Preface
General information and
1
networking
2
Operator panels
SINUMERIK
Handheld units
3
SINUMERIK 840D sl
Operator Components and
4
Machine control panels
Networking
Keyboards and additional
5
components
Manual
A
Appendix
Valid for: SINUMERIK 840D sl / 840DE sl control
03/2016
6FC5397-1AP40-5BA3
Preface
SINUMERIK documentation
The SINUMERIK documentation is organized in the following categories:
● General documentation
● User documentation
● Manufacturer/service documentation
Additional information
You can find information on the following topics at http://www.siemens.com/motioncontrol/
docu:
● Ordering documentation / documentation overview
● Additional links to download documents
● Using documentation online (find and search in manuals/information)
For any questions about the technical documentation (e.g. suggestions for improvement,
corrections), please send an e-mail to the following address:
mailto:docu.motioncontrol@siemens.com
My Documentation Manager (MDM)
Under the following link you will find information on how to compile OEM-specific machine
documentation based on the Siemens content:
Training
Information about training courses can be found at:
SITRAIN - Siemens training for products, systems and solutions in automation technology
SinuTrain - training software for SINUMERIK
FAQs
You can find Frequently Asked Questions in the Service&Support pages under Product
Operator Components and Networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
3
Preface
SINUMERIK
You can find information about SINUMERIK at the following link:
Target group
This documentation is intended for:
● Project engineers, electricians and installers
● Maintenance and service personnel
Benefits
The manual provides information on the components and functions of devices so that the target
group is capable of installing, setting up, testing, operating, and troubleshooting the devices
correctly and in absolute safety.
Standard scope
This documentation only describes the functionality of the standard version. Additions or
revisions made by the machine manufacturer are documented by the machine manufacturer.
Other functions not described in this documentation might be executable in the controller. This
does not, however, represent an obligation to supply such functions with a new controller or
when servicing.
For the sake of simplicity, this documentation does not contain all detailed information about
all types of the product and cannot cover every conceivable installation, operation, or
maintenance situation.
Technical Support
You will find telephone numbers for other countries for technical support in the Internet under
EC Declaration of Conformity
The EC Declaration of Conformity for the EMC Directive can be found on the Internet at:
Operator Components and Networking
4
Manual, 03/2016, 6FC5397-1AP40-5BA3
Fundamental safety
1
instructions
2
System overview
3
Application planning
SINUMERIK
Connecting
4
SINUMERIK 840D sl
General information and networking
5
Networking
Manual
Valid for: SINUMERIK 840D sl / 840DE sl control
03/2016
6FC5397-1AP40-5BA3
Table of contents
1
Fundamental safety instructions
5
1.1
General safety instructions
5
1.2
Handling electrostatic sensitive devices (ESD)
8
1.3
Industrial security
8
1.4
Residual risks of power drive systems
10
2
System overview
11
2.1
Application
11
2.2
System configuration
11
2.3
Overview of operator components
13
3
Application planning
15
3.1
Secondary electrical conditions
15
3.1.1
Power supply
15
3.1.2
Grounding concept
16
3.1.3
EMC compatibility
16
3.2
Ambient climatic and mechanical conditions
18
3.2.1
Transport and storage conditions
18
3.2.2
Operating conditions
20
3.2.3
Cooling
21
3.3
Standards and approvals
24
3.4
Recycling and disposal
25
4
Connecting
27
4.1
Pin assignment of the interfaces
27
4.2
Handling membrane connectors
41
5
Networking
43
5.1
System settings
43
5.1.1
Settings for SINUMERIK solution line
43
5.1.2
System boot with system network
45
5.1.3
Thin Client Unit (TCU)
46
5.1.4
Factory default settings
47
5.2
Commissioning TCU
49
5.2.1
Using the TCU's main menu
49
5.2.2
Using additional TCU menus
51
5.2.3
How to register a TCU on the system network
61
5.2.4
How to calibrate a touch panel
65
5.2.5
Connecting-up the SIMATIC Thin Client Touch Panel
67
5.2.6
This is how you configure the SIMATIC Thin Client Touch Panel
68
5.2.7
Settings in the "config.ini" file
70
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
3
Table of contents
5.2.8
Settings in the "TCU.ini" file
72
5.2.9
Displacement mechanism for TCUs
78
5.2.10
Disable switchover between TCU via PLC
80
5.2.11
Example: How to select the behavior of the TCUs during boot up
82
5.3
Network configuration
83
5.3.1
Permissible network topologies
83
5.3.2
Networks without connection to the company network
84
5.3.2.1
Configuration 1: NCU and TCU
84
5.3.2.2
Configuration 2: NCU and PCU with direct OP
85
5.3.3
Networks with NCU connection to the company network
86
5.3.3.1
Configuration 3: NCU and TCU
86
5.3.3.2
Configuration 4: NCU and PCU with direct OP
87
5.3.3.3
Configuration 5: PCU with TCU on NCU
88
5.3.3.4
Connecting the programming device (PG) to the NCU
89
5.3.4
Example: Configuring a VNC connection to a PC
89
5.3.5
Application example
91
5.4
Service and diagnostics
93
5.4.1
Booting of the TCU
93
Index
95
General information and networking
4
Manual, 03/2016, 6FC5397-1AP40-5BA3
Fundamental safety instructions
1
1.1
General safety instructions
DANGER
Danger to life due to live parts and other energy sources
Death or serious injury can result when live parts are touched.
● Only work on electrical devices when you are qualified for this job.
● Always observe the country-specific safety rules.
Generally, six steps apply when establishing safety:
1. Prepare for shutdown and notify all those who will be affected by the procedure.
2. Disconnect the machine from the supply.
- Switch off the machine.
- Wait until the discharge time specified on the warning labels has elapsed.
- Check that it really is in a no-voltage condition, from phase conductor to phase
conductor and phase conductor to protective conductor.
- Check whether the existing auxiliary supply circuits are de-energized.
- Ensure that the motors cannot move.
3. Identify all other dangerous energy sources, e.g. compressed air, hydraulic systems, or
water.
4. Isolate or neutralize all hazardous energy sources by closing switches, grounding or short-
circuiting or closing valves, for example.
5. Secure the energy sources against switching on again.
6. Ensure that the correct machine is completely interlocked.
After you have completed the work, restore the operational readiness in the inverse sequence.
WARNING
Danger to life through a hazardous voltage when connecting an unsuitable power supply
Touching live components can result in death or severe injury.
● Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV-
(Protective Extra Low Voltage) output voltages for all connections and terminals of the
electronics modules.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
5
Fundamental safety instructions
1.1 General safety instructions
WARNING
Danger to life when live parts are touched on damaged devices
Improper handling of devices can cause damage.
For damaged devices, hazardous voltages can be present at the enclosure or at exposed
components; if touched, this can result in death or severe injury.
● Ensure compliance with the limit values specified in the technical data during transport,
storage and operation.
● Do not use any damaged devices.
WARNING
Danger to life through electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
● As a minimum, connect cable shields and the cores of cables that are not used at one end
at the grounded housing potential.
WARNING
Danger to life due to electric shock when not grounded
For missing or incorrectly implemented protective conductor connection for devices with
protection class I, high voltages can be present at open, exposed parts, which when touched,
can result in death or severe injury.
● Ground the device in compliance with the applicable regulations.
WARNING
Danger to life due to fire spreading if housing is inadequate
Fire and smoke development can cause severe personal injury or material damage.
● Install devices without a protective housing in a metal control cabinet (or protect the device
by another equivalent measure) in such a way that contact with fire is prevented.
● Ensure that smoke can only escape via controlled and monitored paths.
General information and networking
6
Manual, 03/2016, 6FC5397-1AP40-5BA3
Fundamental safety instructions
1.1 General safety instructions
WARNING
Danger to life through unexpected movement of machines when using mobile wireless
devices or mobile phones
Using mobile wireless devices or mobile phones with a transmit power > 1 W closer than
approx. 2 m to the components may cause the devices to malfunction, influence the functional
safety of machines therefore putting people at risk or causing material damage.
● Switch the wireless devices or mobile phones off in the immediate vicinity of the
components.
WARNING
Danger to life due to fire if overheating occurs because of insufficient ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent
fire and smoke. This can cause severe injury or even death. This can also result in increased
downtime and reduced service lives for devices/systems.
● Ensure compliance with the specified minimum clearance as ventilation clearance for the
respective component.
WARNING
Danger to life when safety functions are inactive
Safety functions that are inactive or that have not been adjusted accordingly can cause
operational faults on machines that could lead to serious injury or death.
● Observe the information in the appropriate product documentation before commissioning.
● Carry out a safety inspection for functions relevant to safety on the entire system, including
all safety-related components.
● Ensure that the safety functions used in your drives and automation tasks are adjusted
and activated through appropriate parameterizing.
● Perform a function test.
● Only put your plant into live operation once you have guaranteed that the functions relevant
to safety are running correctly.
Note
Important safety notices for Safety Integrated functions
If you want to use Safety Integrated functions, you must observe the safety notices in the Safety
Integrated manuals.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
7
Fundamental safety instructions
1.3 Industrial security
1.2
Handling electrostatic sensitive devices (ESD)
Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules
or devices that may be damaged by either electric fields or electrostatic discharge.
NOTICE
Damage through electric fields or electrostatic discharge
Electric fields or electrostatic discharge can cause malfunctions through damaged individual
components, integrated circuits, modules or devices.
● Only pack, store, transport and send electronic components, modules or devices in their
original packaging or in other suitable materials, e.g conductive foam rubber of aluminum
foil.
● Only touch components, modules and devices when you are grounded by one of the
following methods:
- Wearing an ESD wrist strap
- Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring
● Only place electronic components, modules or devices on conductive surfaces (table with
ESD surface, conductive ESD foam, ESD packaging, ESD transport container).
1.3
Industrial security
Note
Industrial security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly that
you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should also
be considered. For more information about industrial security, visit this address (http://
To stay informed about product updates as they occur, sign up for a product-specific
General information and networking
8
Manual, 03/2016, 6FC5397-1AP40-5BA3
Fundamental safety instructions
1.3 Industrial security
WARNING
Danger as a result of unsafe operating states resulting from software manipulation
Software manipulation (e.g. by viruses, Trojan horses, malware, worms) can cause unsafe
operating states to develop in your installation which can result in death, severe injuries and/
or material damage.
