Technical specifications
7.3 Machine control panels
7.3
Machine control panels
Table 7-2
Machine control panels
Safety
Safety class
III; PELV according to EN 50178
Degree of protection ac-
Front side IP54
Rear side IP00
cording to
DIN EN 60529
Approvals
CE / UL
Electrical data
Input voltage
24 VDC
Power consumption, max.
2 W (without illuminated customer keys)
Mechanical data
Dimensions (mm)
Width:
Height:
Depth
Milling MCP: 49
465.9
412.4
(without additive in-
Turning MCP: 78
stallation ele-
ments):
Weight
5 kg
Tightening torques, max.
Standard
Weld studs/sockets
M3:
0.8 Nm
0.5 Nm
M4:
1.8 Nm
1 Nm
M5:
3 ... 6 Nm
1.5 Nm
Mechanical ambient condi-
Operation
Transport
tions (with PCU)
(in transport packaging)
Vibratory load
10 - 58 Hz: 0.075 mm
5 - 58 Hz: 0.075 mm
58 - 500 Hz: 9.8 m/s2
58 - 500 Hz: 9.8 m/s2
according to EN 60721-3-3
according to EN 60721-3-2
Shock load
50 m/s2, 30 ms,
100 shocks
according to DIN EN 60068-2-27
Climatic ambient conditions
Heat dissipation
By natural convection
Moisture condensation and
Not permissible
ice formation
Supply air
Without aggressive gases, dusts, and oils
Use and operation
Applicable standards
EN 60721-3-3
Climate class
Based on 3K3
Temperature limits
0 ... 40 ºC
Temperature change
Max. 30 K/h
Limits for relative humidity
5 ... 90% / ≤ 25 g/m3
Permissible change in the
Max. 6%/h
relative air humidity
ERGOline Stage 3
44
Manual, 02/2018, 6FC5397-4FP40-0BA1
Spare parts
8
8.1
Overview
The table provides an overview of the spare parts available for the machine control panels.
Name
Description
Quantity
Order number
Handwheel
For turning machine control panel
1
6FC9320-5DM00
Feedrate / rapid tra-
Electronic rotary switch 1x23G, T=32, cap, knob, pointer, rap-
1
6FC5247-0AF13-1AA0
verse override
id traverse and feedrate dials
Feedrate / rapid tra-
Electronic rotary switch 1x29G, T=32, cap, knob and pointer
1
6FC5247-0AF14-1AA0
verse override
Rotary knob
Cap, knob and pointer for override rotary switch
10
6FC5248-0AF31-0AA0
Key caps with label
- 90, ergo-gray
1 set
6FC5248-0AF12-0AA0
fields
- 20 each of red/green/yellow/mid-gray
Labeled key caps
For turning version
1 set
6FC5248-0AF25-0AA0
Labeled key caps
For milling version
1 set
6FC5248-0AF26-0AA0
8.2
Replacement
8.2.1
Handwheel
Removing the handwheel
1. Loosen the grub screw ① of the rotary knob ⑥.
2. Pull the rotary knob off the axle.
3. Loosen the fastening nut M15 ②.
4. Remove the washer.
5. Pull the handwheel backward out of the front plate.
6. Release the wiring.
ERGOline Stage 3
Manual, 02/2018, 6FC5397-4FP40-0BA1
45
Spare parts
8.2 Replacement
① Grub screw (hexagon socket-head screw) - not visible
② Fastening nut M15 and washer
③ Handwheel axle
④ Connecting terminals
⑤ Gasket
⑥ Rotary knob
Figure 8-1
Mounting kit for the handwheel
Installing the handwheel
Installation is performed in the reverse order.
Make sure the gasket is correctly seated ⑤.
Connection
Note
When a connected handwheel triggers pulses from its idle position or in the event of tiny
contacts, connect it so that the label is facing the wrong way.
Exchange
- The wire of terminal A with the wire of terminal /A
- The wire of terminal B with the wire of terminal /B
The pin assignments of the handwheel interfaces can be found in Section COM board IE
MCP (Page 24).
8.2.2
Rotary switch
Removing the rotary switch
1. Pry off the cap ③ from the rotary knob ② (snap on connection).
2. Remove the nut of collet ① with a wrench (size 10).
ERGOline Stage 3
46
Manual, 02/2018, 6FC5397-4FP40-0BA1
Spare parts
8.2 Replacement
3. Pull off the complete rotary knob
②.
4. Loosen the lock nut ⑤ on the axle of the rotary switch ④ with a wrench (size 14).
5. Remove the connector at the end of the rotary switch cable from the slot.
6. Remove the rotary switch.
① Nut of the collet
② Rotary knob
③ Cap
④ Rotary switch axle
⑤ Fastening nut
⑥ Scale
Figure 8-2
Removing a rotary switch
Installing the rotary switch
1. Push the O-ring ① onto the axle of the new rotary switch as a gasket.
2. Insert the rotary switch into the front cutout so that pressure is applied to the O-ring.
3. Screw the lock nut ④ onto the rotary switch axle from the front with a wrench (size 14)
(tightening torque: 3 Nm).
4. Connect the arrow ring ③ and the rotary knob ⑤.
5. Push both parts onto the axle of the rotary switch.
6. Align the arrow point on the ring with position "0" on the scale.
7. Tighten the collet nut of the rotary knob by hand and using a torque wrench tighten to a
torque of 2 Nm.
ERGOline Stage 3
Manual, 02/2018, 6FC5397-4FP40-0BA1
47
Spare parts
8.2 Replacement
8. Place the cap
② on the rotary knob and snap it into position.
9. Fold and fasten the connecting cable ⑦ as shown in the diagram on the left.
;
① O-ring
Detail diagram of the connection plug
② Cap
③ Arrow ring
④ Fastening nut
⑤ Rotary knob
⑥ Connection plug
⑦ Connection cable
⑧ Connection board
⑨ COM board
Figure 8-3
Installing a rotary switch
The pin assignments of the rotary switch interfaces can be found in Section COM board IE
MCP (Page 24).
Proceed in the same way to install the second rotary switch.
NOTICE
Damage to the components through incorrect installation of the rotary switches
● It is essential that the specified tightening torques are complied with.
● Make sure that the connection cable is cleanly folded as in the figure and lay it so that it
does not come into contact with any chafing edges.
ERGOline Stage 3
48
Manual, 02/2018, 6FC5397-4FP40-0BA1
Accessories
9
The following accessories are available for the machine control panels:
Component
Description
Quantity
Order number
For universal use
1
6XV1840-2AH10
Ethernet cables
Trailable
1
6XV1840-3AH10
Ethernet connector
180°
1
6GK1901-1BB10-2AA0
ERGOline Stage 3
Manual, 02/2018, 6FC5397-4FP40-0BA1
49
Fundamental safety
1
instructions
2
Description
Operator control and display
3
elements
SINUMERIK
4
Dimension drawings
SINUMERIK 840D sl
Operator panel fronts: TOP 1500,
5
Assembly
TOP 1900, TOP 2200
Connection
6
Manual
7
Networking
Service and maintenance
8
9
Technical data
Spare parts / accessories
10
11
Safety symbols
Valid for:
Control system
SINUMERIK 840D sl/840DE sl
05/2019
A5E43201322B AB
Table of contents
1
Fundamental safety instructions
5
1.1
General safety instructions
5
1.2
Equipment damage due to electric fields or electrostatic discharge
8
1.3
Warranty and liability for application examples
8
1.4
Industrial security
9
1.5
Residual risks of power drive systems
11
2
Description
13
2.1
Overview
13
2.2
Interfaces
14
2.3
Rating plate
15
3
Operator control and display elements
17
3.1
View
17
3.2
Using the operator panel front
17
3.3
Activating the screensaver
19
4
Dimension drawings
21
5
Assembly
23
5.1
Permitted mounting positions
23
5.2
Mounting cut-out
25
5.3
Positioning the mounting clips for IP65-compliant installation
25
5.4
Attaching the mounting clips
27
6
Connection
31
6.1
Pin assignment of the interfaces
31
6.1.1
Power supply
31
6.1.2
USB interfaces
31
6.1.3
Ethernet RJ45 interface
33
7
Networking
35
7.1
System settings
35
7.1.1
Thin Client Unit (TCU)
35
7.1.2
Settings for SINUMERIK solution line
36
7.1.3
System boot with system network
38
7.1.4
Factory default settings
39
7.2
Commissioning TCU
41
7.2.1
Key assignment
41
7.2.2
Settings in the "TCU.ini" file
42
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
3
Table of contents
7.2.3
Displacement mechanism for TCUs
43
7.2.4
Disable switchover between TCU via PLC
44
7.2.5
Example: How to select the behavior of the TCUs during boot up
47
7.3
Network configuration
48
7.3.1
Permissible network topologies
48
7.3.2
Networks without connection to the company network
49
7.3.2.1
Configuration 1: NCU and TCU
49
7.3.3
Networks with NCU connection to the company network
50
7.3.3.1
Configuration 2: NCU and TCU
50
7.3.3.2
Configuration 3: PCU/IPC with TCU on NCU
51
7.3.3.3
Connecting the programming device (PG) to the NCU
52
7.3.4
Example: Configuring a VNC connection to a PC
52
7.4
Service and diagnostics
54
7.4.1
Using the TCU's main menu
54
7.4.2
Operating the TCU menu "Service sessions"
57
7.4.3
Operating the TCU menu "Service menu"
59
7.4.4
Operating the TCU menu "Modify settings"
62
7.4.5
Operating the menu for a new TCU or spare part TCU
63
7.4.6
How to register a TCU on the system network
68
7.4.7
This is how you register a spare part TCU
71
7.4.8
Booting of the operator panel front
72
7.4.8.1
Messages during booting
72
7.4.8.2
Diagnostics options during booting
73
8
Service and maintenance
75
9
Technical data
77
9.1
Technical data
77
9.2
Supplementary electrical conditions
79
9.2.1
Power supply
79
9.2.2
Grounding concept
80
9.2.3
RI suppression measures
81
9.2.4
SINUMERIK_SouthKorea_Note
82
9.3
Standards and approvals
82
9.4
Recycling and disposal
82
10
Spare parts / accessories
83
11
Safety symbols
85
Index
87
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
4
Manual, 05/2019, A5E43201322B AB
Fundamental safety instructions
1
1.1
General safety instructions
WARNING
Electric shock and danger to life due to other energy sources
Touching live components can result in death or severe injury.
