No. 267 Air conditioning has abnormal sound
Malfunction
t
Cause Solution
(1)The driving belt has not been tensioned. It will be prolonged in the process of usage and
thus cause the abnormal sound; the belt shall be re-tensioned in case of this situation
occurs;
(2).The pulley and the tensioner bearing break down with rumbling sound during the
operation; a harsh feeling is showed when rotating the pulley by hand: replace the bearing,
check the tensioner and the pulley, replace them in case they are out of service.
(3)The abnormal sound may be caused by the looseness of the mounting bolt between the
engine and the compressor bracket as well as untightening of the bolt when mounting the
compressor bracket; the bolt shall be checked and retightened to ensure its reliable
connection;
(4).The compressor is oil shortage that causes the piston seizure, the piston scraping and
also the abnormal sound: the refrigeration oil shall be added;
(5).Too much or too little refrigerant, which causes the malfunction or the liquid impact of the
compressor; the refrigerant must be refilled;
(6).Failure of compressor electromagnetic clutch; replace the electromagnetic clutch or the
compressor assembly;
(7).Undersupply of the sedan generator battery that causes the insufficiency in the
compressor electromagnetic clutch coil suction resultant; the electromagnetic clutch is in
nearly sucking condition, which may cause the abnormal sound; the generator battery shall
be checked or replaced;
The compressor
has abnormal
sound
(8).The pulley is un-tightened: tightening the fastening screw;
(1).The abnormal sound is generated owing to the mismatch of the thermo expansion valve
structure with the system; it normally occurred when opening or closing the air conditioning;
here opening of the thermo expansion valve can be lowered (clockwise fasten the set screw
by half turn to 3/4 turn; over low fastening has no effect and over high fastening will influence
the performance); replace the thermo expansion valve if the above method is invalid;
(2)Performance of the thermo expansion valve does not mate with the system. The thermo
expansion valve will have an abnormal sound under certain operation mode if the capacity of
the thermo expansion valve is too large; replace into a thermo expansion valve of suitable
capacity.
(3).Resonance of the thermo expansion valve will be caused if the thermo expansion valve
structure does not mate with the system; the thermo expansion valve shall be replaced under
this condition;
The thermo
expansion valve
has abnormal
sound
(4). It is caused by the quality problem of the thermo expansion valve such as ultra low of the
spring force; the thermo expansion valve shall be replaced;
(1) abnormal sound of the blower, imbalance of the blower fan blade, abnormal sound
caused by excessive wear of the blower motor: replace the blower;
(2) Looseness of the clamp or the knock during the operation: tighten the clamping stirrup,
eliminate the friction or the vibration between the hoses and other parts;
(3) There has chatter in the pressure line caused by overfilling of the refrigerant; surplus
refrigerant shall be discharged;
The
compressor
has abnormal
sound during
the operation
The air
conditioning has
other abnormal
sound
(4) There has hissing sound at inlet of the thermo expansion valve caused by inadequate
filling of the refrigerant; the refrigerant shall be supplied;