● Keep the software up to date.
You will find relevant information and newsletters at this address (http://
support.automation.siemens.com).
● Incorporate the automation and drive components into a holistic, state-of-the-art industrial
security concept for the installation or machine.
You will find further information at this address (http://www.siemens.com/
industrialsecurity).
● Make sure that you include all installed products into the holistic industrial security concept.
WARNING
Danger to life due to software manipulation when using exchangeable storage media
Storing files onto exchangeable storage media amounts to an increased risk of infection, e.g.
with viruses and malware. As a result of incorrect parameterization, machines can
malfunction, which in turn can lead to injuries or death.
● Protect files stored on exchangeable storage media from malicious software by taking
suitable protection measures, e.g. virus scanners.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
9
Fundamental safety instructions
1.4 Residual risks of power drive systems
1.4
Residual risks of power drive systems
When assessing the machine- or system-related risk in accordance with the respective local
regulations (e.g., EC Machinery Directive), the machine manufacturer or system installer must
take into account the following residual risks emanating from the control and drive components
of a drive system:
1.
Unintentional movements of driven machine or system components during commissioning,
operation, maintenance, and repairs caused by, for example,
- Hardware and/or software errors in the sensors, control system, actuators, and cables
and connections
- Response times of the control system and of the drive
- Operation and/or environmental conditions outside the specification
- Condensation/conductive contamination
- Parameterization, programming, cabling, and installation errors
- Use of wireless devices/mobile phones in the immediate vicinity of electronic
components
- External influences/damage
- X-ray, ionizing radiation and cosmic radiation
2.
Unusually high temperatures, including open flames, as well as emissions of light, noise,
particles, gases, etc., can occur inside and outside the components under fault conditions
caused by, for example:
- Component failure
- Software errors
- Operation and/or environmental conditions outside the specification
- External influences/damage
3.
Hazardous shock voltages caused by, for example:
- Component failure
- Influence during electrostatic charging
- Induction of voltages in moving motors
- Operation and/or environmental conditions outside the specification
- Condensation/conductive contamination
- External influences/damage
4.
Electrical, magnetic and electromagnetic fields generated in operation that can pose a risk
to people with a pacemaker, implants or metal replacement joints, etc., if they are too close
5.
Release of environmental pollutants or emissions as a result of improper operation of the
system and/or failure to dispose of components safely and correctly
For more information about the residual risks of the drive system components, see the relevant
sections in the technical user documentation.
General information and networking
10
Manual, 03/2016, 6FC5397-1AP40-5BA3
System overview
2
2.1
Application
Overview
SINUMERIK 840D sl offers modularity, openness, flexibility and uniform structures for
operation, programming, and visualization. It provides a system platform with trend-setting
functions for almost all technologies.
Integrated into the SINAMICS S120 drive system and complemented by an automation
system, such as SIMATIC S7-300, the SINUMERIK 840D sl forms a complete digital system
that is ideally suited for the mid to upper performance range.
SINUMERIK 840D sl is characterized by:
● A high degree of flexibility
● Excellent dynamic response and precision
● Optimum integration into networks
Benefits
● Outstanding performance and flexibility for multi-axis systems of average to high complexity
thanks to scalable hardware and software.
● Universal openness of the user interface, the PLC and the NC kernel to allow integration
of your specialist know-how.
● Integrated safety functions for man and machine: SINUMERIK Safety Integrated
● Comprehensive range of products for integrating machine tools into communication,
engineering and production processes: SINUMERIK Integrate
Field of application
The SINUMERIK 840D sl can be used worldwide in tool and mold making, for high-speed
cutting applications, for wood and glass processing, for handling operations, in transfer lines
and rotary indexing machines, for mass production and JobShop production.
The SINUMERIK 840DE sl is available as an export version for use in countries where approval
is required.
2.2
System configuration
SINUMERIK 840D sl combines CNC, HMI, PLC, closed-loop control, and communication tasks
within a single NCU (Numerical Control Unit).
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
11
System overview
2.2 System configuration
Components
For operating, programming and visualization, the corresponding operator software is already
integrated in the CNC software. For increased operating performance, the SINUMERIK PCU
50.5 industrial PC can be used.
Up to four distributed OPs can be operated on one NCU / PCU. The operator panel can be
installed as a Thin Client at a distance of up to 100 m.
6,180(5,.
6,180(5,. RSHUDWRU SDQHO IURQWV ZLWK 7&8
6,180(5,.
+7
3&8
,QGXVWULDO (WKHUQHW
352),1(7
352),%86
,QGXVWULDO (WKHUQHW
'5,9( &/L4
(7
SUR
6,1$0,&6 6
1;
ವವವ
3RZHU VXSSO\
ವವವ
6,180(5,.
' VO
ZLWK 6,1$0,&6 6
0DLQ VSLQGOH PRWRU
6HUYR PRWRUV
Image 2-1
Typical topology of the SINUMERIK 840D sl complete system
The following components can be connected to the SINUMERIK 840D sl:
● SINUMERIK operator panel front with PCU/TCU
● SINUMERIK machine control panel MCP/MPP
● SINUMERIK handheld units
● SIMATIC CE panel
● SIMATIC thin client (as of firmware V1.4)
● Distributed PLC I/O via PROFIBUS DP or PROFINET IO
● SINUMERIK PP 72/48 I/O module
● SINUMERIK ADI 4 analog drive interface for four axes
● SINAMICS S120 drive system
● Feed and main spindle motors
General information and networking
12
Manual, 03/2016, 6FC5397-1AP40-5BA3
System overview
2.3 Overview of operator components
2.3
Overview of operator components
Overview of the operator components
6,180(5,. 23
7
6,180(5,. 23
6,180(5,. 23
6
6,180(5,. 23
&
6,180(5,. 23
6,180(5,. 23
6,180(5,. 23
$
6,180(5,. 23
23
$7 73
$ 73
$7 23
EODFN
6,180(5,. 7&8
6,180(5,. 7&8
6,180(5,. 3&8
Image 2-2
Operator panels
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
13
System overview
2.3 Overview of operator components
6,180(5,. .%
&
6,180(5,. .%
&
3& NH\ERDUG VWDQGDUG
&DUG UHDGHU
.%3& 8/ 86
86%b
6,180(5,. 0&3
& 31
6,180(5,. 0&3
& 31
6,180(5,. +7
+DQGZKHHO
6,180(5,. 0&3
31
6,180(5,. 0&3
31
6,180(5,. 033
6,180(5,. 033
,( +
6,180(5,. +7
0LQL KDQGKHOG XQLW
Image 2-3
Machine control panels, handheld units, keyboards and additional components (selection)
General information and networking
14
Manual, 03/2016, 6FC5397-1AP40-5BA3
Application planning
3
3.1
Secondary electrical conditions
3.1.1
Power supply
Requirements for DC power supplies
DANGER
Danger of death caused by unsafe power supply
The DC power supply must be implemented as a circuit of Category PELV/DVC A according
to EN 61800-5-1.
WARNING
Inadequately fused supply cables can be life-threatening
In the case of supply lines > 10 m, protectors must be installed at the device input in order to
protect against lightning (surge).
The DC power supply must be connected to the ground/shield of the NC for EMC and/or
functional reasons. For EMC reasons, this connection should only be made at one point. As
a rule, the connection is provided as standard in the S7-300 I/Os. In exceptional
circumstances when this is not the case, the ground connection should be made on the
grounding rail of the NC cabinet (also refer to /EMC/EMC Installation Guide.)
Table 3-1
Requirements of the DC power supply
Rated voltage
According to EN 61131-2
24 VDC
Voltage range (mean value)
20.4 VDC to 28.8 VDC
Voltage ripple, peak/peak
5% (unsmoothed 6-pulse recti-
Powering up time when switched
fication)
on
any
Non-periodic overvoltages
≤ 35 V
Period of overvoltage
≤ 500 ms
Recover time
≥ 50 s
Events per hour
≤ 10
Transient voltage interruptions
Downtime
≤ 3 ms
Recovery time
≥ 10 s
Events per hour
≤ 10
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
15
Application planning
3.1 Secondary electrical conditions
3.1.2
Grounding concept
Components
The SINUMERIK 840D sl system consists of a number of individual components which have
been designed so that the system complies with the appropriate EMC and safety standards.
The individual system components are:
● Numerical Control Unit (NCU)
● Machine Control Panel (MCP), Machine Pushbutton Panel (MPP)
● Keyboard
● Operator panels (operator panel front + TCU/PCU)
● Distributor box and handheld unit
● S7-300 I/O with IM 153 interface module
Grounding measures
The individual modules are attached to a metal cabinet panel. Insulating paints on the mounting
points (e.g. tension jacks) must be removed.
It is permissible to cluster the operator control components regarding connection/potential
bonding.
Example: The control panel on the swivel arm.
It is sufficient in this instance to connect the ground connections of, for example, the PCU,
TCU, and operator panel front using a cable and to route a shared grounding conductor to the
central ground connection in the control cabinet.
Additional references
EMC Design Guidelines
3.1.3
EMC compatibility
In addition to the protective grounding of system components, special precautions must be
taken to guarantee safe, trouble-free operation of the system. These measures include
shielded signal lines, special equipotential bonding connections, and isolation and shielding
measures.
Shielded signal cables
● For safe and fault-free operation of the system, the specified cables must be used.
● For digital signal transmission, the shield must have a conductive connection at both sides
of the housing.
General information and networking
16
Manual, 03/2016, 6FC5397-1AP40-5BA3
Application planning
3.1 Secondary electrical conditions
Cable definition
Definition:
● Signal cables (example)
- Data cables (Ethernet, PROFIBUS, sensor cables, etc.)
- Digital I/Os
- Cables for safety functions (emergency stop, enabling)
● Power cables (example)
- Low-voltage supply lines (230 VAC, +24 VDC, etc.)
- Motor cables
Rules for routing cables
In order to achieve the greatest possible EMC compatibility for the complete system (control,
power unit, machine), the following EMC measures must be carefully observed:
● If necessary, signal and power cables may cross one another (if possible at an angle of
90°), but must never be laid close or parallel to one another.
● Only use cables approved by SIEMENS for the signal lines from and to the Control Unit.