● Only work on electrical devices when you are qualified for this job.
● Always observe the country-specific safety rules.
Generally, the following six steps apply when establishing safety:
1. Prepare for disconnection. Notify all those who will be affected by the procedure.
2. Isolate the drive system from the power supply and take measures to prevent it being
switched back on again.
3. Wait until the discharge time specified on the warning labels has elapsed.
4. Check that there is no voltage between any of the power connections, and between any of
the power connections and the protective conductor connection.
5. Check whether the existing auxiliary supply circuits are de-energized.
6. Ensure that the motors cannot move.
7. Identify all other dangerous energy sources, e.g. compressed air, hydraulic systems, or
water. Switch the energy sources to a safe state.
8. Check that the correct drive system is completely locked.
After you have completed the work, restore the operational readiness in the inverse sequence.
WARNING
Electric shock due to connection to an unsuitable power supply
When equipment is connected to an unsuitable power supply, exposed components may
carry a hazardous voltage. Contact with hazardous voltage can result in severe injury or death.
● Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV-
(Protective Extra Low Voltage) output voltages for all connections and terminals of the
electronics modules.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
5
Fundamental safety instructions
1.1 General safety instructions
WARNING
Electric shock due to equipment damage
Improper handling may cause damage to equipment. For damaged devices, hazardous
voltages can be present at the enclosure or at exposed components; if touched, this can result
in death or severe injury.
● Ensure compliance with the limit values specified in the technical data during transport,
storage and operation.
● Do not use any damaged devices.
WARNING
Electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
● As a minimum, connect cable shields and the cores of cables that are not used at one end
at the grounded housing potential.
WARNING
Electric shock if there is no ground connection
For missing or incorrectly implemented protective conductor connection for devices with
protection class I, high voltages can be present at open, exposed parts, which when touched,
can result in death or severe injury.
● Ground the device in compliance with the applicable regulations.
WARNING
Spread of fire from built-in devices
In the event of fire outbreak, the enclosures of built-in devices cannot prevent the escape of
fire and smoke. This can result in serious personal injury or property damage.
● Install built-in units in a suitable metal cabinet in such a way that personnel are protected
against fire and smoke, or take other appropriate measures to protect personnel.
● Ensure that smoke can only escape via controlled and monitored paths.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
6
Manual, 05/2019, A5E43201322B AB
Fundamental safety instructions
1.1 General safety instructions
WARNING
Unexpected movement of machines caused by radio devices or mobile phones
When radio devices or mobile phones with a transmission power > 1 W are used in the
immediate vicinity of components, they may cause the equipment to malfunction.
Malfunctions may impair the functional safety of machines and can therefore put people in
danger or lead to property damage.
● If you come closer than around 2 m to such components, switch off any radios or mobile
phones.
● Use the "SIEMENS Industry Online Support app" only on equipment that has already been
switched off.
WARNING
Fire due to inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent fire
and smoke. This can cause severe injury or even death. This can also result in increased
downtime and reduced service lives for devices/systems.
● Ensure compliance with the specified minimum clearance as ventilation clearance for the
respective component.
NOTICE
Overheating due to inadmissible mounting position
The device may overheat and therefore be damaged if mounted in an inadmissible position.
● Only operate the device in admissible mounting positions.
WARNING
Unexpected movement of machines caused by inactive safety functions
Inactive or non-adapted safety functions can trigger unexpected machine movements that
may result in serious injury or death.
● Observe the information in the appropriate product documentation before commissioning.
● Carry out a safety inspection for functions relevant to safety on the entire system, including
all safety-related components.
● Ensure that the safety functions used in your drives and automation tasks are adjusted and
activated through appropriate parameterizing.
● Perform a function test.
● Only put your plant into live operation once you have guaranteed that the functions relevant
to safety are running correctly.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
7
Fundamental safety instructions
1.3 Warranty and liability for application examples
Note
Important safety notices for Safety Integrated functions
If you want to use Safety Integrated functions, you must observe the safety notices in the Safety
Integrated manuals.
1.2
Equipment damage due to electric fields or electrostatic discharge
Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules
or devices that may be damaged by either electric fields or electrostatic discharge.
NOTICE
Equipment damage due to electric fields or electrostatic discharge
Electric fields or electrostatic discharge can cause malfunctions through damaged individual
components, integrated circuits, modules or devices.
● Only pack, store, transport and send electronic components, modules or devices in their
original packaging or in other suitable materials, e.g conductive foam rubber of aluminum
foil.
● Only touch components, modules and devices when you are grounded by one of the
following methods:
- Wearing an ESD wrist strap
- Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring
● Only place electronic components, modules or devices on conductive surfaces (table with
ESD surface, conductive ESD foam, ESD packaging, ESD transport container).
1.3
Warranty and liability for application examples
Application examples are not binding and do not claim to be complete regarding configuration,
equipment or any eventuality which may arise. Application examples do not represent specific
customer solutions, but are only intended to provide support for typical tasks.
As the user you yourself are responsible for ensuring that the products described are operated
correctly. Application examples do not relieve you of your responsibility for safe handling when
using, installing, operating and maintaining the equipment.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
8
Manual, 05/2019, A5E43201322B AB
Fundamental safety instructions
1.4 Industrial security
1.4
Industrial security
Note
Industrial security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement - and continuously maintain - a holistic, state-of-the-art industrial
security concept. Products and solutions from Siemens constitute one element of such a
concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the Internet if and to the extent such a connection is necessary and
only when appropriate security measures (e.g. using firewalls and/or network segmentation)
are in place.
For additional information on industrial security measures that can be implemented, please
visit:
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they become
available, and that only the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase customer’s exposure
to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed at:
Further information is provided on the Internet:
Industrial Security Configuration Manual (https://support.industry.siemens.com/cs/ww/en/
view/108862708)
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
9
Fundamental safety instructions
1.4 Industrial security
WARNING
Unsafe operating states resulting from software manipulation
Software manipulations, e.g. viruses, Trojans, or worms, can cause unsafe operating states
in your system that may lead to death, serious injury, and property damage.
● Keep the software up to date.
● Incorporate the automation and drive components into a holistic, state-of-the-art industrial
security concept for the installation or machine.
● Make sure that you include all installed products into the holistic industrial security concept.
● Protect files stored on exchangeable storage media from malicious software by with
suitable protection measures, e.g. virus scanners.
● On completion of commissioning, check all security-related settings.
● Protect the drive against unauthorized changes by activating the "Know-how protection"
converter function.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
10
Manual, 05/2019, A5E43201322B AB
Fundamental safety instructions
1.5 Residual risks of power drive systems
1.5
Residual risks of power drive systems
When assessing the machine- or system-related risk in accordance with the respective local
regulations (e.g., EC Machinery Directive), the machine manufacturer or system installer must
take into account the following residual risks emanating from the control and drive components
of a drive system:
1.
Unintentional movements of driven machine or system components during commissioning,
operation, maintenance, and repairs caused by, for example,
- Hardware and/or software errors in the sensors, control system, actuators, and cables
and connections
- Response times of the control system and of the drive
- Operation and/or environmental conditions outside the specification
- Condensation/conductive contamination
- Parameterization, programming, cabling, and installation errors
- Use of wireless devices/mobile phones in the immediate vicinity of electronic
components
- External influences/damage
- X-ray, ionizing radiation and cosmic radiation
2.
Unusually high temperatures, including open flames, as well as emissions of light, noise,
particles, gases, etc., can occur inside and outside the components under fault conditions
caused by, for example:
- Component failure
- Software errors
- Operation and/or environmental conditions outside the specification
- External influences/damage
3.
Hazardous shock voltages caused by, for example:
- Component failure
- Influence during electrostatic charging
- Induction of voltages in moving motors
- Operation and/or environmental conditions outside the specification
- Condensation/conductive contamination
- External influences/damage
4.
Electrical, magnetic and electromagnetic fields generated in operation that can pose a risk
to people with a pacemaker, implants or metal replacement joints, etc., if they are too close
5.
Release of environmental pollutants or emissions as a result of improper operation of the
system and/or failure to dispose of components safely and correctly
6.
Influence of network-connected communication systems, e.g. ripple-control transmitters or
data communication via the network
For more information about the residual risks of the drive system components, see the relevant
sections in the technical user documentation.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
11
Description
2
2.1
Overview
NOTICE
Observe the EMC-compatible installation of the components
The components provided by Siemens meet CE requirements. Make sure that the
components continue to meet the requirements once installed.
The SINUMERIK TOP XX00 operator panel front has a touch-sensitive glass surface with
multiple finger operator control. The integrated TCU enables the panel front and control to be
installed separately.
The panel is linked to the PCU/IPC/NCU via Ethernet as thin client in a dedicated subnet (via
DHCP server on the PCU/IPC/NCU). The distance to the panels is determined by the maximum
distance between two network nodes / access points (100 m). Mixed operation with several
TCUs and one panel directly on the PCU/IPC is possible.
