Ford Ranger EV. Electric Manual - part 51

 

  Index      Ford     Ford Ranger EV - Electric manual 1998 year

 

Search            

 

 

 

 

 

 

 

 

 

Content   ..  49  50  51  52   ..

 

 

Ford Ranger EV. Electric Manual - part 51

 

 

LESSON 5: DIAGNOSIS

5-45

Battery Diagnostic System (BDS) Battery Module and
Sense Lead Diagnostics

Diagnosing a battery module or sense lead fault can be of critical

importance when a vehicle is brought in for service.

It is important to note that a single bad module or single sense lead

will not usually illuminate any of the warning lights in the

instrument cluster.

However, if signals from five or more modules are lost, an

emergency power off (EPO) condition will occur, which will result

in a power limit light illumination, no charging, and a vehicle

shutdown.

Because all the batteries in the battery pack are wired in series, a bad

module may cause a significant loss of range. Because of this series

arrangement, one weak module limits the energy output of the whole

pack.

However, sometimes the symptoms may not be very apparent.

Symptoms of module failure can vary depending on the severity of the

failure.

For example, if a module’s capacity is only slightly lower than the

other modules in the pack, the vehicle’s range may only be

decreased slightly.

If the customer never runs the battery pack below 40 or 50% state

of charge (SOC), they may not notice any decrease in vehicle

range.

However, DTC C1671 (BATTERY VOLTAGE OUT OF RANGE)

will be stored in the BCM’s memory.

If an individual module’s capacity is significantly lower than the other

modules of the battery pack, its failure can cause a significant

decrease in vehicle range that will be readily apparent to most

customers.

It should be noted that weak battery modules tend to occur one at

a time.

A single battery sense lead failure will usually have no symptoms

at all. As with a bad module, no warning light in the instrument

cluster will illuminate, and the only way you may become aware of

the failure is that a DTC 1671 will be stored in the BCM’s memory.

The rule for a sense lead failure is that a bad sense lead will cause a

fault to be indicated in two modules.

LESSON 5: DIAGNOSIS

5-46

This is due to the fact that each sense lead monitors the voltage of

two battery modules.

For example, the sense lead that monitors the voltage for module

15 also monitors module 16’s voltage.

So a failure of the sense lead will cause both modules to indicate

bad.

The only exception is for battery modules 1 and 39, which are

monitored by their own individual sense lead.

Manual Method for Diagnosing Battery Modules and
Sense Leads

Early production versions of the NGS software may not support the

battery diagnostic system (BDS). If this is the case the manual method

of diagnosing battery modules and sense leads must be used. Use the

Battery Voltage Record Sheet (the next sub-section of this book) and

the following steps to locate the cause of a battery module or sense

lead concern.

Enter the BCM PID menu. Review the BAT_FT (battery sense lead

fault) PID for each battery module.

If there is a fault indicated, view the BAT_MV PID for that module

in BCM active command mode.

If that module indicates less than 3-volts, view the voltage

indications of the modules around it. If the module voltage directly

connected to the module that sets the fault (for example, module 2

set a fault, and module 1 or 3 also has a fault), suspect that a sense

lead is bad.

Operate the vehicle until the state of charge (SOC) PID indicates

that the battery pack SOC is 20%.

LESSON 5: DIAGNOSIS

5-47

Return the vehicle to the repair facility.

Actuate heater/defroster mode on high fan and leave on headlamps

to discharge battery pack.

When battery pack reaches 10% SOC, view BAT_MV PID for

each of the 39 battery modules.

Using the BAT_MV PID, record the battery voltage on the Battery

Voltage Record Sheet. (A copy is provided on the next page. There

is also a copy included as part of Worksheet L, and another copy

that can be found in the Diagnostic Information Appendix.)

Select the five lowest voltage battery modules.

Return to the BAT_MV PID and record the voltages of the five

lowest voltage battery modules.

From these five, compare the voltage readings of the lowest three

battery modules.

If the lowest voltage battery is 0.1 less than the second lowest

voltage battery, replace the lowest voltage battery module.

If the second lowest voltage battery is more than 0.08 volts less

than the third lowest voltage battery, replace the second lowest

voltage battery.

Prior to replacing the module, verify the serviceability of the

battery’s sense lead (measure for resistance of 30.9 K ohms), and

verify the module’s voltage reading with a DVOM.

LESSON 5: DIAGNOSIS

5-48

Battery Voltage Record Sheet

Directions

1. Enter BCM ACTIVE COMMANDS.

2. Enter BATTERY MODULE SELECT menu.

3. Enter PID menu.

4. Select BAT_MV PID.

5. Press START.

6. Press SETUP button (8).

7. Press AUTO (4).

8. Press CANCEL to return to ACTIVE COMMAND menu.

9. With battery module highlighted, press TRIGGER. This will shrink highlighted (darkened) area to only

include the battery module number.

10. Read and record voltage for battery module #1. Record the reading in the table below.

11. Rotate the scroll bar (center knob) and the module number will change. Read the voltage and record it.

12. Continue for each of the 39 battery modules. Record each reading in the table below.

BATTERY VOLTAGE

BATTERY VOLTAGE

BATTERY VOLTAGE

READINGS

READINGS

READINGS

1.

14.

27.

2.

15.

28.

3.

16.

29.

4.

17.

30.

5.

18.

31.

6.

19.

32.

7.

20.

33.

8.

21.

34.

9.

22.

35.

10.

23.

36.

11.

24.

37.

12.

25.

38.

13.

26.

39.

 

 

 

 

 

 

 

Content   ..  49  50  51  52   ..