● Signal cables must not be routed close to strong external magnetic fields (e.g. motors and
transformers).
● If signal lines cannot be routed a sufficient distance away from other cables, they must be
installed in grounded cable ducts (metal).
● The operator panel fronts, MCPs, MPPs, and full keyboards must be installed in metallically
enclosed EMC-compatible housings.
Note
For further information on interference suppression measures and the connection of
shielded cables, please refer to the EMC Installation Guide.
EMC limit values in South Korea
The EMC limit values to be complied with for South Korea correspond to the limit values of the
EMC product standard for variable-speed electric drives EN 61800-3, Category C2, or limit
value class A, Group 1 according to EN 55011. By applying suitable supplementary measures,
the limit values according to Category C2 or according to limit value class A, Group 1, are
maintained. Further, additional measures may be required, for instance, using an additional
radio interference suppression filter (EMC filter).
The measures for EMC-compliant design of the system are described in detail in this manual
respectively in the Installation Guideline EMC.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
17
Application planning
3.2 Ambient climatic and mechanical conditions
Please note that the final statement on compliance with the standard is given by the respective
label attached to the individual unit.
3.2
Ambient climatic and mechanical conditions
3.2.1
Transport and storage conditions
The components of the SINUMERIK 840D sl system exceed the requirements according to
EN 61800-2 with regard to shipping and storage conditions.
The following data applies under the following conditions:
● Long-term storage in the transport and product packaging:
At weather-protected locations that have continuous contact with outside air through
openings.
● Transport in the transport packaging:
- In unventilated containers under conditions not protected from weather effects.
- In the “cold" in accordance with outside air.
- Air transport in the air-conditioned cargo hold.
Table 3-2
Ambient conditions during storage and transport
Type of condition
Permissible range/class
Transport
Storage
Classification
EN 60721-3-2
EN 60721-3-1
Climate class
2K4
1K4
Ambient temperature 1)
-40° C ... +70° C
-25° C ... +55° C
Biological environmental condi-
2B1 2)
1B1 2)
tions
Chemically active environmental
2C2 3)
1C2 3)
conditions
Maximum permissible tempera-
Direct interaction in air/air:
30 k/h
ture change
-40°/+30° C at 95% relative
humidity
Relative humidity (without conden-
5 to 95%
sation)
Precipitation, rain
6 mm/min 2)
Not permissible
Water other than rain
1 m/s and wet loading surfa-
Not permis-
1 m/s and wet
ces 4)
sible 5)
loading surfaces 4)
General information and networking
18
Manual, 03/2016, 6FC5397-1AP40-5BA3
Application planning
3.2 Ambient climatic and mechanical conditions
Type of condition
Permissible range/class
Height
Max. 4,000 m above sea level
Condensation, splash water,
Permissible
Not permis-
Permissible 4)
icing, salt spray
sible 5)
1)
Transport and storage of operator panel fronts and diskette drives: -20° C to +55° C.
2)
Mold growth, slime, rodents, termites and other animal vermin are not permissible.
3)
In marine- and weather-resistant transport packaging (container).
4)
For storage in the transport packaging.
5)
For storage in the product packaging.
Note
Remove the transport protective foil and packaging material before installing the components.
Shipping backup batteries
Backup batteries must only be shipped in the original packaging. No special authorization is
required to ship backup batteries. The lithium content is approximately 300 mg.
Note
The backup battery is classified as a hazardous substance, Class 9 in accordance with the
relevant air-freight transportation regulations.
Storage of backup batteries
Always store backup batteries in a cool and dry place. The batteries have a maximum shelf
life of 10 years.
Rules for handling backup batteries
WARNING
Incorrect handling of backup batteries can lead to a risk of ignition, explosion and combustion
The stipulations of DIN EN 60086-4, in particular regarding avoidance of mechanical or
electrical tampering of any kind, must be complied with.
● Do not open a battery. Replace a faulty battery only with the same type.
● Obtain replacement batteries only from Siemens.
● Always try to return low batteries to the manufacturer or deliver these to a registered
recycling company.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
19
Application planning
3.2 Ambient climatic and mechanical conditions
3.2.2
Operating conditions
The components of the SINUMERIK 840D sl system are intended for a weatherproof, fixed
location. The documented
environmental conditions apply to the climate in the immediate vicinity of the units and to the
entry of the cooling air. They exceed the requirements according to EN 60204-1, EN 61800-2,
EN 61131-2 and IEC 62477-1.
NOTICE
Damage to components by coolants and lubricants
The SINUMERIK operator components have been designed for industrial use, particularly on
machine tools and production machines. This also takes into account the use of commercially
available coolants and lubricants. The use of aggressive compounds and additives can
damage components and result in their failure.
Contact between the operator components and coolants and lubricants should be avoided
as far as possible, as resistance to all coolants and lubricants cannot be guaranteed.
Table 3-3
Ambient conditions for operation
Environmental conditions
Application areas
Remarks
Climatic environmental conditions
Climate class
Better than class 3K3
According to EN 60721-3-3
Permissible ambient tempera-
0 ... 45 °C (32 ... 113
Except PCU50.5;
ture when installed vertically
°F), up to 2000 m
front-side for OP, MCP/MPP and CNC
(6562 ft) above sea
standard keyboards KB.
level
0 ... 55 °C (32 ... 131
All, rear-side for OP, MCP/MPP and CNC
°F), up to 2000 m
standard keyboards KB.
(6562 ft) above sea
level
5 ... 55 °C (41 ... 131
For PCU50.5
°F), up to 2000 m
(6562 ft) above sea
level
Above an altitude of 2000 m (6562 ft), the max. ambient temperature
decreases by 7 °C (44.6 °F) for every 1000 m (3281 ft) increase in
altitude
Relative humidity (without con-
5% to 95% (60% when corrosive gases and/or dusts are present)
densation)
Condensation, formation of ice
Not permissible
Dripping water, spray, splash
Not permissible
All components, except ...
water, jet-water according to de-
Permissible
For handheld units, front side of operator
gree of protection
and machine control panels (MCP and
MPP), front side of the keyboards KB 310
and KB 483C
Max. installation altitude
Up to 4000 m (13123 ft) above sea level
Air pressure
620 hPa ... 1060 hPa
According to altitude range 0 m to 4000 m
(0 ft to 13123 ft) above sea level
General information and networking
20
Manual, 03/2016, 6FC5397-1AP40-5BA3
Application planning
3.2 Ambient climatic and mechanical conditions
Environmental conditions
Application areas
Remarks
Biological, chemical and mechanical influences, pollutants
Biological environmental conditions
Class 3B1 according to EN 60 721-3-3:
Mold, mold growth, slime, rodents, termite
and other animal vermin are not permissible.
Chemically active environmental conditions
Class 3C1 according to EN 60721-3-3
Mechanically active environmental conditions
Class 3S1 according to EN 60721-3-3:
Conductive dust not permissible.
Classification of the mechanical
3M3 for components on the machine
environment
3M1/3M2 for components in the control cab-
inet
Degree of contamination
2
EMC conducted / radiation
Class C3 according to EN 61800-3
Note
The user must consider radio interference for the complete system. Particular attention should
be paid to cabling. Please contact your sales representative for assistance and support.
If compliance with limit value class C2 is required, please contact your local sales
representative.
3.2.3
Cooling
To calculate the heat dissipation, the total power loss PVtotal of all heat-generating components
in a housing must be taken into account.
Total power loss PVtotal = PV1 + PV2 + PV3 +... [W]
Convection surface area A [m2]:
The surface areas of the front and bottom sides are not included in the convection surface
area calculation.
Note
A recommended value for the power loss of the operator control components is contained in
the "Technical data" section of the associated component (see "Power consumption").
Means of heat dissipation
Heat dissipation can take place as follows:
● Heat dissipation by natural convection
● Heat dissipation by natural convection and internal air turbulence
● Heat dissipation by open-circuit cooling
● Heat dissipation by open-circuit ventilation
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
21
Application planning
3.2 Ambient climatic and mechanical conditions
+HDW GLVVLSDWLRQ
+HDW GLVVLSDWLRQ
XVLQJ QDWXUDO FRQYHFWLRQ
XVLQJ QDWXUDO FRQYHQWLRQ DQG
LQWHUQDO WXUEXOHQFH
2SHUDWRU
2SHUDWRU
YROXPHWULF IORZ RI WKH IDQ
SDQHO IURQW
SDQHO IURQW
P K
7
7
7
7
7KH UHTXLUHG IUHH FRQYHFWLRQ VXUIDFH $>P @ RI WKH
URRP WR EH FRQYHUWHG VWHHO RU DOXPLQXP VKHHWLQJ
PP WKLFNQHVV LV FDOFXODWHG EDVHG RQ
D WHPSHUDWXUH GLIIHUHQFH 7
7
ෙ7 ุ
. DSSUR[LPDWHG IURP
39
>:@
39JHV>:@
$ >P @
JHV
$ >P @
˂7 >.@
˂7 >.@
+HDW GLVVLSDWLRQ
+HDW GLVVLSDWLRQ
XVLQJ RSHQ FLUFXLW YHQWLODWLRQ
XVLQJ RSHQ FLUFXLW YHQWLODWLRQ
7KH UHTXLUHG YROXPHWULF
IORZ IRU GLVVLSDWLQJ WKH KHDW
ORVV LV FDOFXODWHG XVLQJ
DSSUR[LPDWLRQV IURP
2SHUDWRU
2SHUDWRU
SDQHO IURQW
SDQHO IURQW
39JHV >:@
9 >P K@
7
7
7
7
˂7 >.@
Image 3-1
Means of heat dissipation
Fan design
● The fan must be positioned to produce an optimum heat dissipation. A clearance of 10 mm
must be maintained in front of the fan.
● The inlet and outlet slots must remain free for the open-circuit ventilation.
● Air filters must be provided to maintain the permitted environmental conditions.