Validity
The following description applies to the following components:
Type
Description
Article number
SINUMERIK
15.6" operator panel front as thin client, with touch
6FC5303-0AF18-0AA0
TOP 1500
screen
SINUMERIK
18.5" operator panel front as thin client, with touch
6FC5303-0AF21-0AA0
TOP 1900
screen
SINUMERIK
21.5" operator panel front as thin client, with touch
6FC5303-0AF20-0AA0
TOP 2200
screen
Features
The following are integrated in the operator panel front:
Characteristic
SINUMERIK TOP
SINUMERIK TOP
SINUMERIK TOP
1500
1900
2200
Screen size in inches
15.6
18.5
21.5
Resolution in pixels
1366 x 768
1920 x 1080
Display
LED backlight
Brightness, typ. in cd/m2
220
250
190
Multiple finger operation in the
Yes
screen area (gesture opera-
tion possible)
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
13
Description
2.2 Interfaces
Characteristic
SINUMERIK TOP
SINUMERIK TOP
SINUMERIK TOP
1500
1900
2200
USB interfaces
3 USB interfaces at the rear according to 2.0 Specification:
● 3x USB Hi-Speed, max. respective current carrying capacity
500 mA
● Max. total current carrying capacity of all USB interfaces: 1.5 A
Ethernet
2 x Ethernet 10/100/1000 Mbit/s
TCU
Thin client unit (TCU) for connection to the operator panel
Degree of protection
IP65 (on the front)
2.2
Interfaces
The figure shows the position of the interfaces on the rear of the operator panel front:
① X203
USB Hi-Speed (type A socket)
② X204
USB Hi-Speed (type A socket)
③ X213
USB Hi-Speed (type A socket)
④ X201, X202 Ethernet, RJ45 socket 10/100/1000 Mbit/s
⑤ X206
24 V power supply, 3-pin terminal (screw type) with a connection for grounding of
the enclosure
⑥
Protective conductor connection
Figure 2-1
Interfaces of the panel
The following special requirements apply for the connecting cables:
● The 24 V cable must be approved for temperatures up to 70° C.
● Select the permitted conductor cross-section in accordance with the national regulations
(NEC, VDE, etc.) from 1.3 mm2 (AWG 16) to 3.3 mm2 (AWG 12). The basis for this can be
the output current of the 24 V supply or the overcurrent protection device used in the 24 V
circuit. If the 24 V power supply unit that is used has a short-circuit current greater than 50 A,
a corresponding overcurrent protection device, which is limited to this value, must be used
upstream of the product.
● Strip the cables (7 mm) for connection to the 24 V plug.
● Flame resistance of the 24 V cable according to UL 2556 VW-1/ tested according to IEC
60332-1-2.
● Observe the permissible bending radii of the cables.
● Only rotate the panel in a way that does not cause pinching of the cables.
● Route all of the cables in such a way that they do not come into contact with chafing edges.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
14
Manual, 05/2019, A5E43201322B AB
Description
2.3 Rating plate
WARNING
Warning for areas subject to NEC or CEC:
Safety notice for connectors with Ethernet marking:
A Ethernet or Ethernet segment, with all its associated interconnected equipment, shall be
entirely contained within a single low-voltage power distribution and within a single building.
The Ethernet is considered to be in an "environment A" according IEEE802.3 or "environment
0" according IEC TR 62102, respectively.
Never make direct electrical connection to TNV-circuits (Telephone Network) or WAN (Wide
Area Network).
2.3
Rating plate
SIEMEN
S
SINUMERIK
TOP 1500
1P 6FC5303-0AF18-0AA0
FS: 01
A5E338404023
s T-J66028844
Supply 24V
1,7A
Protection:
refer to user manual
00-1F-F8-30-11-D9
4,3 kg
LISTED
PROG. CNTLR
E164110
Siemens AG, Frauenauracher Str. 80, DE 91056 Erlangen
Made in Germany
① Material number
② Component name
③ Article number
④ Serial number
⑤ MAC address
Figure 2-2
Example graphic of a nameplate
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
15
Description
2.3 Rating plate
Note
Different contents of the rating plates
The contents of the individual rating plate fields on the panel may differ from those described
in this manual (e.g. new product version, approvals and markings not yet issued).
Note
Product code scanning
The product code contains the article number of the device. Scan the product code with the aid
of the Siemens Industry Online Support App to be taken directly to the Internet Webpage for the
product, including all of the technical information and graphical data.
The app is available for iPhone, iPad, Android and Windows Phone.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
16
Manual, 05/2019, A5E43201322B AB
Operator control and display elements
3
3.1
View
The figure below shows the TOP 1900 as example:
① Recesses for each mounting clip
② Display with touch screen
Figure 3-1
Front and side view of the SINUMERIK operator panel front TOP1900
Display unit:
●
15", 19" or 22" LED display
Note
Pixel error according to DIN EN ISO 9241-307, Error class II.
3.2
Using the operator panel front
The operator panel front is operated through finger contact with the touch-sensitive glass
surface:
● Depending on the application-specific functions shown in the display area, for example, by:
- pressing a softkey or a displayed button
- Gestures with up to 5 fingers
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
17
Operator control and display elements
3.2 Using the operator panel front
WARNING
Unexpected machine movements caused by incorrect operation
Incorrect operation of devices with a touch screen can lead to unexpected machine
movements. This can result in death, serious injury and material damage.
● Prevent unintentional incorrect operation by appropriate configuration of the user
interface, e.g. by placing the buttons for starting and stopping machine components far
enough apart.
● Configure the machine so that safety-related functions are not operated with the touch
screen.
Note
Notes on operation of the touch-sensitive glass surface with multi-finger operation function
using gestures
Observe the following notes in order to avoid incorrect operation of the touch-sensitive glass
surface with multi-finger operation function. Otherwise, entries made at the device will either be
incorrectly identified/implemented - or not at all.
● The SINUMERIK TOP XX00 does not support safety-relevant functions and these may also
not be implemented in the touch-sensitive glass user interface.
● The touch-sensitive glass surface reacts to contact with its surface, not to pressure.
Therefore, do not subsequently attach a protective film to the touch-sensitive glass surface.
Also remove all protective and packaging films, as these have a negative impact/prevent
data from being entered and initiate incorrect operator entries.
● Only operate the touch-sensitive glass user interface with your finger tips.
● Touch the touch-sensitive glass surface either perpendicularly or at a maximum angle of 45°
to the surface.
● Note that the SINUMERIK TOP XX00 is not intended for continuous use as a workstation
screen.
● Avoid unintentional multiple touches, e.g. with the knuckles or by leaning on or against the
display.
● Make sure that the surface of the touch-sensitive glass screen is free of dirt.
Always check whether the executed operator actions have been recognized by the device.
Note
Note the valid C standards for the particular machine type (e.g. for turning machines: EN ISO
23125-2010, pages 36 and 49). This states that a button that initiates motion with the protective
door open must be implemented using an additional acknowledgment device; this is because
for single-channel keyboards generally no PL (performance level) level "d" can be achieved.
Displaying the TCU menu
To display the TCU menu, simultaneously touch the left-hand and right-hand lower corner of
the active display area in order to display the TCU menu.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
18
Manual, 05/2019, A5E43201322B AB
Operator control and display elements
3.3 Activating the screensaver
Gloves
You can wear thin gloves made of cotton or gloves for touch-sensitive glass user interfaces with
capacitive contact function when operating the touch-sensitive glass user interface.
You can wear the following gloves for operating the touch-sensitive glass user interface of the
operator panel front:
● Dermatril L
● Camatril Velours Art. 730
● Uvex Profas Profi ENB 20A
● Comasec PU 900 (4342)
● Camapur Comfort Antistatic type 619
● KCL Men at Work Art. 301
● Carex Art. 1505/k (leather)
● Reusable gloves, medium, white, cotton: BM Polyco
Note
The gloves listed above are recommendations only. The type designations can change.
Information about third-party software used
This product contains open source software. License information can be obtained via the
shortcut "License files" on your SINUMERIK PCU desktop, or navigate to the SINUMERIK
Operate Readme OSS path "Setup/system data: System CF card/siemens/oss-license" on
your SINUMERIK NCU and read the appropriate OSS file for this device.
3.3
Activating the screensaver
If an image with high contrast is displayed without change for longer than one hour, the dark-ON
function must be activated for energy efficiency reasons.
You can adapt the time individually. Further information can be found in the manual
"Commissioning of Basic Software and Operating Software, SINUMERIK Operate (IM9)".
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
19
Operator control and display elements
3.3 Activating the screensaver
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
20
Manual, 05/2019, A5E43201322B AB
Dimension drawings
4
Figure 4-1
Front, side and top view of the operator panel front
TOP 1500
TOP 1900
TOP 2200
①
257
294
331
②
398
464
529
③
239
276
313
④
141
⑤
18.2
37
⑥
380
446
511
⑦
249
⑧
32
65
97
⑨
87
⑩
25.4
⑪
8.9
All dimensions in mm
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
21
Dimension drawings
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
22
Manual, 05/2019, A5E43201322B AB
Assembly
5
5.1
Permitted mounting positions
The device offers the following mounting options:
● Mounting cabinets
● Control cabinets
● Switchboards
● Consoles
In the following, all of these mounting options are referred to by the general term "cabinet".
The device is self-ventilated and approved for inclined mounting at angles up to +/-35° in
stationary cabinets.
NOTICE
Damage due to overheating
Inclined installation reduces the convection by the device and therefore the maximum
permitted ambient temperature for operation.
If there is sufficient forced ventilation, the device can also be operated in the inclined mounting
position up to the maximum permitted ambient temperature for vertical installation. The device
may otherwise be damaged and its certifications and warranty will be rendered null and void.
