Parker Variable Speed Drive AC30 series. User’s Manual (2017) - page 22

 

  Index      Manuals     Parker Variable Speed Drive AC30 series. User’s Manual (2017)

 

Search            copyright infringement  

 

 

 

 

 

 

 

 

 

 

 

Content      ..     20      21      22      23     ..

 

 

 

Parker Variable Speed Drive AC30 series. User’s Manual (2017) - page 22

 

 

 

 Parameter Reference  

 D-49

 

Functional Description 

During a fast deceleration, the kinetic energy of the motor load is regenerated to the drive, charging the DC link capacitors. 
When the 

VDC Lim Level

 is reached, the speed septoint is held, waiting for the DC link to go below 

VDC Lim Level

When the DC link falls below this level, the speed setpoint is released and is ramped down using system ramp deceleration. 
This sequence is run until the speed septoint reaches the user speed demand. 
 
By Default, 

VDC Lim Level

 is set to the same value as the braking threshold.  

 
This feature is run at a rate of 1 milli-second. 
 

Ramp

Power Loss 

Ride Thru

DC Link 

Volts Limit

Slew Rate 

(V/Hz only)

Speed Setpoint path

User 

Speed control loop

 

 
 

D-50 

Parameter Reference  

Device Commands 

Parameters::Device Manager::Device Commands 

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Update Firmware 

 

 

1002 

 

 

Parameters::Device Manager::Device 
Commands 

 

 

FALSE 

 

 

 

 

STOPPED 

 

This parameter is only visible when an SD card with a firmware update file is inserted into the drive. Changing this parameter to TRUE 
will start the firmware update procedure. 

Following a firmware update it is advisable to power re-run the Setup Wizard, D-61 

 

Save All Parameters 

 

 

1001 

 

 

Parameters::Device Manager::Device 
Commands 

 

 

FALSE 

 

 

 

 

ALWAYS 

 

When a parameter is modified via the GKP or via the built-in web page the parameter value is saved automatically. When a parameter 
is modified via another source, (for example via the Modbus TCP/IP communications protocol), the value will not be saved 
automatically. In this case a save may be instigated by changing this parameter from FALSE to TRUE. 

 

 Parameter Reference  

 D-51

 

Device State 

Parameters::Device Manager::Device State 

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Target State 

 

 
0988 

 

Parameters::Device Manager::Device 
State 
 

 

 

3:PREOPERATIONAL 
7:OPERATIONAL 
 

 

 

STOPPED 

 

The requested operating state. This may be set from the Web Page or GKP. The PDQ configuration tool changes the operating state 
of the drive using a different mechanism. 

 

Actual State 

 

 
0989 

 

Parameters::Device Manager::Device 
State 
 

 

 

0:INITIALISING 
1:INITIALISED 
2:PREPARING PREOP 
3:PREOPERATIONAL 
4:PREPARING OP 
5:FAILED TO READY 
6:READY FOR OP 
7:OPERATIONAL 
8:FAULTED 
9:FATAL ERROR RECOVER 
 

 

 

NEVER 

 

Reports the actual operating state of the drive.  

 

Application FE State 

 

 
0990 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 

 

 

 

NEVER 

 

 

Base IO FE State 

 

 
0991 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 

 

 

 

NEVER 

 

 

Basic Drive FE State 

 

 
0992 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 
 

 

 

NEVER 

 

 

Ethernet FE State 

 

 
0993 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 
 

 

 

NEVER 

 

 

Keypad FE State 

 

 
0994 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 
 

 

 

NEVER 

 

 

Comms Option FE State 

 

 
0995 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 
 

 

 

NEVER 

 

D-52 

Parameter Reference  

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

IO Option FE State 

 

 
0996 

 

Parameters::Device Manager::Device 
State 

 

 

 

Same as PNO 989 
 

 

 

NEVER 

 

 

System Board FE State 

 

 
1742 

 

Parameters::Device Manager::Device 
State 
 

 

 

Same as PNO 989 
 

 

 

NEVER 

 

The parameters above indicate the state of individual components, (or Functional Elements), within the drive. They may help with fault 
finding if the drive ever fails to enter the normal Operational state.  