NOTICE
Damage to the operating components caused by temperatures that are too high or too low
Contaminated air filters impair the desired heat dissipation. For handling the air filters, pay
attention to:
● Proper handling
● Regular replacement
● Correct disposal
General information and networking
22
Manual, 03/2016, 6FC5397-1AP40-5BA3
Application planning
3.2 Ambient climatic and mechanical conditions
Guidelines
If the convection area A [m2] does not suffice for the "heat dissipation using natural convection",
then use:
● "Heat dissipation using natural convection and internal turbulence" for hot spots and heat
concentrations in housings subject to space constraints. The total power loss PLtot for
thermally critical applications can be determined as follows:
- Current measurement for a 24 V supply voltage
- Power loss PLtot [W] = U (24 V) * |measured value in ampères|
● Heat dissipation using open-circuit ventilation
Calculation of the volumetric flow
The power loss (thermal) dissipated by the components in an operator unit is to be dissipated
using open-circuit ventilation. The volumetric flow V required for this should be calculated at
a difference in temperature of T2 - T1 = ΔT ≥ 10K.
([DPSOH IRU KHDW GLVVLSDWLRQ ZLWK RSHQ FLUFXLW YHQWLODWLRQ
3&8
ZLWK 23
3&8
&DOFXODWLRQ RI WKH SRZHU ORVV
LQFOXGLQJ LQWHUQDO SRZHU VXSSO\ XQLW
23
:
3&8
:
39JHV
:
PD[
:
7
7
39JHV
>:@
9
>P K@
˂7 >.@
23
([WHUQDO WHPSHUDWXUH
7
r&
ය ˂7
,QWHUQDO WHPSHUDWXUH
7
r&
Image 3-2
Calculating heat dissipation for PCU 50.5 with OP 019
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
23
Application planning
3.3 Standards and approvals
3.3
Standards and approvals
Approvals
CE approval
Image 3-3
CE marking
The operator panels and the safety-relevant accessories satisfy the requirements and
protection objectives of the following EC directives. The operator panels and the safety-
relevant accessories comply with the harmonized European standards (EN), promulgated in
the Official Journals of the European Community:
●
2004/108/EC "Electromagnetic Compatibility" (EMC directive)
● Directive 2006/42/EC of the European Parliament and Council of May 17, 2006, on
machinery, and Directive 95/16/EC (amendment)
SIBE Switzerland Certification Service
For the HT 2 and HT 8 units.
Image 3-4
Symbol of the certifying body
HT 2
The HT 2 operator panel and the safety-relevant accessories (is identified in the "Accessories"
section for the respective devices) satisfy Category 3, PL d according to EN ISO 13849-1:2008.
The safety function Enabling device for special mode control and the emergency stop button
satisfy the following requirements:
● Category 3, PL d according to EN ISO 13849-1:2008
● Requirements of EN 60204-1:2006, when complying with the safety instructions in the
relevant chapters of this documentation
HT 8
The HT 8 operator panel and the safety-relevant accessories (is identified in the "Accessories"
section for the respective devices) satisfy Category 3, PL d according to EN ISO 13849-1:2008.
The emergency stop button meets the following requirements:
● Category 3, PL d according to EN ISO 13849-1:2008
● Requirements of EN 60204-1:2006, when complying with the safety instructions in the
relevant chapters of this documentation
General information and networking
24
Manual, 03/2016, 6FC5397-1AP40-5BA3
Application planning
3.4 Recycling and disposal
The safety function Enabling device for special mode control satisfies the following
requirements:
● Category 4, PL e according to EN ISO 13849-1:2008
● Requirements of EN 60204-1:2006, when complying with the safety instructions in the
relevant chapters of this documentation
Address:
NSBIV AG, SIBE Switzerland, Brünigstrasse 18, CH-6005 Lucerne
Accreditation SCESp 0046 / Notified Body 1247
Number of the prototype test certificate: No. 1416
Risk assessment
The following standards must be used to perform the risk assessment:
● EN ISO 12100-1:2003 and EN ISO 12100-2:2003, General Design Guidelines for Machines
● EN ISO 14121-1:2007, Risk Assessment for Machinery
● EN ISO 13849-1:2008, Safety-related Parts of Machines
These considerations result in a category (B, 1, 2, 3, 4) and a performance level (PL a to e) in
accordance with EN ISO 13849-1:2008 that ultimately dictate how the safety-related parts of
the system to be monitored must be constructed.
The connection examples with different monitoring units in "Handheld units", Section: "HT 2",
Section: "Connections" → "Connection examples for acknowledgment button and Emergency
Stop button" can also be used for other operator panels and demonstrate how Category 3, PL
d according to EN ISO 13849-1:2008 can be attained with the safety-related parts of the
operator panels. Note that the overall concept of the installation must be designed with this in
mind.
3.4
Recycling and disposal
Products should be disposed of corresponding to the relevant national regulations.
The products described in this manual can be mostly recycled due to the fact that they contain
very few damaging substances. To recycle and dispose of your old device in an
environmentally friendly way, please contact an appropriate disposal company.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
25
Application planning
3.4 Recycling and disposal
General information and networking
26
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4
4.1
Pin assignment of the interfaces
The pins of the component interfaces are assigned as specified in the tables below. Any
deviations are indicated at the relevant point.
Signal type:
I
Input
O
Output
B
Bidirectional (inputs/outputs)
V
Power supply
-
Ground (reference potential) or N.C. (not connected)
Power supply interface
Connector type:
Terminal block, 3-pin plug connector
Max. cable length:
10 m
Table 4-1
Assignment of the power supply interface
Pin
Name
Type
Meaning
1
P24 (+)
-
24 VDC potential (20.4 to 28.8 VDC)
2
M24 (-)
Ground 24 V
VI
3
SHIELD (PE)
Shield potential
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
27
Connecting
4.1 Pin assignment of the interfaces
Serial interface COM1
9-pin sub-D connector
Table 4-2
Assignment of the serial interface COM1 (V.24/RS232)
Connector
Pin
Name
Type
Remark
1
DCD (M5)
Receive signal level (carrier)
I
2
RxD (D2)
Serial receive data
3
TxD (D1)
Serial transmit data
O
4
DTR (S1)
Data terminal ready
5
GND (E2)
-
Ground (reference potential)
6
DSR (M1)
I
Data Set Ready
7
RTS (S2)
O
Request To Send
8
CTS (M2)
Clear To Send
I
9
RI (M3)
Incoming call
USB interfaces
The USB interfaces are implemented as sockets and comply with the generally valid standard.
The version information (1.1, 2.0 etc.), the maximum velocity (low speed, full speed, etc.) and
the socket type (A or B) are documented in the individual sections for the associated devices.
In principle, USB interfaces have the following characteristics:
● Integrated power supply up to 500 mA for each socket.
● Maximum cable length 3 m (Length including the supply cable to the hub and the connected
terminal device; only 1 hub at maximum is permitted. It should be noted that some
keyboards already have a hub.)
NOTICE
Cables that are too long can cause the screen to freeze
Observe the following restrictions for the USB front interface for connecting operator
panels to the keyboard, mouse or USB FlashDrive:
● Maximum cable length: 1.8 m
● Extension cables are not permissible
● Hot-plugging-capable devices are connected during operation and are identified
automatically.
Note
Correct identification is only guaranteed for USB I/Os that comply to 100% with the USB
specification.
General information and networking
28
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.1 Pin assignment of the interfaces
Table 4-3
Assignment of the USB interface
Type A socket
Type B socket
Pin
Name
Type
Remark
1
P5V_fused
V
+ 5 V (fused)
2
Data-
Data -
B
3
Data+
Data +
4
GND
V
Ground (reference potential)
USB sticks
If you want to connect a USB stick to the USB interface, preferably use the tested SIMATIC
USB stick 16 GB for this purpose (Article No.: 6ES7648-0DC60-0AA0). Alternatively, you can
use a USB stick with any memory size. It must, however, meet the following minimum
requirements:
● File system: FAT16 or FAT32
● Partitioning: only in PC partition format (MBR)
USB sticks that deviate from these requirements have not been tested can may not be
recognized by the NCU.
PROFIBUS DP / MPI interface
Connector type:
9-pin sub-D socket
Max. data transmission rate:
12 Mbit/s
Max. cable length:
100 m
Table 4-4
Assignment of the PROFIBUS DP / MPI interface
Connector
Pin
Name
Type
Remark
1,2
N.C.
-
Not connected
3
LTG_B
B
Signal line B of MPI module
4
RTS_AS
I
Control signal for receive data current. Signal 1
active if directly connected control is sending.
5
M5EXT
V
Return line (GND) of 5 V supply. Current load
from a load of 90 mA max. connected between
P5EXT and M5EXT.
6
P5EXT
V
5 V supply (current load see M5EXT)
7
N.C.
-
Not connected
8
LTG_A
B
Signal line A of MPI module
9
RTS_PG
O
RTS signal of MPI module; signal is "1", when
PG is sending
Shield
-
On connector housing
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
29
Connecting
4.1 Pin assignment of the interfaces
PROFIBUS DP interface
Connector type:
9-pin sub-D socket
Max. data transmission rate:
12 Mbit/s
Max. cable length:
100 m
Table 4-5
Assignment of the PROFIBUS DP interface
Connector
Pin
Name
Type
Remark
1,2
N.C.
-
Not connected
3
RS_DP
B
RS-485 differential signal
4
RTS_DP
O
Request To Send
5
M5EXT
V
5 V external ground
6
P5EXT
V
5 V external potential
7
N.C.
-
Not connected
8
XRS_DP
B
RS-485 differential signal
9
N.C.
-
Not connected
Ethernet RJ45 interface
Connector type:
Standard RJ45 socket
Max. data transmission rate:
10/100/1000 Mbit/s
Max. cable length:
100 m
Table 4-6
Assignment of the Ethernet RJ45 interface 10/100 Mbit/s
Connector
Pin
Name
Type
Remark
1
TxD+
O
Transmit data
2
TxD-
3
RxD+
I
Receive data
4/5
GND
-
(terminated internally with 75 Ω; not re-
quired for data transmission)
/('
/('
6
RD-
I
Receive data
7/8
GND
-
(terminated internally with 75 Ω; not re-
quired for data transmission)
Shield
-
-
On connector housing
-
Green LED
-
Lights up: 10 or 100 Mbit/s
(right)
Off: No or faulty connection
-
Orange LED
-
Illuminated: Data exchange
(left)
Off: No data exchange
General information and networking
30
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.1 Pin assignment of the interfaces
Table 4-7
Assignment of the Ethernet RJ45 interface 1000 Mbit/s
Connector
Pin
Name
Type
Remark
1
DA+
B
Bidirectional pair A+
2
DA-
Bidirectional pair A-
3
DB+
Bidirectional pair B+
4
DC+
Bidirectional pair C+
/('
/('
5
DC-
Bidirectional pair C-
6
DB-
Bidirectional pair B-
7
DD+
Bidirectional pair D+
8
DD-
Bidirectional pair D-
Shield
-
-
On connector housing
-
Green LED
-
Illuminated orange: 1000 Mbit/s
(right)
Off: No or faulty connection
-
Orange LED
-
Illuminated: Data exchange
(left)
Off: No data exchange
Note
Connection only on LAN, not on telecommunication networks!