For information on permitted ambient temperatures, refer to the section Technical data
(Page 77).
Selecting the mounting position
Select one of the approved mounting positions for your device. The following mounting
positions are possible:
● Horizontal mounting
● Vertical mounting (only possible with TOP 2200)
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
23
Assembly
5.1 Permitted mounting positions
Mounting in horizontal format
All devices are suitable for horizontal mounting positions.
r&
r&
0 °C
r&
r&
r&
r&
rದ r
rದ r
A maximum ambient temperature of +50° C is permitted for vertical mounting of the TOP 1500
and TOP 1900 (0° angle of inclination); a maximum temperature of +40° C for inclined
mounting.
A maximum ambient temperature of +45° C is permitted for vertical mounting of the TOP 2200.
Mounting in vertical format
You can also install the TOP 2200 vertically.
r&
0 °C
r&
r&
r&
rದ r
rದ r
r&
A maximum ambient temperature of +40° C is permissible for vertical mounting (0° tilt angle);
a maximum of +35° C is permitted for inclined mounting.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
24
Manual, 05/2019, A5E43201322B AB
Assembly
5.3 Positioning the mounting clips for IP65-compliant installation
5.2
Mounting cut-out
Size of the mounting cut-out for the installation of devices in horizontal format:
Table 5-1
Device
Width (mm)
Height (mm)
Installation depth + ventilation clearance
(mm)
TOP 1500
382 + 1
241 + 1
78 + 10
TOP 1900
448 + 1
278 + 1
78 + 10
TOP 2200
513 + 1
315 + 1
78 + 10
The operator panel front is fastened using the supplied mounting clips. When using clip
fastening, holes or threaded holes are not required.
This mounting method also provides IP65 degree of protection if the mounting panel
corresponds to the requirements specified in the dimension drawing. The seal (PU foam seal)
to the mounting panel is already provided on the operator panel front.
5.3
Positioning the mounting clips for IP65-compliant installation
Fasten the device with 12 mounting clips from the accessory kit; they are also available as
accessories.
See also Section "Accessories (Page 83)".
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
25
Assembly
5.3 Positioning the mounting clips for IP65-compliant installation
To achieve IP65 degree of protection for the device, the mounting clips must be affixed at the
positions listed below.
Device
Position
TOP 1500
TOP 1900
TOP 2200
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
26
Manual, 05/2019, A5E43201322B AB
Assembly
5.4 Attaching the mounting clips
Degree of protection IP65
The party setting up the system is responsible for proper mounting of the device.
WARNING
Risk of electric shock
If the device is not installed correctly, the degree of protection cannot be ensured. Humidity or
water can penetrate the device and cause an electric shock or destroy the system.
The IP65 degree of protection is only ensured for the front of the device if the following
requirements are met:
● Fasten the device with mounting clips.
● The continuous seal is correctly affixed for the correct size of the cut-out.
● Please follow the specifications for the dimensions in Section Dimension drawings
(Page 21).
5.4
Attaching the mounting clips
WARNING
Electric shock in the event of an individual error when grounding is insufficient
If the panel is installed with inadequate grounding in an environment with hazardous voltages,
this may cause an electric shock in the event of an individual error. This can result in death,
serious injury and material damage.
Adequately ground the conductive parts of the panel in accordance with the nationally
applicable regulations. When dimensioning the protective conductor connection, note the fuse
ratings of the electrical circuits with hazardous voltages, which would have an effect in
possible individual error scenarios.
WARNING
Unexpected machine movements caused by defective grounding
A defective or non-existent ground connection can lead to malfunction of the touch screen.
The malfunction can trigger an unexpected machine movement, or a machine movement can
no longer be stopped.
Ground the touch screen with the shortest possible cable with a minimum conductor cross-
section of 2.5 mm².
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
27
Assembly
5.4 Attaching the mounting clips
WARNING
Parasitic voltage
If the device is installed with inadequate insulation in an environment with higher/more
hazardous voltages, parasitic voltages may occur. This can result in death, serious injury and
material damage.
Insulate the cables appropriately for the highest voltage coming into consideration.
The safety of a system with an integrated operator panel front is the responsibility of the system
installer.
The installation is performed in accordance with the installer's instructions.
Observe all the relevant information from this manual regarding installation.
Requirements
● All packaging components and protective films have been removed from the device.
● The mounting clips included in the accessory kit are to hand.
● Slotted screwdriver, blade 0.5 x 3 mm.
Procedure
NOTICE
Damage to the glass front
Do not use suction grippers to lift the glass front in order to avoid damage.
Note
Compliance with the degree of protection is not guaranteed in the case of damage
If the mounting seal is damaged, the degree of protection is not guaranteed.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
28
Manual, 05/2019, A5E43201322B AB
Assembly
5.4 Attaching the mounting clips
To fasten the device with mounting clips, proceed as follows:
1. Working from the front, insert the device into the mounting cut-out. Secure the device to
prevent it from falling out.
&OLFN
[
2. Ensure that all four spring fasteners at the top and bottom of the device are fully latched in
position. At a position that is not fully latched into position, press the device again carefully
into the mounting cut-out, if necessary.
3. Insert a mounting clip into the cutout provided on the device. Make sure it is in the correct
position; see the section "Positioning the mounting clips for IP65-compliant installation
(Page 25)".
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
29
Assembly
5.4 Attaching the mounting clips
4. Tighten the threaded pin to secure the mounting clip. The maximum torque when tightening
the threaded pins of the mounting clips is 0.5 Nm.
&OLFN
5. Repeat steps 3 and 4 until all mounting clips are fastened.
6. Check the fit of the mounting seal.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
30
Manual, 05/2019, A5E43201322B AB
Connection
6
6.1
Pin assignment of the interfaces
The pins of the component interfaces are assigned as specified in the tables below. Any
deviations are indicated at the relevant point.
Signal type
I
Input
O
Output
B
Bidirectional (inputs/outputs)
V
Power supply
-
Ground (reference potential) or N.C. (not connected)
6.1.1
Power supply
Connector type:
Terminal block, 3-pin contact strip, screw type
Total cable length:
30 m
Table 6-1
Assignment of the power supply interface
Pin
Name
Type
Meaning
1
P24 (+)
24 VDC potential (20.4 to 28.8 VDC)
2
M24 (-)
0 V
V/V/-
3
Functional earth
Connection for grounding the hous-
ing
6.1.2
USB interfaces
The USB interfaces are implemented as sockets and comply with the generally valid standard.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
31
Connection
6.1 Pin assignment of the interfaces
In principle, USB interfaces have the following characteristics:
● Integrated power supply up to 500 mA for each socket.
● Maximum cable length 3 m (Length including the supply cable to the hub and the connected
terminal device; only 1 hub is permitted. Note that some keyboards already have a hub.)
Note
Cables that are too long can result in malfunctions or faults on the screen
Observe the following restrictions for the USB front interface for connecting operator panels
to the keyboard, mouse or USB FlashDrive:
● Maximum cable length: 1.8 m
● Extension cables: Not permitted
● Hot-plugging-capable devices are connected during operation and are identified
automatically.
Note
Correct identification is only guaranteed for USB I/Os that comply to 100% with the USB
specification.
Table 6-2
Assignment of the USB interface
Type A socket
Pin
Name
Type
Remark
1
P5V_fused
V
+ 5 V (fused)
2
Data-
Data -
B
3
Data+
Data +
4
GND
V
Ground (reference potential)
USB sticks
If you want to connect a USB flash drive to the USB interface, you can use a USB flash drive
of any memory size. It must, however, meet the following minimum requirements:
● File system: FAT16 or FAT32
● Partitioning: only in PC partition format (MBR)
USB sticks that deviate from these requirements have not been tested and may not be
recognized by the NCU.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
32
Manual, 05/2019, A5E43201322B AB
Connection
6.1 Pin assignment of the interfaces
6.1.3
Ethernet RJ45 interface
Connector type:
Standard RJ45 socket
Max. data transmission rate:
10/100/1000 Mbit/s
Max. cable length:
100 m
Table 6-3
Assignment of the Ethernet RJ45 interface 1000 Mbit/s
Connector
Pin
Name
Type
Remark
1
DA+
B
Bidirectional pair A+
2
DA-
Bidirectional pair A-
3
DB+
Bidirectional pair B+
4
DC+
Bidirectional pair C+
/('
/('
5
DC-
Bidirectional pair C-
6
DB-
Bidirectional pair B-
7
DD+
Bidirectional pair D+
8
DD-
Bidirectional pair D-
Shield
-
-
On connector housing
-
Green LED
-
Illuminated orange: 1000 Mbit/s
(right)
Off: No or faulty connection
-
Orange LED
-
Illuminated: Data exchange
(left)
Off: No data exchange
Note
Connection is only possible on LAN, not on telecommunication networks.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
33
Connection
6.1 Pin assignment of the interfaces
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
34
Manual, 05/2019, A5E43201322B AB
Networking
7
7.1
System settings
7.1.1
Thin Client Unit (TCU)
TCU overview
The Thin Client Unit (TCU) for the distributed configuration permits spatial separation of the
SINUMERIK operator panel front (OP/TP) and the SINUMERIK PCU/SIMATIC IPC or NCU.
With SINUMERIK solution line, the TCU is used to visualize the user interface of the PCU 50,
SIMATIC IPC for SINUMERIK with PCU basic software or NCU.
One TCU can be connected to multiple PCUs/IPCs/NCUs. All TCUs and PCUs/IPCs/NCUs
that are connected to one other via a Gigabit switch form the "system network". The user
interface of a PCU/IPC/NCU is copied to several OPs each with one TCU. This means that all
TCUs display the same screen. Operator actions can only be performed on one TCU at a time.