 

Config Fault Area 

 

 
0997 

 

Parameters::Device Manager::Device 
State 
 

 

 

0:NONE 
1:POWER STACK 
2:OPTION IO 
3:OPTION COMMS 
4:APPLICATION 
5:MOTOR CONTROL 
6:KEYPAD 
7:BASE COMMS 
8:BASE IO 
9:FEEDBACK MISSING 
10:SYSTEM BOARD 
 

 

 

NEVER 

 

Indicates which component within the drive is preventing the drive from entering the normal Operational state. 

 

RTA Code 

 

 
0998 

 

Monitor::Trips 
Parameters::Device Manager::Device 
State 
 

 

 

 

 

NEVER 

 

Run Time Alert fault code, indicates a fault in the hardware or configuration, typicaly detected during power on initialization. Refer to 
chapter 10, Trips and Fault Finding. 

 

RTA Data 

 

 
0999 

 

Same as PNO 998 
 

 

 

 

 

NEVER 

 

Data associated with a Run Time Alert. 

 

 Parameter Reference  

 D-53

 

DeviceNet Option 

Monitor::Communications::Option 
Setup::Communications::Option 
Parameters::Option Comms::Comms 
Parameters::Option Comms::Read Process 
Parameters::Option Comms::Write Process 
Parameters::Option Comms::Event 
Parameters::Option Comms::ControlNet 

 

Refer to DeviceNet Technical Manual HA501840U001  

D-54 

Parameter Reference  

Drive info 

Setup::Environment 
Parameters::Device Manager::Drive info 

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Drive Name 

 
 

 

0961 

 

 

Setup::Environment 
Parameters::Device Manager::Drive info 

 

 

 

 

 

ALWAYS 

 

A string value that may be used to identify this drive in a system. 

 

Firmware Version 

 

 

1100 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The version of the firmware running in the Control Module. 

 

Boot Version 

 

 

0951 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The version of the boot loader firmware running in the Control Module, presented as a text string. 

 

Boot Version Number 

 

 

0687 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The version of the boot loader firmware running in the Control Module. 

 

Power Stack Required 

 

 

0987 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

Same as PNO 543 

 

 

 

CONFIG 

 

The rating of the power electronics for the configuration loaded in the drive. If 0987 Power Stack Required is different from 0543 Power 
Stack Fitted the drive will be prevented from operating normally until the configuration is corrected. 

 

Power Stack Fitted 

 

 

0543 

 

 

Parameters::Device Manager::Drive info 

 

 

 

0:NONE 
1:3.5 A  400 V 
2:4.5 A  400 V 
3:5.5 A  400 V 
4:7.5 A  400 V 
5:10.0 A  400 V 
6:12.0 A  400 V 
7:16.0 A  400 V 
8:23.0 A  400 V 
9:32.0 A  400 V 
10:38.0 A  400 V 

 

 

NEVER 

 

 

 Parameter Reference  

 D-55

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

11:45.0 A  400 V R1 
12:60.0 A  400 V R1 
13:73.0 A  400 V R1 
14:87.0 A  400 V 
15:105 A  400 V 
16:145 A  400 V 
17:180 A  400 V 
18:205 A  400 V 
19:260 A  400 V 
20:45.0 A  400 V 
21:60.0 A  400 V 
22:73.0 A  400 V 
23:315 A  400 V 
24:380 A  400 V 
25:440 A  400 V 

26:530 A  400 V 

27:590 A  400 V 

28:650 A  400 V 

29:730 A  400 V 

30:840 A  400 V 

 

The rating of the power stack that the Control Module is fitted to. When the Control Module not attached to a stack this parameter is not 
visible and is ignored. 

The Power Stack names ending in “R1” are for the initial release of Frame G stacks with ventilation holes in the casing.  Later revisions 
of the Frame G stacks have no ventilation holes but have an internal cooling fan. 

 

Attached to Stack 

 

 

0695 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

A Boolean parameter that indicates that the Control Module is attached to a power stack. When the Control Module is not attached to a 
stack but is powered using the auxiliary 24v input this parameter will indicate FALSE. 

 

Stack Pcode 

 

 

1109 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The product code string that may be used to order an equivalent Power Stack. 

 

Stack Serial No 

 

 

1258 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The serial number of the Power Control Card, (part of the Power Stack assembly). 