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
31
Connecting
4.1 Pin assignment of the interfaces
DVI-I interface
Table 4-8
Assignment of DVI-I interface
Connector
Pin
Name
Type
Remark
S
GND
-
Ground
S1
GND
-
Ground
C1
R
Red
C2
G
O
Green
C3
B
Blue
&
&
&
C4
HSYNC
O
Horizontal synchronizing pulse
&
&
C5
GND
-
Ground
CSA
GND
-
Ground
1
TX2N
TDMS data 2-
O
2
TX2P
TDMS data 2+
3
GND
-
Ground
4
N.C.
-
Not connected
5
N.C.
-
Not connected
6
DDC CLK
DDC clock
B
7
DDC CLK
DDC data
8
VSYNC
O
Vertical synchronizing pulse
9
TX1N
TDMS data 1-
O
10
TX1P
TDMS data 1+
11
GND
-
Ground
12
N.C.
-
Not connected
13
N.C.
-
Not connected
14
+ 5 V
VO
+ 5 V
15
GND
VO
Ground
16
MONDET
I
Hot plug detect
17
TX0N
TDMS data 0-
O
18
TXoP
TDMS data 0+
19
GND
-
Ground
20
N.C.
-
Not connected
21
N.C.
-
Not connected
22
GND
-
Ground
23
TXCP
TDMS clock +
O
24
TXCN
TDMS clock -
I/O USB interface
All signals required for connecting operator panel fronts, with the exception of the display
interface, are assigned to this interface.
Associated interface cable:
K1
Connector type:
2 x 13-pin socket connector
General information and networking
32
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.1 Pin assignment of the interfaces
Table 4-9
Allocation of the I/O USB interface
Connector
Pin
Name
Type
Meaning
1
GND
Ground
VO
2
P12C
+power supply for backlight inverter
3
BL_ON
O
Backlight On
4
P5V_fused
VO
+5 V VCC (fused in PCU/TCU)
5
GND
VO
Ground
6
P3V3_fused
VO
+3.3 V VCC (fused in PCU/TCU)
7 - 10
N.C.
-
Not connected
11
P5V_fused
VO
+5 V VCC (fused in PCU/TCU)
12
USB_D1M
USB data- Channel 1
B
13
USB_D1P
USB data+ Channel 1
14
GND
VO
Ground
15
LCD_SEL0
1
16
LCD_SEL1
Display type select signal
2
17
LCD_SEL2
I
3
18
LCD_SEL3
4
19
RESET_N
Reset signal (low active)
20
reserved
-
Reserved
21
HD_LED
O
HD LED, anode with 1 kΩ in series on the
motherboard
22
DP_LED
O
MPI/DP LED, anode with 1 KΩ in series
on the motherboard
23
Ethernet_LED
O
Ethernet LED, anode with 1 kΩ in series
on the motherboard
24
TEMP_ERR
O
LED temperature sensor; anode with 1
kΩ in series on the board
25
RUN_R *)
O
Watchdog error LED, anode with 1 kΩ in
series on the motherboard
26
RUN_G
O
Watchdog OK LED, anode with 1 kΩ in
series on the motherboard
LVDS display interface channel 1
Used to connect operator panel fronts with TFT displays with 640 x 480 pixels (VGA), 800 x
600 pixels (SVGA) or 1024 x 768 pixels (XGA).
Associated interface cable:
K2, max. length: 0.5 m
Connector type:
2 x 10-pin socket connector
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
33
Connecting
4.1 Pin assignment of the interfaces
Table 4-10
Allocation of the LVDS display interface
Connector
Pin
Name
Type
Meaning
1/2
P5V_D_fused
VO
+5 V display supply voltage (fused in PCU/
TCU)
3
RXIN0-
Bit 0 (-)
I
LVDS input signal
4
RXIN0+
Bit 0 (+)
5/6
P3V3_D_fused
VO
+3.3 V display supply voltage (fused in PCU/
TCU)
7
RXIN1-
Bit 1 (-)
I
LVDS input signal
8
RXIN1+
Bit 1 (+)
9/10
GND
-
System ground (reference potential)
11
RXIN2-
Bit 2 (-)
I
LVDS input signal
12
RXIN2+
Bit 2 (+)
13/14
GND
-
System ground (reference potential)
15
RXCLKIN-
(-)
O
LVDS cycle clock signal
16
RXCLKIN+
(+)
17/18
GND
System ground (reference potential)
-
19/20
N.C.
Not connected
LVDS display interface channel 2
Used for expanding the LVDS display interface channel 1 to control TFT displays with 1280 x
1024 pixels (SXGA).
Associated interface cable:
K3
Connector type:
2 x 10-pin socket connector
Table 4-11
Allocation of the LVDS display interface
Connector
Pin
Name
Type
Meaning
1/2
GND
-
System ground (reference potential)
3
RXIN10-
LVDS input signal
Bit 0 (-)
I
4
RXIN10+
Bit 0 (+)
5/6
GND
-
System ground (reference potential)
7
RXIN1-
LVDS input signal
Bit 1 (-)
I
8
RXIN1+
Bit 1 (+)
9/10
GND
-
System ground (reference potential)
11
RXIN2-
LVDS input signal
Bit 2 (-)
I
12
RXIN2+
Bit 2 (+)
13/14
GND
V
Ground
15
RXCLKIN-
LVDS cycle clock sig-
(-)
O
nal
16
RXCLKIN+
(+)
17
GND
V
Ground
18-20
P12VF
VO
+12 V fused
General information and networking
34
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.1 Pin assignment of the interfaces
Rotary switch: Feed override X30
Connector designation:
X30
Connector type:
2 x 5-pin plug connector, according to EN 60603-13 with coding
Max. cable length:
0.6 m
Table 4-12
Assignment of X30 connector (on delivery)
Pin
Name
Type
Meaning
1
N.C.
-
Not connected
2
N.C.
-
Not connected
3
M
V
Ground
4
N.C.
-
Not connected
5
P5
V
5 V supply
6
OV_VS16
Override rotary switch value 16
7
OV_VS8
Override rotary switch value 8
8
OV_VS4
I
Override rotary switch value 4
9
OV_VS2
Override rotary switch value 2
10
OV_VS1
Override rotary switch value 1
Rotary switch: Spindle override X31
Connector designation:
X31
Connector type:
2 x 5-pin plug connector, according to EN 60603-13 with coding
Max. cable length:
0.6 m
Table 4-13
Assignment of X31 connector (on delivery)
Pin
Name
Type
Meaning
1
N.C.
-
Not connected
2
N.C.
-
Not connected
3
M
V
Ground
4
N.C.
-
Not connected
5
P5
V
5 V supply
6
OV_SP16
Override rotary switch value 16
7
OV_SP8
Override rotary switch value 8
8
OV_SP4
I
Override rotary switch value 4
9
OV_SP2
Override rotary switch value 2
10
OV_SP1
Override rotary switch value 1
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
35
Connecting
4.1 Pin assignment of the interfaces
Optional customer buttons IN (X51 / X52 / X55)
Only switches (passive inputs) may be connected via the X51, X52 and X55 connectors. X51
and X52 are typically used for connecting illuminated pushbuttons. The lamps in the buttons
are activated via X53 and X54. X55 has no corresponding outputs.
Note
Connection miniature handheld unit
Alternatively, at the inputs X51, X52 and X55, one miniature handheld unit may be operated.
For details, please refer to the corresponding section.
9
9
; L
.7M ,1
.7M ,1
.7M ,1
0 *1'
0 *1'
L
M
Image 4-1
Main circuit diagram of the input circuit for X51, X52 and X55
Connector designation:
X51 / X52 / X55
Connector type:
4-pin plug connector
Max. cable length:
0.6 m
Table 4-14
Assignment of connector X51
Pin
Name
Type
Meaning
1
KT-IN1
Customer key 1
2
KT-IN2
I
Customer key 2
3
KT-IN3
Customer key 3
4
M
V
Ground
General information and networking
36
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.1 Pin assignment of the interfaces
Table 4-15
Assignment of connector X52
Pin
Name
Type
Meaning
1
KT-IN4
Customer key 4
2
KT-IN5
I
Customer key 5
3
KT-IN6
Customer key 6
4
M
V
Ground
Table 4-16
Assignment of connector X55
Pin
Name
Type
Meaning
1
KT-IN7
Customer key 7
2
KT-IN8
I
Customer key 8
3
KT-IN9
Customer key 9
4
M
V
Ground
Optional customer buttons OUT (X53 / X54)
The short-circuit-proof outputs X53/X54 are provided to control lamps in the keys.
Lamps with 24 V and 2.4 W per output are recommended.
3
;
.7 287
.7 287
.7 287
0 *1'
0
3
;
.7 287
.7 287
.7 287
0 *1'
0
Image 4-2
Main circuit diagram of the input circuit for X53 and X54
NOTICE
Damage to the electronics
Do not connect any relays, valves or other inductive loads.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
37
Connecting
4.1 Pin assignment of the interfaces
Connector designation:
X53 / X54
Connector type:
4-pin plug connector
Max. cable length:
0.6 m
Table 4-17
Assignment of connector X53
Pin
Name
Type
Meaning
1
KT-OUT1
Output 1 lamp
2
KT-OUT2
O
Output 2 lamp
3
KT-OUT3
Output 3 lamp
4
M
V
Ground
Table 4-18
Assignment of connector X54
Pin
Name
Type
Meaning
1
KT-OUT4
Output 4 lamp
2
KT-OUT5
O
Output 5 lamp
3
KT-OUT6
Output 6 lamp
4
M
V
Ground
Interfaces for two handwheels X60 / X 61
Interface:
Handwheel 1
Handwheel 2
Connector designation:
X60
X61
Connector type:
15-pin Sub-D socket
Max. cable length:
25 m
Table 4-19
Assignment of connectors X60/X61
Pin
Name
Type
Meaning
1
P5HW
V
5 V power supply
2
M
V
Ground
3
HW1_A / HW2_A
I
Handwheel pulses track A
4
HW1_XA / HW2_XA
I
Handwheel pulses track A (negated)
5
N.C.