This TCU then has user authorization. The PCU can also have its own OP connected directly
to it.
The classic operator panel fronts can be used with an IPC 427E if a TCU is available.
The following diagram shows a configuration example for a distributed topology:
6,180(5,.
' VO
2SHUDWRU SDQHOV ZLWK 7&8V 0&3V DQG (0V
3&8
+7
6,0$7,& ,3&
*LJDELW VZLWFK
The mobile SINUMERIK HT 8 handheld terminal works on the thin client principle and
combines the functions of an operator panel with a machine control panel.
The configuration and cabling of the whole system based on a permissible configuration is
described in Section "Network configurations (Page 48)".
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
35
Networking
7.1 System settings
Supplementary conditions
The following supplementary conditions apply for the operation of a TCU:
● In the system network, the number of active thin clients is limited:
- A maximum of 2 TCUs: NCU 710.3 PN
- A maximum of 4 TCUs: NCU 720.3 PN or NCU 730.3 PN
- A maximum of 4 TCUs: PCU/IPC
Any number of TCUs can be operated in the system network.
● CompactFlash Cards cannot be used on the TCU.
● A 16 bit or 32 bit depth of color setting may be selected.
● If a PC keyboard is connected to the TCU, it is not possible to ensure that all special keys,
e.g. multi-media keys, will be transferred to the software of the NCU/PCU/IPC.
● Machine control panels connected via a PROFIBUS network are not supported for
switchover.
● Distributed memory media that are connected to the TCU via USB can be used.
● The TOP Panels must be networked on the basis of the Gigabit standard, e.g. Gigabit switch
or Ethernet cable according to CAT 6 or higher.
7.1.2
Settings for SINUMERIK solution line
Fundamentals
The system network for SINUMERIK solution line is structured as a star topology with a central
Ethernet switch, to which all Ethernet-based components of the system are connected.
For an NCU, the connection is via the X120 Ethernet socket, for an IPC/PCU, it is via the
"Ethernet 2" or "X2" or "X2 P1" connection. There is no default for all other components with two
Ethernet connections. These components have an internal 2-port switch and may be used to
connect an additional operator component. Thus, in this case, there can be deviations from the
strict star topology.
System network
In the system network, the IP address 192.168.214.xxx with subnet mask 255.255.255.0 is pre-
selected. Here there is precisely one DHCP server with DNS that can run on one NCU or one
PCU/IPC. The server ensures assignment of IP addresses to the Ethernet components in the
system network (DHCP clients) from a specified address band.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
36
Manual, 05/2019, A5E43201322B AB
Networking
7.1 System settings
The following rules apply for assignment of IP addresses in the system network:
● For all NCUs and/or PCUs/IPCs, the commissioning engineer assigns fixed IP addresses in
the associated address bands, as well as appropriate computer names (host names). All
other operator components are automatically assigned an IP address by the DHCP server.
Its name is generated automatically (for MCP, MPP, HT 8), or is entered at commissioning
(TCU).
● If there are multiple NCUs, IPCs and/or PCUs in the system network, depending on the boot
sequence, the system automatically specifies the DHCP server and automatically ensures
synchronization of all necessary data, so that the next time the system boots any other NCU,
IPC, or PCU could take on the role of DHCP server. However it is better to specify a DHCP
master. This is an NCU, IPC, or PCU in the system network that is available on each system
boot and which regularly takes over the task of the DHCP server and DNS server.
Synchronization of data takes place in any event so that any other NCU, IPC, or PCU can
take over this task, unless you deactivate this option in the DHCP configuration. All non-
master NCUs/IPCs/PCUs wait while the system boots for a preset time for the master to
become available.
Note
In a system network or on a boot server, i.e. on the NCU, IPC, or PCU that accommodates
the active DHCP server, a maximum of 30 operator stations may be operated
simultaneously with the TCU.
A maximum of 10 operator stations with a TCU may connect up simultaneously with the
same HMI application when powering up.
Connection to a company network
Each NCU can be connected via X130, and each PCU/IPC can be connected via "Ethernet 1"
to a company network. The company network is used to exchange operating software with
servers or to execute part-programs directly from servers in the company network. Company
network and system network should always be logically and also physically separated.
Service interface X127
The service interface X127 of the NCU is used for direct connection of a PG/PC for service
purposes. Here, access with STEP 7 to the PLC, and with NCU 7x0.3 PN also to PROFINET
is possible.
With direct connection (peer-to-peer) of a PG/PC to X127 it is absolutely necessary that the PG
is operated as a DHCP client.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
37
Networking
7.1 System settings
7.1.3
System boot with system network
System behavior at boot
The system boot behavior is based on the following principle:
● For the configuration of an NCU 7x0 with a PCU/IPC, the default for a network configuration
is as follows: The NCU keeps the default IP address 192.168.214.1 on X120, the PCU/IPC
keeps the default IP address 192.168.214.241 on Eth2.
● For a configuration of more than one NCU 7x0 without PCU/IPC, with one or morel PCUs/
IPCs, a distinction must be made between two cases:
- All address conflicts and DHCP conflicts are resolved automatically when booting and
the system is ready for operation. In this configuration there is no guarantee that all
NCUs and PCUs/IPCs will always receive the same IP address at each system boot.
- If the user requires all NCUs, and possibly also the PCU/IPC, to have a defined constant
IP address at each boot, for example, because the IP address is stated explicitly in the
PLC program, the user must configure a fixed IP address in the adapter settings in the
Windows Control Panel for each affected NCU 7x0/PCU/IPC.
● You can specify a DHCP master in the basesys.ini file.
● Assigning names:
- Assign meaningful names for all NCUs in the basesys.ini file otherwise the names will be
generated automatically.
- A PCU/IPC always has a computer name, which you can change if required.
● The IP addresses of the TCU, MCP/MPP, EKS, HT2, and HT8 are freely assigned within the
specified address range on each boot. MCP/MPP, HT2, and HT8 are identified in the PLC
via their DIP switch settings.
Using DNS name service
Availability of the DNS (Domain Name System) name service offers the following advantages
for system network administration:
● The name service enables easier configuration with names instead of IP addresses for
management of operating units: All components in the system network can be addressed
via a symbolic computer name. This name can to some extent be freely assigned, to some
extent it is derived automatically from a DIP switch setting (MCP, MPP, EKS, HT 8, HT 2).
● A computer node in the system network (NCU, PCU/IPC, TCU, MCP, HT 8, etc.) can be
addressed solely through assignment of the IP address, either via a freely selectable name
or via an internally generated name in the system network, and thus becomes independent
from its network address in the system network. Thus a change in the network address does
not necessarily necessitate a series of additional setting changes.
● In addition, the name service is used by the system for address resolution for MCP/MPP,
direct keys, and EKS when changing the user authorization.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
38
Manual, 05/2019, A5E43201322B AB
Networking
7.1 System settings
7.1.4
Factory default settings
Meaning of the symbols:
○
Eth 1 as a DHCP client
●
Eth 2 as a DHCP server
■
Eth 2 with a fixed IP address
Preconfiguration of the TCU
The TCU is configured as a DHCP client and primarily accepts IP addresses from SINUMERIK
components, from the DHCP server of such components that are inherent to SINUMERIK, for
example, an NCU at X120 or a PCU/IPC on the system network or from a standard DHCP
server. The behavior of the TCU cannot be changed here.
A TCU is a SINUMERIK DHCP client.
The TCU has a single Ethernet connection.
7&8
A TCU executes a boot via the network. The boot server is the computer node from which the
TCU also obtains its IP address.
Pre-configuration of the PCU
A PCU has two Ethernet interfaces with default settings for use with SINUMERIK solution line:
Eth 1 is pre-selected as a default DHCP client for connection to a
company network.
3&8
Eth 2 is pre-selected as a SINUMERIK DHCP server for connec-
tion to a system network. On Eth 2 the fixed IP address
(WK
(WK
192.168.214.241 is pre-selected.
Preconfiguration of the IPC
An IPC has two Ethernet interfaces with default settings for use with SINUMERIK solution line:
X1 is preset as the standard DHCP client for connection to a com-
pany network.
,3&
X2 is preset as a SINUMERIK DHCP server for connection to a
system network. The fixed IP address 192.168.214.241 is preset
;
;
on X2.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
39
Networking
7.1 System settings
Preconfiguration of the NCU
On the X120, the NCU is preconfigured for the SINUMERIK DHCP protocol. The NCU is pre-
selected here as a SINUMERIK DHCP server. On X120, the NCU occupies the fixed IP address
192.168.214.1 with the subnet mask 255.255.255.0 in its capacity as a DHCP server. The
DHCP server of the NCU assigns IP addresses from the range 192.168.214.10 -
192.168.214.239 to the DHCP clients.
It is also possible to make the NCU a DHCP client. The configured IP address in basesys.ini is
a "requested" IP address, which is rejected in the case of an address conflict and replaced by
a dynamic IP from the address range.
In large system networks, it makes sense to set an NCU/PCU/IPC as the DHCP master. If an
additional 2-3 hosts are used (NCU/PCU/IPC), the user sets the DHCP priority to "ON_HIGH".
For the other hosts, the user sets DHCP priority to "ON_CLIENT_SYNC" or
"ON_CLIENT_NO_SYNC".
Restricting the available address band that is managed by the DHCP server of the NCU frees
up IP addresses 192.168.214.2 to 192.168.214.9 as well as addresses 192.168.214.241 to
192.168.214.254 for network nodes with fixed IP addresses.
