10. SPINDLE SPEED FUNCTION
B-64693EN-1/01
- 1730 - NOTE 1 Even if this signal is once set to “1”, this signal is set to “0” when the speed difference exceeds the value set in parameter No.4810 2 For the correspondence between the signal of each spindle and actual signal address, see the description of "Signal address".
Spindle phase error monitor signal SYCAL<Fn044.4> [Classification] Output signal [Function] This signal posts that in the spindle synchronous control mode for the first/second spindles, the error pulse difference between the two spindles is greater than a
[Output cond.] This signal is set to “1” in the following case: - In the spindle synchronous control mode, the error pulse difference between two This signal is set to “0” in the following cases: The spindle synchronous control mode is not set. - In the spindle synchronous control mode, the error pulse difference between two
Spindle phase error monitor signal for each spindle SYCAL1 to SYCAL4<Fn043.0 to Fn043.3> [Classification] Output signal [Function] These signals post that in the spindle synchronous control mode with each spindle set as a slave spindle, the error pulse difference between two spindles is greater than a
[Output cond.] This signal is set to “1” in the following case: - In the spindle synchronous control mode, the error pulse difference between two This signal is set to “0” in the following cases: The spindle synchronous control mode is not set. - In the spindle synchronous control mode, the error pulse difference between two NOTE
For the correspondence between the signal of each spindle and
Spindle synchronous speed ratio control signal SBRT<Gn038.1> [Classification] Input signal [Function] This signal specifies switching to speed ratio control in spindle synchronous control.
[Operation] When this signal is set to “1”, speed ratio control is set. When this signal is set to “0”, speed ratio control is canceled. |