D-56 

Parameter Reference  

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Control Module Pcode 

 

 

1116 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The product code string that may be used to order an equivalent Control Module, excluding options. 

 

Control Module Serial 

 

 

0977 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The serial number of the Control Module. 

 

Comms Option Pcode 

 

 

1121 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The product code string that may be used to order an equivalent Communications Option, (only visible when a Communications Option 
is selected). 

 

Comms Option Serial 

 

 

1129 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The serial number of the fitted Communications Option, (only visible when a Communications Option is selected). 

 

IO Option Pcode 

 

 

1125 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The product code string that may be used to order an equivalent IO Option, (only visible when an IO Option is selected). 

 

IO Option Serial No 

 

 

1134 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

The serial number of the fitted IO Option, (only visible when an IO Option is selected). 

 

IO Option SW Version 

 

 

1254 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

For intellilgent IO options this parameter shows the version of the firmware running in the option. 

 

 Parameter Reference  

 D-57

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Drive Diagnostic 

 

 

0688 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

0:OK 
1:STACK NOT CONNECTED 
2:STACK DATA CORRUPT 
3:UNKNOWN STACK 
4:STACK MISMATCH 

 

 

 

 

 

NEVER 

 

Indicates the health of the drive configuration. When the drive configuration includes a mutually conflicting requirement, this parameter 
indicates the problem; for example, it attempting to run in Closed Loop Vector control mode when no feedback option is configured. 

 

Product Code Flags 

 

 

1551 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

Manufacturing flags byte read from the power electronics stack.  

Bit 0  

When set, indicates that the dynamic brake switch power electronics is fitted. On larger frame sizes the brake switch is a  

 

 

factory fit option. On frames C,D,E,F and G this bit is ignored. 

Bit 1 – 7 

Reserved 

 

Manufacturing Flags 

 

 

1636 

 

 

Parameters::Device Manager::Drive info 
 

 

 

 

 

NEVER 

 

Manufacturing flags word read from the control module. 

Bit 0  

When set, indicates that the drive is a special build. 

Bits 1 – 15  Reserved 

 

OEM ID 

 

 

1256 

 

 

Parameters::Device Manager::Drive info 

 

 

 

 

 

NEVER 

 

A 16-bit integer set in the factory, that identifies the equipment manufacturer. This may be used to lock or tailor an application to a 
given manufacturer. To obtain a unique ID apply to Parker Hannifin Electomechanical Drives Business Unit. 

D-58 

Parameter Reference  

Encoder 

Setup::Inputs and Outputs::Option 
Monitor::Inputs and Outputs 
Parameters::Option IO::Encoder 

 
This feature allows you to setup and monitor the operation of the 

Encoder

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Encoder Supply 

 

 

1511 

 

 

Setup::Inputs and Outputs::Option 
Parameters::Option IO::Encoder 

 

 

 

 

0:5 V 
1:12 V 
2:15 V 
3:24 V 

 

 

 

STOPPED 

 

Allows the user to select the correct supply voltage for the pulse encoder. 

 

Encoder Lines 

 

 

1512 

 

 

Same as PNO 1511 

 

 

2048 

 

 

1 to 100000 

 

 

 

STOPPED 

 

The number of lines per one encoder revolution, as required by the encoder in use. Incorrect setting of this parameter will result in an 
erroneous speed measurement. 

 

Encoder Invert 

 

 

1513 

 

 

Same as PNO 1511 

 

 

FALSE 

 

 

 

 

STOPPED 

 

Reverses the encoder direction if set to TRUE. The encoder direction needs to be correct if encoder feedback is used to control the 
motor in vector mode. The autotune identifies whether the parameter is in the correct state required to control the motor, and changes 
it if necessary.  It is possible to do this manually, by attempting to run the motor, and changing the parameter if necessary until the 
motor is controlled correctly. 

 

Encoder Type 

 

 

1514 

 

 

Same as PNO 1511 

 

 

 

 

0:QUADRATURE 
1:CLOCK/DIRECTION 

 

 

 

STOPPED 

 

Normally the encoder type will be quadrature.  Exceptionally, e.g. if a proximity sensor or other pulse train is used, it needs to be clock / 
direction type. 