The NCU has three Ethernet connections:
;
;
● X120 to connect to the system network with an active DHCP
server (Eth 0)
1&8
● X130 to connect to the company network as the standard
;
DHCP client (Eth 1)
● X127 as a service connection with an active DHCP server (Ibn
0)
On X130, the NCU is set as a default DHCP client for the address reference from a company
network. The IP address received here is specified by the DHCP server from the company
network.
On X127, an NCU is a standard DHCP server in contrast to the SINUMERIK DHCP server. On
X127, the NCU has the fixed IP address 192.168.215.1 with the subnet mask 255.255.255.224
as Service input. The IP addresses 192.168.215.2 - 192.168.215.23 are dynamically assigned
to the DHCP clients. The range 192.168.215.24 - 192.168.215.30 is reserved, and can be used
by stations on the network with a fixed IP address, e.g. by a modem.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
40
Manual, 05/2019, A5E43201322B AB
Networking
7.2 Commissioning TCU
IP address ranges reserved for NCU and PCU/IPC
The following defaults apply on delivery:
● Connection to the system network with subnet mask 255.255.255.0:
IP address
Network station
Remark
192.168.214.1
NCU on X120
Default
192.168.214.2 - 9
For additional NCUs with a fixed IP address on
Not assigned
the system network
192.168.214.10 - 239
For additional TCUs, later for additional PCUs,
DHCP clients
IPCs, NCUs, MCPs, MPPs
192.168.214.240
Reserved for EKS (Electronic Key System)
Default
192.168.214.241
Fixed IP address of PCU/IPC on Eth 2
Default
192.168.214.242 - 249
For additional PCUs/IPCs with a fixed IP ad-
Not assigned
dress
192.168.214.250 - 254
For PGs with a fixed IP address (Service con-
Not assigned
nection)
● Service connection with subnet mask 255.255.255.224:
IP address
Network station
Remark
192.168.215.1
NCU on X127
Default
192.168.215.2 - 23
For service purposes with PG, PC
DHCP clients
192.168.215.24 - 30
Fixed IP address, e.g. for a modem
Not assigned
7.2
Commissioning TCU
7.2.1
Key assignment
Key assignment
Functions of the keys and softkeys in the "Operator panel service system":
Softkey
Key on OP
External key-
Description
board
HSK1
<F1>
Moves the cursor down a row
HSK2
<F2>
Moves the cursor up a row
Page
HSK3
<F3>
Moves the cursor down a page
Page
HSK4
<F4>
Moves the cursor up a page
Char
HSK5
<F5>
Inserts text or digits
Char
HSK6
<F6>
Inserts text or digits
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
41
Networking
7.2 Commissioning TCU
Softkey
Key on OP
External key-
Description
board
VSK7
←
Cancel / Return
Cancel
VSK8
→
OK / Confirm
Ok
---
Pos1
Moves the cursor to the top row
---
End
Moves the cursor to the bottom row
Exceptions to the above are mainly the result of input fields. Where these are present, the left/
right cursor keys move the input cursor rather than performing an OK/cancel function. The
Return key takes you to the next field (like the "down" key) rather than closing the entire dialog
with OK. There are also Backspace (deletes character to the left) and Delete (deletes character
to the right) keys for editing text and numbers. The F5, F6, Backspace, Delete, and Select keys
(between the cursor keys) can be used to switch between Yes/No fields.
Note
Special function for Touch Panels without additional keys
Letters and numbers in input fields can be edited with HSK5/HSK6, which switch one character
forward or backward. With a touch screen, you can activate all the softkeys and even select
rows in a menu simply by touching them.
For operator panel fronts without keys, a virtual keyboard automatically appears.
7.2.2
Settings in the "TCU.ini" file
Directories
The tcu.ini file is created in the following directories:
NCU:
../siemens/system/etc/tcu.ini
../user/system/etc/tcu.ini
../oem/system/etc/tcu.ini
PCU/IPC (Windows 7 and Windows 10):
C:\ProgramData\Siemens\MotionControl\siemens\System\etc\tcu.ini
C:\ProgramData\Siemens\MotionControl\user\System\etc\tcu.ini
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
42
Manual, 05/2019, A5E43201322B AB
Networking
7.2 Commissioning TCU
C:\ProgramData\Siemens\MotionControl\oem\System\etc\tcu.ini
Note
The following entries are evaluated by SINUMERIK Operate:
● VNCServer/VetoMode
● VNCServer/AlarmBoxTimeOut
● VNCServer/FocusTimeout
● VNCServer/AdaptResolution
● VNCServer/MaxActiveTCUs
● VNCViewer/ExternalViewerSecurityPolicy
Restrictions
Restrictions for such external operator control units are:
● Neither MCP and direct keys nor an EKS system can be assigned. This also means that
these devices cannot be activated to be an operator control unit in the system.
● Direct keys cannot be triggered, i.e. the softkeys to the direct keys can be triggered in the
operating software. However, the keys do not appear in the direct key image to the PLC.
● There is no config.ini configuration file, as for a TCU, i.e. a configuration for a TCU is not
possible for such an operator control unit (power-up behavior, displacement, t:m:n);
however, the displacement mechanism on the external operator control units is effective.
● An external operator control unit is never signaled as active operator station in the PLC.
Configuring the external operator control units in the tcu.ini file in section:
[externalTcu]
# EXTERNAL TCU IP-ADDRESSES
# List of accepted TCUs in IP-V4-format (index 1 to maximal 16)
ExternalTcuIP_1=
You can also set the desired screen resolution in the tcu.ini file:
[VNCServer]
Resolution = ...
7.2.3
Displacement mechanism for TCUs
To operate a machine with more operating stations then the maximum number, the
displacement mechanism ensures that only the permitted number of TCUs are active in a
shadowing group. The remaining TCUs are switched to passive mode, which means they no
longer represent a load with regard to the resources. Thus the number of TCUs that can be
connected to one HMI application is practically no longer limited. The limitation is the number
of concurrently active TCUs.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
43
Networking
7.2 Commissioning TCU
Supplementary conditions
The following supplementary conditions apply when operating the TCU:
2 active TCU connected in parallel to NCU 710.3 PN
4 active TCU connected in parallel to NCU 720.3 PN, NCU 730.3 PN
4 active TCUs connected in parallel to PCU/IPC
Displacement rules
You configure the displacement mechanism in SINUMERIK Operate in the "Setup" operating
area > menu forward key > "OPs" softkey for the respective operator panel.
The TCU can assume the following states:
● The TCU is active and has user authorization: This can be identified as the TCU shows the
screen of the operating software and the screen is bright.
● The TCU is active, is in the monitoring mode and has no user authorization: This can be
identified as the TCU shows the screen of the operating software, however, it is darkened
in comparison to the TCU with user authorization.
● The TCU is passive: The TCU shows the selection menu of the possible connections
instead of a screen of the operating software, and the softkey for selection of the last active
connection of the TCU is shown in color.
When powering up, the TCU always always attempts to establish the first connection. The
TCUs from a shadowing group establish their specified connection one after the other as long
as the maximum number of permissible active operator units is not exceeded.
If a TCU encounters the situation that this number is already reached in its power up, then it
attempts to obtain a connection via the displacement mechanism. If it can displace a formerly
active operator unit then it takes on the active status itself, otherwise it transitions to passive
status immediately after booting.
7.2.4
Disable switchover between TCU via PLC
Overview
The TCU switchover disable offers the option of dynamically disabling switchover from one
TCU to the next when the system is running via the PLC. For the duration of the disable, a user
authorization request to change user authorizations between TCUs will be ignored by the
system and rejected.
The rejected user authorization request causes a message to be output in the dialog line of the
HMI, in the form of a feedback message for the requester. The message disappears after five
seconds.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
44
Manual, 05/2019, A5E43201322B AB
Networking
7.2 Commissioning TCU
HMI ↔ PLC data interface
The "switchover disable" function is always active and does not have to be switched on
explicitly. The function is controlled by a data bit in the PLC. The HMI transfers the active OP
to the PLC, thus forming the basis of the control function in the PLC.
The control bits and control information for this function are stored in the m:n data interface of
the PLC. In terms of m:n, this function can be operated separately for the currently overridden
HMIs in both m:n online interfaces (DB19.DBW120 ff for HMI1 and DB19.DBW130 ff for HMI2).
If a system is not running an m:n, only the first m:n online interface is used for this function.
Switchover disable is controlled by a TCU_SHIFT_LOCK bit, managed by the user, on each
HMI in the PLC. The bit address for the first HMI is DB19.DBB126.6 and DB19.DBB136.6 for
the second HMI.
The PLC m:n online interface is expanded so that byte DB19.DBB118 is also assigned to the
first interface and byte DB19.DBB119 to the second. These bytes acquire the index of the
active TCU/OP for the appropriate HMI. The byte is called TCU_INDEX. The appropriate HMI
uses the TCU index configured for the active TCU to describe the TCU_INDEX byte.
The TCU_SHIFT_LOCK bit is monitored by the appropriate HMI. A value = 1 triggers the
switchover disable. Switchover is enabled if the value returns to 0. The TCU_SHIFT_LOCK bit
can be set, for example, to the PLC by the user pressing a key or it can be managed by the PLC
user program according to its own logic. The TCU_SHIFT_LOCK bit is managed in the PLC
exclusively by the user; the HMI only accesses this bit in read-only mode.
The HMI assigns the TCU_INDEX field with the configured index to the TCU or PCU/IPC with
an OP that currently possesses user authorization in the shadow group. If no OP is active, a
value of 0 is entered in TCU_INDEX.
If no TCU index is configured for the active TCU/OP, the value 255 = undefined is transferred
as a TCU index. This means that the values 0 and 255 may not be configured as the TCU index.