-
Not connected
6
HW1_B / HW2_B
I
Handwheel pulses track B
7
HW1_XB / HW2_XB
I
Handwheel pulses track B (negated)
8
N.C.
-
Not connected
9
P5HW
V
5 V power supply
10
N.C.
-
Not connected
11
M
V
Ground
General information and networking
38
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.1 Pin assignment of the interfaces
Pin
Name
Type
Meaning
12
N.C.
-
Not connected
13
N.C.
-
Not connected
14
N.C.
-
Not connected
15
N.C.
-
Not connected
Note
The handwheels can either be operated with TTL or differential signals.
You set the signal type using S1 (wire bridge) on the COM board.
The handwheels are supplied with 5 V ± 5% and 100 mA via the interface.
Contour and velocity specification via handwheel are not supported.
Interfaces for direct keys
X11 on the operator panel (OP) fronts can be used to fetch the state of the direct keys. The
connection of a 20-pin ribbon cable allows the direct keys to evaluate the following components:
● Direct key module (DTM)
● X70 in the machine control panels (MCP, MPP) and the handwheel connection module
(HAM)
● X205 on the Thin Client Unit (TCU)
The signals are then forwarded to the control over the various communications networks. Note
that DTM and HAM can be operated only with PROFIBUS DP.
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
'7
Image 4-3
Assignment of the direct keys to the vertical softkeys of an operator panel front
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
39
Connecting
4.1 Pin assignment of the interfaces
16 digital inputs (5 V) can be fetched via the X11 connector.
Connector designation:
X11
Connector type:
20-pin plug connector
Max. cable length:
0.85 m
Table 4-20
Assignment of connector X11
Pin
Name
Type
Meaning
1
DT1
Direct key 1
O
16
DT16
Direct key 16
17
P5V
+ 5 V (fused)
18
P5V
+ 5 V (fused)
V
19
GND
Ground
20
GND
Ground
16 digital inputs can be polled by the X70/X205/DTM connector.
Connector designation:
X70/X205/DTM
Connector type:
20-pin plug connector
Max. cable length:
0.85 m
Table 4-21
Assignment of connector X70 (MCP, MPP, HAM) / X205 (TCU) / DTM
Pin
Name
Type
Meaning
1
DT1
Direct key 1
I 1)
16
DT16
Direct key 16
17
P5V / CON1 2)
+ 5 V input voltage 3)
18
P5V / CON2 2)
+ 5 V input voltage 3)
V
19
GND
Ground
20
GND
Ground
1)
The inputs are electrically isolated for MCP / MPP / HAM and DTM.
2)
For the TCU, it is evaluated whether the direct keys have been connected.
3)
Power consumption: 100 mA for MCP / MPP / HAM; 500 mA for DTM
Table 4-22
Signal level
HIGH level:
5 V or open
Low level
<= 0.8 V
General information and networking
40
Manual, 03/2016, 6FC5397-1AP40-5BA3
Connecting
4.2 Handling membrane connectors
4.2
Handling membrane connectors
When replacing parts it can sometimes be necessary to disconnect membrane connectors
from the boards and reconnect them again.
This should be done as follows:
(1)
Clamping frame of socket
Image 4-4
Removing (left) and attaching (right) a membrane connector
Unplugging the membrane connector
1. Loosen the dark clamping frame of the socket by pushing it up with your fingernails until it
engages in its upper, unlocked position (Fig. left).
2. Carefully pull off the membrane connector upward.
Plugging in the membrane connector
1. With the clamping frame in the upper position, carefully plug the membrane connector into
the socket.
2. Lock it in place by pushing down the clamping frame (Figure right).
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
41
Connecting
4.2 Handling membrane connectors
General information and networking
42
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5
5.1
System settings
5.1.1
Settings for SINUMERIK solution line
Range of validity
This description is valid for:
● NCU 7x0.3 PN with NCU-Basesoftware (Linux-based)
● PCU 50.5 with PCU-Basesoftware (Windows XP, Windows 7)
Introduction
This manual describes the structure and commissioning of the system network with
SINUMERIK solution line control and operator components with Ethernet-based
communication. The fundamentals of the system network are described first, details and
special cases are described in subsequent chapters.
Fundamentals
The system network for SINUMERIK solution line is structured as a star topology with a central
Ethernet switch, to which all Ethernet-based components of the system are connected.
For an NCU the connection is executed via the X120 Ethernet socket, for PCU it is executed
via the "Ethernet 2" connection. There is no default for all other components with two Ethernet
connections. These components have an internal 2-port switch and may be used to connect
an additional operator component. Thus in this case there can be deviation from the strict star
topology.
System network
In the system network the IP address 192.168.214.xxx with subnet mask 255.255.255.0 is pre-
selected. Here there is precisely one DHCP server with DNS that can run on one NCU or one
PCU. The server ensures assignment of IP addresses to the Ethernet components in the
system network (DHCP clients) from a specified address band.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
43
Networking
5.1 System settings
The following rules apply for assignment of IP addresses in the system network:
● For all NCUs and PCUs the commissioning engineer assigns fixed IP addresses in the
associated address bands, as well as appropriate computer names (host names). All other
(operator) components are automatically assigned an IP address from the DHCP server.
Its name is generated automatically (for MCP, MPP, HT 8), or is entered at commissioning
(TCU).
● If there are multiple NCU and/or PCU in the system network the system automatically
(depending on the start-up sequence) specifies the DHCP server and automatically ensures
synchronization of all necessary data so that the next time the system boots any other NCU
or PCU could take on the role of DHCP server. However it is a good idea to specify a DHCP
master. This is an NCU or PCU in the system network that is available at each system boot
and which regularly takes over the task of the DHCP server and DNS server.
Synchronization of data takes place in any event so that any other NCU or PCU can take
over this task. All non-master NCU / PCU wait in the system boot an adjustable length of
time for availability of the master.
Note
In a system network, on a boot server respectively - i.e. the NCU or PCU which
accommodates the active DHCP server - a maximum of 30 operator stations may be
operated simultaneously with a TCU.
A maximum of 10 operator stations with a TCU may connect up simultaneously with the
same HMI application when powering up.
Connection to a company network
Each NCU can be connected via X130, and each PCU can be connected via "Ethernet 1" to
the company network. The company network is used to exchange operating software with
servers or to execute part-programs directly from servers in the company network. Company
network and system network should always be logically and also physically separated.
Service interface X127
The service interface X127 of the NCU is used for direct connection of a PG/PC for service
purposes. Here access with STEP 7 to the PLC, and with NCU 7x0.3 PN also to PROFINET
is possible.
With direct connection (peer-to-peer) of a PG/PC to X127 it is absolutely necessary that the
PG is operated as a DHCP client.
General information and networking
44
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.1 System settings
5.1.2
System boot with system network
System behavior at boot
As of NCU system software V2.4 SP1 and PCU-Basesoftware V8.1, system boot behavior is
based on the following principle:
● For configuration of an NCU 7x0 with a PU 50, the default for a network configuration is as
follows: The NCU keeps the default IP address 192.168.214.1 on X120, the PCU 50 keeps
the default IP address 192.168.214.241 on Eth2.
● For a configuration of more than 1 NCU 7x0 without PCU, with one or several PCU 50, then
a differentiation must be made between two cases:
- At boot automatically all address conflicts and DHCP conflicts are resolved and the
system is ready for operation. In this configuration there is no guarantee that all NCUs
and PCUs will always receive the same IP address at each system boot.
- If in the user's view there is a requirement that all NCUs, and possibly also the PCUs,
get a defined constant IP address at each boot, for example because the IP address is
entered in the respective PLC program, then the user must configure a fixed IP address
for each NCU 7x0/PCU 50 in question, in the basesys.ini file.
● The user can specify a DHCP master in the basesys.ini file.
● Assigning names:
- The user should assign meaningful names for all NCUs in the basesys.ini file; if not the
names will be generated automatically.
- A PCU 50 always has a computer name that can be changed as needed.
● The IP addresses of TCUs and MCPs are freely assigned within the specified address band
at each boot. The MCPs are identified in the PLC via their DIP switch setting.
Using DNS name service
Availability of the DNS (Domain Name System) name service offers the following advantages
for system network administration:
● The name service enables easier configuration with names instead of IP addresses for
management of operating units: All components in the system network can be addressed
via a symbolic computer name. This name can to some extent be freely assigned, to some
extent it is derived automatically from a DIP switch setting (MCP, MPP, EKS, HT 8, HT 2).
● A computer node in the system network (NCU, PCU, TCU, MCP, HT 8, etc.) can be
addressed solely through assignment of the IP address, either via a freely selectable name
or via an internally generated name in the system network, and thus becomes independent
from its network address in the system network. Thus a change in the network address
does not necessarily necessitate a series of additional setting changes.
● In addition, the name service is used by the system for address resolution for MCP/MPP,
direct keys, and EKS when changing the user authorization.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
45
Networking
5.1 System settings
5.1.3
Thin Client Unit (TCU)
TCU overview
The Thin Client Unit (TCU) for the distributed configuration permits spatial separation of the
SINUMERIK operator panel front (OP/TP) and the SINUMERIK PCU or NCU. On the
SINUMERIK solution line, the TCU is used to display the user interface of the PCU 50 or the
NCU.
It is possible to connect one TCU to several PCUs/NCUs. All TCUs and PCUs/NCUs that are
connected to one another via a switch form the "system network". The user interface of a PCU/
NCU is copied to several OPs with one TCU each. In other words, all of the TCUs display the
same screen. Operator actions can only be performed on one TCU at a time. This TCU then
has user authorization. The PCU can also have its own OP connected directly to it.
The following diagram shows a configuration example for a distributed topology:
7&8
7&8
7&8
+7
6,180(5,.