 

Encoder Single Ended 

 

 

1515 

 

 

Same as PNO 1511 

 

 

FALSE 

 

 

 

 

STOPPED 

 

 

 Parameter Reference  

 D-59

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

If set to TRUE this parameter informs the encoder option card to expect just A and B from the encoder, not differential /A and /B. 

 

Encoder Speed 

 

 

1516 
 

 

Monitor::Inputs and Outputs 
Parameters::Option IO::Encoder 
 

 

x. 
 

 

Min to Max 
 

 

 RPM 
 

 

NEVER 

 

The speed measured by the encoder, in revolutions per minute. 

 

Encoder Count Reset 

 

 

1517 

 

 

Same as PNO 1511 

 

 

FALSE 

 

 

 

 

ALWAYS 

 

If set to TRUE resets the encoder count. 

 

Encoder Count Init 

 

 
1783 

 

Parameters::Option IO::Encoder 
 

 

TRUE 
 

 

 

 

ALWAYS 

 

If set to TRUE the encoder count is reset to zero when the drive powers up. 

 

Encoder Count 

 

 

1518 

 

 

Same as PNO 1516 

 

 

 

Min to Max 

 

 

 

NEVER 

 

This parameter shows the encoder count, which is a 32 bit counter that will increment and decrement with the encoder pulses, up to 
2^31 or down to -2^31. 

D-60 

Parameter Reference  

Encoder Slot 1 

Parameters::System Board::Encoder Slot 1 

This feature allows you to setup and monitor the operation of the encoder attached to slot 1 of the system board.

 

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Encoder Supply 

 

 
1663 

 
Setup::Inputs and Outputs::SB Encoder 
Slot1 
Parameters::System Board::Encoder 
Slot 1 
 

 

 

 
0:5 V 
1:12 V 
2:15 V 
3:20 V 
 

 

 

STOPPED 

 

Configures the encoder supply for both Encoder 1 

and Encoder 2

 

 

Encoder Lines 

 

 
1664 

 

Same as PNO 1663 
 

 

2048 
 

 

1 to 100000 
 

 

 

STOPPED 

 

The number of lines per encoder revolution 

 

Encoder Invert 

 

 
1665 

 

Same as PNO 1663 
 

 

FALSE 
 

 

 

 

STOPPED 

 

Reverses the encoder direction if TRUE. 

 

Encoder Type 

 

 
1666 

 

Same as PNO 1663 
 

 


 

 

0:QUADRATURE 
1:CLOCK/DIRECTION 
 

 

 

Normally the encoder will be quadrature.  Exceptionally, eg if a proximity sensor or other pulse train is used, it needs to be clock / 
direction. 

 

High Input Threshold 

 

 
1667 

 

Same as PNO 1663 
 

 

FALSE 
 

 

 

 

STOPPED 

 

Changes the threshold level for the encoder pulses between 1.8 V and 6.5 V typical. For encoders powered from 5 V the low theshold 
should be used. For other supply voltages the high threshold will provide greater noise immunity. 

 

Encoder Speed 

 

 
1668 

 

Monitor::System Board::Encoder Slot 1 

Parameters::System Board::Encoder Slot 1 

 

 

 

 

 RPM 
 

 

NEVER 

 

The speed measured by the encoder, in revolutions per minute. 

 

 Parameter Reference  

 D-61

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Encoder Count Reset 

 

 
1669 

 

Same as PNO 1663 
 

 

FALSE 
 

 

 

 

ALWAYS 

 

Resets the encoder count. 

 

Encoder Count 

 

 
1670 

 

Same as PNO 1668 
 

 

 

Min to Max 
 

 

 

NEVER 

 

The encoder count is a 32 bit count which will increment and decrement with the encoder pulses, up to (or down to) 2^31. 

D-62 

Parameter Reference  

Encoder Slot 2 

Parameters::System Board::Encoder Slot 2 

This feature allows you to setup and monitor the operation of the encoder attached to slot 2 of the system board.

 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Encoder Lines 

 

 
1671 

 

Setup::Inputs and Outputs::SB Encoder 

Slot2 
Parameters::System Board::Encoder 
Slot 2 

 

 

2048 
 

 

1 to 100000 
 

 

 

STOPPED 

 

The number of lines per encoder revolution 

 

Encoder Invert 

 

 
1672 

 

Same as PNO 1671 
 

 

FALSE 
 

 

 

 

STOPPED 

 

Reverses the encoder direction if TRUE. 