Configuration
The TCU index is configured on the PCU/IPC in the same way as a machine control panel
address (MCP address). The TCU index is set in the "OP Properties" dialog of the "System
Network Center" program.
Operating principle
If the TCU_SHIFT_LOCK bit is set for switchover disable, a user authorization request is not
carried out independently of the mode set on the HMI for allocation of user authorizations (veto
mode), i.e. a change of user authorization is rejected.
This message appears on all OPs for approximately 5 seconds:
"No switchover: Switchover disable set in current PLC."
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
45
Networking
7.2 Commissioning TCU
While this message is displayed, operations on the OP with the user authorization can still be
carried out unaffected.
Note
Active switching of an OP to another PCU/IPC is possible
The switchover disable only relates to changing the user authorization on the OPs in a
shadowing group on a PCU/IPC.
This means that active switching away from one OP to another PCU/IPC is not prevented.
Special features
The following special cases should be noted:
● Even if switchover disable is set, the TCU_INDEX field value may change in the PLC. This
is the case under the following circumstances:
- If the OP in possession of the user authorization is actively switched to another PCU/IPC.
Depending on whether another TCU takes over the user authorization or whether no
TCU is currently active, the index of the TCU or the PCU/IPC itself (if its directly
connected OP becomes active) is entered, in exactly the same way as when there is a
switchover of user authorization.
This can also be the value 255, if no TCU index is available for the OP. 0 is entered if an
OP is no longer available in the shadow group.
- If an m:n switchover is in progress. The HMI program of the incoming PCU/IPC
deactivates the HMI program which is active on it. Therefore, an OP from the shadow
group of the new (incoming) PCU/IPC must receive the user authorization. The TCU
index of this OP is entered in the TCU_INDEX field.
- If a PCU/IPC is disconnected from an NCK/PLC in the context of m:n. No HMI program
and, therefore, no OP with user authorization is then available on the exited NCK/PLC.
This is signaled independently of a switchover disable by entering the value 0 into the
TCU_INDEX field.
● If a TCU is actively switched over to another PCU/IPC, it can be deactivated there, i.e. it
does not receive user authorization if a switchover disable is set for the destination PCU/IPC.
● With an m:n PCU/IPC switchover - the PCU/IPC is switched to another NCK and, therefore,
to another PLC - the PCU/IPC accepts the switchover disable settings of that PLC.
● The m:n interlock options on the PLC side have priority over the TCU switchover disable, so
that a set TCU switchover disable cannot prevent an m:n switchover. If necessary, the m:n
interference options should be synchronized here with those for the TCU in the PLC. It may,
for example, be practical to set or remove the m:n displacement disable simultaneously with
the TCU switchover disable.
Obtaining user authorization
At a TCU, which has no user authorization, press any key. The operating software does not
evaluate this key; this only serves to request user authorization.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
46
Manual, 05/2019, A5E43201322B AB
Networking
7.2 Commissioning TCU
The settings for the right to veto are stored in file tcu.ini and are only effective if the operating
software is installed on the PCU/IPC. You can use the operating software on the OP or TCU in
the same way as on an OP connected directly to the PCU/IPC.
7.2.5
Example: How to select the behavior of the TCUs during boot up
Example: Distributing boot support across two PCUs/IPCs
Make the following settings to distribute the boot support across two PCUs/IPCs:
● On PCU_1/IPC_1, select "Boot support runtime and configuration only (TFTP/FTP)"
● On PCU_2/IPC_2, select "Boot support IP address only (DHCP)"
● On PCU_3/IPC_3, select the configuration "No boot support"
TCU_1
TCU_2
TCU_3
TCU_4
192.168.214.10
192.168.214.11
192.168.214.12
192.168.214.13
VNC connections:
VNC connections:
VNC connections:
VNC connections:
192.168.214.241
192.168.214.241
192.168.214.241
192.168.214.241
192.168.214.242
192.168.214.243
192.168.214.243
192.168.214.242
192.168.214.243
Switch to system network
PCU_1/IPC_1
PCU_2/IPC_2
PCU_3/IPC_3
192.168.214.241
192.168.214.242
192.168.214.243
Services:
Services:
Services:
X DHCP
✔ DHCP
X DHCP
✔ TFTP
X TFTP
X TFTP
✔ FTP
X FTP
X FTP
✔ VNC
✔ VNC
✔ VNC
Company network
In this case, PCU_2/IPC_2 serves as the DHCP server which provides the IP addresses for the
connected TCUs. PCU_3/IPC_3 is not involved in booting the TCUs, it is however displayed by
the TCUs using VNC.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
47
Networking
7.3 Network configuration
7.3
Network configuration
7.3.1
Permissible network topologies
Ethernet connection
A SINUMERIK 840 D sl can only be operated as a network within which the individual
components communicate with one another via Ethernet connections. This network must be
set up.
The individual components are factory-set so that the most frequently occurring standard
configurations can be operated without changing the settings related to the network.
Division into system network and company network
On the SINUMERIK solution line, the components are generally split into a company network
on the one hand and a system network on the other.
The connection to the company network provides access to the network drives, for example.
On the system network, process data communication and image transmission runs from the
components with operator software to the display units of the respective TCU.
This separation is performed via the following specified use of the Ethernet interfaces on the
components:
● A TCU is connected exclusively to the system network.
● An NCU is always connected to the system network via X120.
● Ethernet interface Eth 2/X2 of the PCU/IPC is preconfigured for connection to the system
network; while Ethernet interface Eth 1/X1 is used for connection to the company network.
● An NCU is connected to the company network via X130.
Meaning of the connections:
○
Eth 1/X1 as DHCP client
●
Eth 2/X2 as DHCP server
■
Eth 2/X2 with fixed IP address
Green connection
Uncrossed Ethernet cable
Gray connection
Crossed Ethernet cable (crossover)
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
48
Manual, 05/2019, A5E43201322B AB
Networking
7.3 Network configuration
7.3.2
Networks without connection to the company network
7.3.2.1
Configuration 1: NCU and TCU
6\VWHP QHWZRUN
7&8
;
1&8
&RPSDQ\ QHWZRUN
A direct Ethernet connection is used to connect a TCU to X120 of the NCU. NCU and TCU are
suitably preconfigured with IP addresses.
The IP addresses are not significant for further operation.
The TCU is connected to the NCU via a crossed Ethernet cable.
The direct connection of the NCU via X120 to the TCU automatically establishes a simple
system network consisting of two computer nodes.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
49
Networking
7.3 Network configuration
7.3.3
Networks with NCU connection to the company network
7.3.3.1
Configuration 2: NCU and TCU
6\VWHP QHWZRUN
7&8
;
1&8
;
6ZLWFK
&RPSDQ\ QHWZRUN
The TCU is directly connected to the NCU via a crossed Ethernet cable. On X130, the NCU is
connected to a switch to the company network with a straight cable.
As in configuration 1, there is a direct Ethernet connection between a TCU and X120 of the
NCU. NCU and TCU are suitably preconfigured with IP addresses. The IP addresses used here
are not significant for further operation.
IP configuration: DHCP server on the company network
On the X130, the NCU is set to the address reference via DHCP. If the company network has
a DHCP server that provides the NCU with an IP address/configuration, the NCU is integrated
in the company network.
Depending on the infrastructure available or the level of network administration of the company
network, the following network parameters must be set for the NCU on X130:
● Computer name on the company network
● The address of a DNS server
● The address of a gateway (default router)
The IP address of the NCU on this connection is also assigned via the network administration.
If the company network offers a low level of administration, in the worst case scenario the
network has only one DHCP server that assigns the addresses from a predefined address
range, the NCU receives an IP address that is initially unknown.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
50
Manual, 05/2019, A5E43201322B AB
Networking
7.3 Network configuration
7.3.3.2
Configuration 3: PCU/IPC with TCU on NCU
6\VWHP QHWZRUN
7&8
6ZLWFK
;
(WK
3&8
1&8
,3&
;
(WK
6ZLWFK
&RPSDQ\ QHWZRUN
In this configuration, a switch is also required for the system network. All components are
connected using straight Ethernet cables.
On X120, the NCU occupies the fixed IP address 192.168.214.1 in its capacity as a DHCP
server (not used in this configuration). For this configuration on Eth 2, the PCU/IPC is assigned
a static IP address in the range 192.168.214.241 - 192.168.214.249 with a subnet mask
255.255.255.0 . The DHCP server of the NCU supplies the TCU with an IP address and serves
as a boot server for the TCU.
The observations made for configuration 2 apply here with regard to the connection to the
company network. The connection to a switch on the company network is made via a patch
cable for Ethernet.
To connect one TCU to both HMI systems you must create an additional connection to the NCU
for the TCU.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
51
Networking
7.3 Network configuration
7.3.3.3
Connecting the programming device (PG) to the NCU
Description
6\VWHP QHWZRUN
7&8
6ZLWFK
(WK
;
3&8
1&8
;
,3&
(WK
3* 3&
;
6ZLWFK
&RPSDQ\ QHWZRUN
For service purposes a programming device is connected to the NCU at X127 as a standard
DHCP client (automatically obtain an IP address). An NCU is a standard DHCP server on X127.
On X127, the NCU occupies the fixed IP address 192.168.215.1 with the subnet mask
255.255.255.224.
At X127, IP addresses from 192.168.215.2 onwards are assigned via DHCP; e.g. to connect a
programming device. This is the reason that a fixed IP address must not be set at the
programming device.
7.3.4
Example: Configuring a VNC connection to a PC
Requirements
In order to use a TCU to get visual access to a computer from a SINUMERIK system via VNC,
the following requirements apply:
● The VNC connections should be configured in the HMI.
