servicing 
dealer or refer to the service manual

Internal engine damage

Take the generator to an authorized Polaris servicing 
dealer or refer to the service manual

POSSIBLE CAUSE

SOLUTION

Out of fuel

Refuel 

Water is present in the fuel

Drain the fuel system and refuel 

Old or non-recommended fuel

Drain the fuel system and refuel 

Fouled or defective spark plug

Inspect spark plug and replace as needed 

No spark to spark plug

Inspect spark plug, verify engine switch is ON 

Water or fuel in crankcase

Take the generator to an authorized Polaris servicing 
dealer or refer to the service manual

Mechanical failure

Take the generator to an authorized Polaris servicing 
dealer or refer to the service manual

Low Oil

Repeat Pre-operation inspection

POSSIBLE CAUSE

SOLUTION

Air filter restricted

Clean or replace air filter(s) 

Bad fuel; generator stored without treating or draining 
gasoline, or refueled with bad gasoline

Drain the fuel system and refuel 

Mechanical failure

Take the generator to an authorized Polaris servicing 
dealer or refer to the service manual

 

 

 

 

 

 

 