 

Encoder Type 

 

 
1673 

 

Same as PNO 1671 
 

 


 

 

0:QUADRATURE 
1:CLOCK/DIRECTION 
 

 

 

STOPPED 

 

Normally the encoder will be quadrature.  Exceptionally, eg if a proximity sensor or other pulse train is used, it needs to be clock / 
direction. 

 

High Input Threshold 

 

 
1674 

 

Same as PNO 1671 
 

 

FALSE 
 

 

 

 

STOPPED 

 

Changes the threshold level for the encoder pulses between 1.8 V and 6.5 V typical. For encoders powered from 5 V the low theshold 
should be used. For other supply voltages the high threshold will provide greater noise immunity. 

 

Encoder Speed 

 

 
1675 

 

Monitor::System Board::Encoder Slot 2 

Parameters::System Board::Encoder 
Slot 2 

 

 

 

 

 RPM 
 

 

NEVER 

 

The speed measured by the encoder, in revolutions per minute. 

 

Encoder Count Reset 

 

 
1676 

 

Same as PNO 1671 
 

 

FALSE 
 

 

 

 

ALWAYS 

 

Resets the encoder count. 

 

Encoder Count 

 

 
1677 

 

Same as PNO 1675 
 

 

 

Min to Max 
 

 

 

NEVER 

 

The encoder count is a 32 bit count which will increment and decrement with the encoder pulses, up to (or down to) 2^31. 

 

 

 Parameter Reference  

 D-63

 

Energy Meter 

Monitor::Energy Meter 
Parameters::Motor Control::Energy Meter 

 
This feature measures the electrical energy used by the motor. 
 

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Power kW 

 

 

0380 

 

 

Monitor::Energy Meter 
Parameters::Motor Control::Energy 
Meter 

 

 

x.xx 

 

 

0.00 to 1000000.00 

 

 

 kW 

 

 

NEVER 

 

This diagnostic shows the power being delivered to the load in kilowatts. 

 

Power HP 

 

 

0381 

 

 

Same as PNO 380 

 

 

x.xx 

 

 

0.00 to 1000000.00 

 

 

 HP 

 

 

NEVER 

 

This diagnostic shows the power being delivered to the load in horsepower. 

 

Reactive Power 

 

 

0382 

 

 

Same as PNO 380 

 

 

x.xx 

 

 

0.00 to 1000000.00 

 

 

 kVAr 

 

 

NEVER 

 

This diagnostic shows the reactive power being delivered to the load in kilo volt-amperes reactive. 

 

Energy kWh 

 

 

0383 

 

 

Same as PNO 380 

 

 

x.xx 

 

 

0.00 to 10000000.00 

 

 

 kWh 

 

 

NEVER 

 

This diagnostic shows the total energy consumed by the load in kilowatt hours. 

 

Power Factor Est 

 

 

0385 

 

 

Same as PNO 380 

 

 

x.xx 

 

 

0.00 to 1.00 

 

 

 

 

 

 

NEVER 

 

This diagnostic shows the power factor estimate (between 0 and 1). 

 

Power Factor Angle Est 

 

 

0386 

 

 

Parameters::Motor Control::Energy 
Meter 

 

 

x.xx 

 

 

0.00 to 90.00 

 

 

 deg 

 

 

NEVER 

 

This diagnostic shows the power factor angle estimate. 

D-64 

Parameter Reference  

Parameter Name 

No. 

Path 

Default 

Range 

Units 

Writable 

 

Reset Energy Meter 

 

 

0389 

 
 

 

Parameters::Motor Control::Energy 
Meter 

 

 

FALSE 

 

 

 

 

ALWAYS 

 

When 

Reset Energy Meter

 is set to TRUE, the 

Energy KWh

 parameter is reset to zero automatically when the maximum value is 

reached. 

When 

Reset Energy Meter

 is set to FALSE, the 

Energy KWh

 parameter is held at the maximum value when the maximum value has 

been reached 

Changing this from FALSE to TRUE at anytime will cause the 

Energy KWh

 parameter to be reset to zero. 

 

 

 

 

 

 

 

 