● The boot server (active DHCP server) in the system network must be an NCU.
● This NCU must be integrated via X130 or X120, i.e. in the network that contains the
computer to be monitored.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
52
Manual, 05/2019, A5E43201322B AB
Networking
7.3 Network configuration
● The computer to be monitored must be configured in the config.ini configuration file of the
TCU according to the general configuration for a TCU in a separate host section as a
switchover target for this TCU.
Where necessary, a password has to be specified in the configuration, if the VNC server
requires one on the target system (see below).
● To ensure that the TCU recognizes the new switchover target, the TCU requires a restart
and reboot.
● The screen resolution of the observed computer must be adjusted to the characteristics of
the TCU. Otherwise the TCU scales the image it receives to match the display area
available to the TCU, which impairs the quality of the display on the TCU.
Configuration
6\VWHP QHWZRUN
7&8
;
1&8
;
3* 3&
1HWZRUN
Figure 7-1
Configuration example
Configuration
The config.ini file is located in the following directory:
NCU:
/user/common/tcu/<TCU name>/common/tcu
PCU/IPC (Windows 7 and Windows 10):
C:\ProgramData\Siemens\MotionControl\user\common\tcu\<TCU name>
\common\tcu
The config.ini file must be stored on the boot server (active DHCP).
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
53
Networking
7.4 Service and diagnostics
Example:
[Station]
maxhostindex=2
/* Number of nodes that are defined under
[host_1] and [host_2].
mcpIndex=192
tcuIndex=1
eksIndex=0
[host_1]
Address=192.168.214.1
/* Address of the NCU to which the
connection is established during booting.
[host_2]
Address=157.163.230.202
/* Address of the PC
password=123456
/* Password of the VNC server on the PC
Switching over between the nodes
With the menu back key + MENU SELECT, the following actions are triggered:
● The TCU name is displayed in the header of the displayed window, e.g. TCU1.
● A selection list for connecting to the other nodes is displayed on the TCU.
7.4
Service and diagnostics
7.4.1
Using the TCU's main menu
"Main menu"
The "Main menu (TCU1)" dialog is started with the menu back key and the <MENU SELECT>
key:
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
54
Manual, 05/2019, A5E43201322B AB
Networking
7.4 Service and diagnostics
① "Main menu" title followed by the TCU name in brackets
② Central area with the list of servers and two further permanent items, "Select service session"
and "Service this panel":
● "Select service session" triggers a server scan which detects all the VNC servers in the local
system network. These are then displayed in a session menu which largely reflects the main
menu.
● "Service this panel" opens the "Service menu for operator panel" submenu.
③ Eight vertical softkeys for use depending on the context
④ Four horizontal softkeys for navigating with the cursor
⑤ Message line whose content can be set via HWS commands from the servers
⑥ Error line in which error messages as well as transient status messages are output
Figure 7-2
TCU menu: Main menu
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
55
Networking
7.4 Service and diagnostics
"Details" softkey
The following connection data for the selected device appears when the "Details" softkey is
pressed:
Figure 7-3
TCU menu: Connection data
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
56
Manual, 05/2019, A5E43201322B AB
Networking
7.4 Service and diagnostics
7.4.2
Operating the TCU menu "Service sessions"
"Service sessions" dialog
When "Select service session" is selected from the main menu, the resulting process begins by
triggering a server scan:
Figure 7-4
TCU menu: Scanning
After this, the following dialog appears:
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
57
Networking
7.4 Service and diagnostics
Figure 7-5
TCU menu: Active sessions
Central area with the server list:
The individual server lines contain either "Show WHAT on NAME (IP)" or the IP address only
where the name is unknown.
Session number
VNC server
Session 0
HMI
Session 4
Command shell
Session 5
System logfile
Session 6
System Network Center (SNC)
Session <N>
Other servers
These details are followed by a status message regarding the accessibility of the VNC server.
● "Connection not ok" appears if it is already impossible to access the server from the IP side
(if switched off, for example).
● "HMI running/ not running", if an HMI VNC server is accessible.
The VSK8, Return or right cursor keys can be used to launch a VNC viewer for the selected
server.
Connection status:
Further details on the connection status can be called with the "Details" softkey. In the next
dialog, "not ok" or "not running" are accompanied by an additional error message with more
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
58
Manual, 05/2019, A5E43201322B AB
Networking
7.4 Service and diagnostics
precise details on the reason for the loss of function. With more favorable scenarios, the
session name for the VNC server will also be specified along with its resolution.
The connection and HMI status are monitored on a regular basis in the backg14round. This may
mean that these specifications change spontaneously if a change is made on the relevant
server, e.g. it may be switched off, the HMI may become available, etc.
7.4.3
Operating the TCU menu "Service menu"
"Service menu for operator panel (TCU)" dialog
The following dialog appears when "Service this panel" is selected from the main menu:
Figure 7-6
TCU menu: Service menu
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
59
Networking
7.4 Service and diagnostics
The following menu items are available here:
● "Show status" shows status information, for example: Software version, hardware
information, TCU network data, and their configuration:
Figure 7-7
TCU menu: OP status
● "Show local logfile" shows a filtered version of the system log file in the /var/log/
messages directory, which contains only the messages of the local TCUs.
Syslog messages received via the network are not displayed.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
60
Manual, 05/2019, A5E43201322B AB
Networking
7.4 Service and diagnostics
Figure 7-8
TCU menu: Local log file
● "Show logfile of remote devices" shows the log file of the other devices in the network:
The syslog messages of devices in the system network which send syslog messages by
broadcast, such as NCU 7x0, ...
● "Modify operator panel settings" opens another submenu, see next section.
● Calibrate touch screen" is only active if there is a touch screen. This menu item recalibrates
an available touch screen.
● "Reboot" initiates a restart of the TCU.
Note
Long lines are broken and wrapped around.
Lines that are longer than the space available wrap round onto the next line so that you do not
have to scroll horizontally. When this occurs, the line has a right-facing arrow at its right edge.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
61
Networking
7.4 Service and diagnostics
7.4.4
Operating the TCU menu "Modify settings"
"Modify settings for operator panel (TCU)" dialog
The following dialog appears when "Modify settings" is selected from the main menu:
Figure 7-9
TCU menu: Settings
The following TCU parameters are set here during the first commissioning:
● "HT 8 individual mode" (yes/no)
This is only visible with HT 8, and is used to switch between Auto Mode and Individual Mode.
You do not have to make settings for an HT 8 in Auto Mode because the name is generated
automatically: ("DIP<n>") MCP address and TCU index are derived from the DIP setting
("DIP<n>").
● "Operator panel index - TCU" (0-255)
Defines the TCU index; see column "TCU" on the user interface.
● "Machine control panel address - MCP" (0-255)
Specifies the address of the associated MCP; see column "MCP" on the user interface.
● "Electronic key system index - EKS" (0-255)
Specifies the index of the associated EKS; see column "EKS" on the user interface.
● "Enable direct keys" (yes/no)
Specifies whether direct keys are registered with the PLC (yes) or are treated as ordinary
keys (no); see column "DCK" on the user interface.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
62
Manual, 05/2019, A5E43201322B AB
Networking
7.4 Service and diagnostics
●
"Virtual Keyboard" (Auto/On/Off)
Specifies whether a virtual keyboard is shown on the screen for touch screens.
Depending on the panel features (Auto), the HMI decides whether a touch screen or
keyboard is available.
This parameter can also be set manually (On/Off).
●
"Software Caps-Lock" (Auto/On/Off)
The HMI can manage the Caps-Lock status of a keyboard in the software itself, when, for
example, the key is not available. This is normally (Auto) switched on via a display machine
data item. This machine data item can be overwritten individually for the TCU with the
setting (On/Off).
●
"Emulation Type" (TCU/TCU20.2/TCU30.3, only for modular TCU30.3)
Specifies which TCU type is to be emulated when the TCU30.3 is operated as replacement
device for an older TCU or as new device on a software version older than 4.7 SP2.
●
"Screen Rotation" (0°/90°/180°/-90°/Auto)
Specifies in which angle the screen is to be rotated in the software. This is useful when the
panel is to be rotated during installation.
For the "Auto" setting, the rotation of the display is taken from the panel.
●
"Old VNC Password"
If a password has already been set, it must be entered here so that it can be changed. If no
password has been set, this field is grayed-out. The existing password can also be deleted
if, after entering the old password, no new password is to be entered at "Set VNC Password"
and "Repeat Password".
●
"Set VNC Password"
Assign a password which is stored in the TCU and, if required, sent to the server when the
VNC connection is established.
●
"Repeat Password"
Repeat the password entered at "Set VNC Password".
●
"Enable touch capability" (yes/no)
Specifies whether the screen can be operated by touch. If you deactivate this option, you will
need a keyboard to reactivate it.
The values are applied and stored with "OK". You can also make any subsequent adaptations
or changes via the user interface in the "Setup" operating area > menu forward key > "OPs"
softkey.
7.4.5
Operating the menu for a new TCU or spare part TCU
Registering a new TCU
When an unknown TCU, i.e. not yet registered with the boot server, is started, a selection menu
containing both the "New" and "Replacement for existing panel" items is displayed. The
accessibility of all the registered TCUs is tested in the backg14round.
The status of this test is displayed in the message line: "(0/3 panels inactive)".
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
Manual, 05/2019, A5E43201322B AB
63
Networking
7.4 Service and diagnostics
Figure 7-10
TCU menu: New TCU
If all TCUs are active, the new TCU cannot be a spare part. The system will then automatically
switch to the name assignment phase after a set period of time has elapsed.
Operator panel fronts: TOP 1500, TOP 1900, TOP 2200
64
Manual, 05/2019, A5E43201322B AB
|