' VO
3&8
0&3
6ZLWFK
The mobile SINUMERIK HT 8 handheld terminal works on the thin client principle and
combines the functions of an operator panel with a machine control panel.
The configuration and cabling of the whole plant system based on a permissible configuration
is described in the chapter 'Network configurations".
Supplementary conditions
For operation of a TCU:
● In the system network, the number of active TCUs is limited:
- a maximum of 2 TCUs: NCU 710.3 PN
- a maximum of 4 TCUs: NCU 720.3 PN or NCU 730.3 PN
- a maximum of 4 TCUs: PCU
Any number of TCUs can be operated in the system network.
● CompactFlash Cards cannot be used on the TCU.
● A 16 bit or 32 bit depth of color setting may be selected.
● If a PC keyboard is connected to the TCU, it is not possible to ensure that all special keys,
e.g., multi-media keys, will be transferred to the software of the NCU / PCU.
General information and networking
46
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.1 System settings
● Machine control panels connected via a PROFIBUS network are not supported for
switchover.
● Distributed memory media that are connected to the TCU via USB can be used.
5.1.4
Factory default settings
Meaning of the symbols:
○
Eth 1 as a DHCP client
●
Eth 2 as a DHCP server
■
Eth 2 with a fixed IP address
Preconfiguration of the TCU
The TCU is configured as a DHCP client and primarily accepts IP addresses from SINUMERIK
components, from the DHCP server of such components that are inherent to SINUMERIK, for
example, an NCU at X120 or a PCU on the system network or from a default DHCP server.
The behavior of the TCU cannot be modified here.
A TCU is a SINUMERIK DHCP client.
The TCU has a single Ethernet connection.
7&8
A TCU executes a boot via the network. The boot server is the computer node from which the
TCU also obtains its IP address.
Pre-configuration of the PCU
A PCU has two Ethernet interfaces with default settings suitable for use with SINUMERIK
solution line:
Eth 1 is pre-selected as a default DHCP client for connection to a
company network.
3&8
Eth 2 is pre-selected as a SINUMERIK DHCP server for connection
to a system network. On Eth 2 the fixed IP address
(WK
(WK
192.168.214.241 is pre-selected.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
47
Networking
5.1 System settings
Preconfiguration of the NCU
On the X120, the NCU is preconfigured for the SINUMERIK DHCP protocol. The NCU is pre-
selected here as a SINUMERIK DHCP server. On X120, the NCU occupies the fixed IP address
192.168.214.1 with the subnet mask 255.255.255.0 in its capacity as a DHCP server. The
DHCP server of the NCU assigns IP addresses from the range 192.168.214.10 -
192.168.214.239 to the DHCP clients. The behavior of the NCU on X120 cannot be
modified.
Restricting the available address band that is managed by the DHCP server of the NCU frees
up IP addresses 192.168.214.2 to 192.168.214.9 as well as addresses 192.168.214.241 to
192.168.214.254 for network nodes with fixed IP addresses.
The NCU has three Ethernet connections:
;
;
- X120 to connect to the system network with an active DHCP serv-
er (Eth 0)
1&8
- X130 to connect to the company network as a default DHCP client
;
(Eth 1)
- X127 as a service connection with an active DHCP server (Ibn 0)
On X130, the NCU is set as a default DHCP client for the address reference from a company
network. The IP address received here is specified by the DHCP server from the company
network.
On X127, an NCU is a standard DHCP server (in contrast to the SINUMERIK DHCP server).
On X127, the NCU has the fixed IP address 192.168.215.1 with the subnet mask
255.255.255.224). The IP addresses 192.168.215.2 - 192.168.215.23 are dynamically
assigned to the DHCP clients. The range 192.168.215.24 - 192.168.215.30 is reserved, and
can be used by stations on the network with a fixed IP address, e.g. by a modem.
Reserved IP addresses for NCU and PCU
The following defaults apply on delivery:
● Connection to the system network with subnet mask 255.255.255.0:
IP address
Network station
Remark
192.168.214.1
NCU on X120
Default
192.168.214.2 - 9
For additional NCUs with a fixed IP address on
Unassigned
the system network
192.168.214.10 - 239
For additional TCUs, subsequently for additional
DHCP clients
PCUs, NCUs, MCPs, MPPs
192.168.214.240
Reserved for EKS (Electronic Key System)
Default
192.168.214.241
Fixed IP address of the PCU on Eth 2
Default
192.168.214.242 - 249
For additional PCUs with a fixed IP address
Unassigned
192.168.214.250 - 254
For PGs with a fixed IP address (service con-
Unassigned
nection)
● Service connection with subnet mask 255.255.255.224:
General information and networking
48
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
IP address
Network station
Remark
192.168.215.1
NCU on X127
Default
192.168.215.2 - 23
for service purposes with PG, PC
DHCP clients
192.168.215.24 - 30
fixed IP address, for example for a modem
Unassigned
5.2
Commissioning TCU
5.2.1
Using the TCU's main menu
Key assignment
Functions of the keys and softkeys in the "Operator panel service system":
Softkey
Key on OP
External key-
Description
board
HSK1
<F1>
Moves the cursor down a row
HSK2
<F2>
Moves the cursor up a row
Page
HSK3
<F3>
Moves the cursor down a page
Page
HSK4
<F4>
Moves the cursor up a page
Char
HSK5
<F5>
Inserts text or digits
Char
HSK6
<F6>
Inserts text or digits
VSK7
←
Cancel / Return
Cancel
VSK8
→
OK / Confirm
Ok
---
Pos1
Moves the cursor to the top row
---
End
Moves the cursor to the bottom row
Exceptions to the above are mainly the result of input fields. Where these are present, the left/
right cursor keys move the input cursor rather than performing an OK/cancel function. The
Return key takes you to the next field (like the "down" key) rather than closing the entire dialog
with OK. There are also Backspace (deletes character to the left) and Delete (deletes character
to the right) keys for editing text and numbers. The F5, F6, Backspace, Delete, and Select
keys (between the cursor keys on the panel) can be used to switch between Yes/No fields.
Touch panels without any additional keys still have a special function which allows you to edit
letters and numbers with HSK5/HSK6 by moving characters forwards or backwards. With a
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
49
Networking
5.2 Commissioning TCU
touch screen, you can activate all the softkeys and even select rows in a menu simply by
touching them.
See also: How to calibrate a touch panel (Page 65)
"Main menu"
The dialog "Main menu (TCU1)" is started with the menu back key and the key <MENU SE-
LECT>:
Image 5-1
TCU menu: Main menu
The main menu contains:
● A "Main menu" title followed by the TCU name in brackets
● A central area listing the servers from config.ini. This is followed by two more fixed items,
"Select service session" and "Service this panel".
- The penultimate menu item, "Select service session", triggers a server scan which
detects all the VNC servers in the local (system) network. These are then displayed in
a session menu which largely reflects the main menu.
- The last menu item on the main menu, "Service this panel", opens the "Service menu
for operator panel" submenu.
General information and networking
50
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
● The right-hand side of the menu has a column containing 8 softkeys for use on a context-
specific basis.
● The lower section of the menu has a row of 4 softkeys for navigating with the cursor.
● There is an error line for displaying error messages directly above the row of softkeys.
Transient status messages also occasionally appear in this line.
● There is a further message line above this error line. The contents of this line can be set
from the servers using HWS commands.
"Details" softkey
The following connection data for the selected device appears when the "Details" softkey is
pressed:
Image 5-2
TCU menu: Connection data
5.2.2
Using additional TCU menus
"Service sessions" dialog
When "Select service session" is selected from the main menu, the resulting process begins
by triggering a server scan:
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
51
Networking
5.2 Commissioning TCU
Image 5-3
TCU menu: Scanning
After this, the following dialog appears:
General information and networking
52
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
Image 5-4
TCU menu: Active sessions
Central area with the server list:
The individual server lines contain either "Show WHAT on NAME (IP)" or the IP address only
where the name is unknown.
Session number
VNC server
Session 0
HMI
Session 4
Command shell
Session 5
System logfile
Session 6
System Network Center (SNC)
Session <N>
other server
These details are followed by a status message regarding the accessibility of the VNC server.
"Connection not ok" appears if it is already impossible to access the VNC server from the IP
side (if switched off, for example). If it can be accessed, a message shows whether an HMI-
VNC server is also accessible ("HMI running/not running").
The VSK8, Return or right cursor keys can be used to launch a VNC viewer for the selected
server.
Connection status:
Further details on the connection status can be called with the "Details" softkey. In the next
dialog, "not ok" or "not running" are accompanied by an additional error message with more
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
53
Networking
5.2 Commissioning TCU
precise details on the reason for the loss of function. With more favorable scenarios, the
session name for the VNC server will also be specified along with its resolution.
The connection and HMI status are monitored on a regular basis in the backg1round. This may
mean that these details change spontaneously if a change is made on the relevant server (for
example, it may be switched off, the HMI may become available, etc.).
"Service menu for operator panel (TCU)" dialog
The following dialog appears when "Service this panel" is selected from the main menu:
Image 5-5
TCU menu: Service menu
General information and networking
54
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
The following menu items are available here:
● "Show status" displays status information including the software version, HW information,
TCU network data, and the contents of the config.ini.
Image 5-6
TCU menu: OP status
● "Show local logfile" displays a filtered version of the system logfile in the /var/log/
messages directory containing local TCU messages only.
Syslog messages received via the network are not displayed.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
55
Networking
5.2 Commissioning TCU
Image 5-7
TCU menu: Local logfile
● "Show logfile of remote devices" displays the logfile of the other devices in the network:
The syslog messages of devices in the system network which send syslog messages by
broadcast, such as NCU 7x0, ...
● "Modify operator panel settings" calls a further submenu. Please refer to the next section.
● "Calibrate touch screen" is only active if there is a touch screen. This menu item recalibrates
the touch screen.
● "Reboot" restarts the TCU.
Note
Where the contents of a line exceed the space available, the remaining text runs onto the
next line so that you do not have to waste time scrolling across. When this occurs, the line
has a right-facing arrow at its right edge.
General information and networking
56
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
"Modify settings for operator panel (TCU)" dialog
The following dialog appears when "Modify settings" is selected from the main menu:
Image 5-8
TCU menu: Settings
The central area is for setting the TCU parameters:
● "HT 8 individual mode" (yes/no)
This is only visible with HT 8, and is used to switch between Auto Mode and Individual
Mode.
There is no need to make any settings if an HT 8 is in Auto Mode, as the name is determined
automatically: ("DIP<n>") the MCP address and TCU index are determined by the DIP
setting ("DIP<n>").
It is possible, however, that another device is registered for the name selected. Such
situations may only prove to be temporary, as is the case when DIP settings or two HT 8
have been confused. For this reason, this status is not reported as an error immediately,
but identified as a possible problem instead ("potential name/DIP setting collision"). The
text will only read ("Name/DIP settings collision") if the situation remains unchanged after
some time has elapsed.
The process itself is unaffected, as the changes only relate to how the warning or error is
displayed. The explanatory text informs the user that they have probably assigned the same
DIP number twice and suggests they change one of them before rebooting the HT 8.
● "Operator panel index - TCU" (0-255)"
This specifies the TCU index. It matches the [Station] tcuIndex setting from the config.ini
file.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
57
Networking
5.2 Commissioning TCU
● "Machine control panel address - MCP" (0-255)
This specifies the address of the associated MCP. It matches the [Station] mcpIndex setting
from config.ini.
● "Electronic key system index - EKS" (0-255)"
This specifies the index of the associated EKS. It matches the [Station] eksIndex setting
from config.ini.
● "Enable direct keys" (yes/no)
This specifies whether direct keys (if present) should communicate with the PLC (yes) or
be treated as ordinary keys (no).
"OK" saves any modified values to the config.ini file or to the Flashstore (HT 8 individual mode).
Parameters for the "config.ini" file
Two steps need to be performed:
1. Select "New" or "Replacement for existing panel".
2. Select what is to be replaced.
When an unknown TCU (i.e. not yet registered with the boot server) is started, a selection
menu containing both the "New" and "Replacement for existing panel" items will appear. The
accessibility of all the registered TCUs is tested in the backg1round.
The status of this test process appears in the message line: "(0/3 panels inactive)".
Image 5-9
TCU menu: New TCU
General information and networking
58
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
If all the TCUs are active, the new one cannot be a replacement. The system will then
automatically switch to the name assignment phase after a set period of time has elapsed.
Image 5-10 TCU menu: Name of TCU
Replacing a device
If "Replacement" is selected, all the registered TCUs will appear in a selection menu. Those
which are active in the network will be grayed out. (As these are functioning, there should be
no question of replacing them.) The cursor automatically defaults to the first row for selection.
As the accessibility test is still running in the backg1round, the active status of the rows may
change if panels are switched on or off.
If a name is ultimately chosen, it will be applied to the new TCU along with the associated
saved settings.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
59
Networking
5.2 Commissioning TCU
Image 5-11 TCU menu: Spare TCU
General information and networking
60
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
Assigning a name
If, as described above, the system automatically follows the "New" path, an additional message
will appear: "This operator panel (TCU) must be new, because there are no inactive panels."
This message will not appear if "New" is selected manually.
Image 5-12 TCU menu: Name of TCU
An available TCU name is suggested in the input field, although the user is able to change
this. The default name is "TCU<N>", where <N> is the lowest number yet to be used. If,
however, the name is already allocated after the OK softkey has been pressed (which may
happen if a number of TCUs log on at the same time) and the suggestion has not changed, a
new and unused name will be specified.
If the name selected was still available, this will now be allocated, and the TCU settings can
still be adapted if required. To enable any changes to be made, a new dialog will appear in
which all the parameters have been pre-assigned their default values. You can make any
changes you like or just select "OK" to accept the existing values.
5.2.3
How to register a TCU on the system network
Preconditions
The boot server (NCU or PCU 50) defined in the system network as a DHCP master, must be
switched on and be available in the network.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
61
Networking
5.2 Commissioning TCU
Sequence for a TCU
Procedure:
1. Connect TCU.
This opens the dialog "New operator panel (TCU)".
2. Select "New" to connect a new TCU and "OK" to confirm.
3. In the next dialog, accept the name suggested by the system or enter a name and confirm
this with "OK".
The following parameters are pre-selected for the TCU:
Operator panel index - TCU [0-255]
1_
Machine control panel address - MCP [0-255]
192
Electronic key system index - EKS [0-255]
0
Enable direct keys
No
4. Restart the TCU to apply the new settings.
5. If you want to change the parameters, select "Main menu" → "Service this panel" → "Modify
operator panel settings".
General information and networking
62
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
Sequence for the HT 8
Procedure:
1. Connect HT 8 to a connection module and calibrate the touch screen.
Additional softkeys are available for convenient touch panel operation:
- "OK" has the same effect as the <INPUT> key
- Select "DEF" to save the "Default" settings.
- "Edit" has the same effect as the <F10> or <MENU SELECT> key.
2. Select HT 8 Individual Mode:
According to the default setting for an HT 8, "HT 8 Individual Mode" is deselected with "No".
This means "Auto" mode is activated for automatic detection in the system network. The
HT 8 is automatically detected based on its name "DIP_". If "HT 8 Individual Mode" is
activated with "Yes", the HT 8 is identified by its MAC address on the system network.
3. For an HT 8, confirm the "DIP..." name proposed by the system or adapt the name. You
can select any other characters.
Press the <INPUT> key to apply the following values as default settings for the HT 8:
HT8 Individual Mode
No
Operator panel index - TCU [0-255]
10
Machine control panel address - MCP [0-255]
10
Electronic key system index - EKS [0-255]
0
Enable direct keys
No
The following message will then appear: "New TCU 'DIP10' registered."
Note
The TCU index is used to evaluate the direct keys. Direct keys can only be activated by
appropriate devices. For an HT 8 the TCU index cannot be set, but is assigned by the
system.
Activate direct keys
The signals from pressing the direct keys are sent directly to the PLC. In the PLC, the keys
appear as 16 digital inputs.
Additional information on programming the PLC is provided in:
References: Function manual basic functions, basic PLC program (P3 sl)
Definition: Operator panel
The term operator panel designates a unit that consists of an OP/TP, a TCU or PCU and a
machine control panel (MCP), that are connected to each other via Ethernet.
All TCUs and PCU 50 can be used along with OP/TP with "integrated TCU", e.g.: OP 08T,
OP 015T, TP 015AT.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
63
Networking
5.2 Commissioning TCU
Specifying settings without machine control panel
If a PCU or a TCU has no Machine Control Panel (MCP), you must set one of the two following
options:
● MCP address = 0 or no entry
After the change of user authorization, there is no switchover of the machine control panel;
the previously active MCP remains active.
● MCP address = 255
If the user authorization is transferred to this PCU or TCU, the previous machine control
panel is deactivated and there is no active machine control panel from this point on.
Connecting a replacement TCU
Procedure:
1. Connect the new TCU.
The following dialog lists the TCUs on the system network along with their "active" or
"inactive" status.
Image 5-13 TCU menu: New operator panel (TCU)
2. Select the name previously assigned to the faulty TCU from the "New operator panel (TCU)"
dialog. As a result, the new TCU is recognized on the network and acquires all of the
configuration settings from the TCU that has been replaced.
General information and networking
64
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
See also
How to calibrate a touch panel (Page 65)
5.2.4
How to calibrate a touch panel
NOTICE
Service life of the touch screen
Do not touch the operating elements of the display with pointed or hard objects. This may
considerably reduce their service lives.
With each HT 8-device, a Touchpen (order no. 6FC5348-0AA08-4AA0) is delivered. This
should be used for calibration purposes and during operation.
Calibrate touch screen
The calibration is automatically started after switching on HT 8.
1. Follow the instructions on the screen:
2. Press the three calibration items one after the other.
This completes the calibration.
3. Press the corresponding horizontal softkey on the touch screen to close the command shell
and to re-establish the connection to the desired PCU.
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
65
Networking
5.2 Commissioning TCU
Recalibrate touch screen
Procedure:
1. The key combination below can be used to initiate further TCU calibration during operation,
if required: <F9> + <F10>.
This corresponds to the key combination on an OP: Menu back key + <MENU SELECT>.
2. Select the menu item "Calibrate touch screen" to start calibration.
Operator panel service system - service menu for operator panel (TCU)
Show status
Show local logfile
Show logfile of remote devices
Modify operator panel settings
Calibrate touch screen
Reboot
TOUCHSCREEN CALIBRATION
(Screen Orientation)
Please touch upper left corner
Cancel
Ok
Page
Page
Image 5-14 HT8 calibrating points
Note
The "Touchware" program, which is available with Windows XP, is deactivated on the TCU.
The calibration process on the HT 8 can alternatively be started with the following key
combination: <Recall> + <MENU SELECT> and then the <U> key.
General information and networking
66
Manual, 03/2016, 6FC5397-1AP40-5BA3
Networking
5.2 Commissioning TCU
5.2.5
Connecting-up the SIMATIC Thin Client Touch Panel
Registration in the system network
The SIMATIC Thin Client Touch Panel behaves just like a TCU when connecting-up. When
registering in "Operator Panel Service System" enter a name in the system network. After this,
the device is available in the "Service Network Center" with the hardware ID "SIMATIC TC":
Image 5-15 SIMATIC Thin Client
Note
The SIMATIC Thin Client Touch Panel has a USB connection at the rear, which behaves just
like the USB connection X204 of a TCU.
An external keyboard is recommended for commissioning and to operate the "Operator Panel
Service System".
General information and networking
Manual, 03/2016, 6FC5397-1AP40-5BA3
67
Networking
5.2 Commissioning TCU
Operating the Touch Panel
To operate the Touch Panel, use the integrated keyboard:
Image 5-16 Virtual Keyboard
The integrated keyboard is activated using the button to the far right on the start bar.
See also
How to register a TCU on the system network (Page 61)
Using the TCU's main menu (Page 49)
Reference
SIMATIC HMI, Operating instructions: Thin Client, Thin Client PRO
5.2.6
This is how you configure the SIMATIC Thin Client Touch Panel
Operating the start bar
The following functions are available in the start bar of the SIMATIC Thin Client:
To select the SINUMERIK mode, press the button:
General information and networking
68
Manual, 03/2016, 6FC5397-1AP40-5BA3
////////////////////////////////////////// |
||
|
|
|