F-5 

Technical Specifications  

 

ENVIRONMENTAL DETAILS 

Operating Temperature 

 
 

NORMAL DUTY

 

HEAVY DUTY  

 

Operating temperature is defined as the surrounding air temperature of the drive, when the drive and other equipment adjacent to 
it is operating at worst case conditions. 

0

°

C to 40

°

C, derate up to a maximum of 50

°

0

°

C to 45

°

C, derate up to a maximum of 50

°

Output power is derated linearly at 2% per degree centigrade for temperature exceeding the maximum rating for the drive. 

Maximum operating temperature of the AC30D in the 24V dc supplied operating mode, without power applied to the stack, is 45

°

C. 

Storage Temperature 

-25

°

C to +55

°

Shipping Temperature 

-25

°

C to +70 

°

Product Enclosure Rating 

IP20 – remainder of surfaces (Europe) 
With frame sizes H & J, in order to retain the IP20 rating when making use of the DC-bus terminals, only partly remove DC-bus 
terminal cover breakouts or use additional external guarding. 
UL (c-UL) Open Type (North America/Canada) 

 

Cubicle Mounted 
 

IP20 

 

UL (c-UL) Open Type (North America/Canada) 

 

Through-panel Mounted 
 

IP20 

 

UL (c-UL) Open Type (North America/Canada) 

Altitude 

If greater than 1000m above sea level, derate by 1% per 100m to a maximum of 2000m 

Humidity 

Maximum 85% relative humidity at 40

°

C non-condensing 

Atmosphere 

Non flammable, non corrosive and dust free  

Climatic Conditions 

Class 3k3, as defined by EN60721-3-3  

Chemically Active Substances 

For the standard product (which inherently includes our optimal level of conformal coating) compliance with EN60721-3-3 is as 
follows – 
a)  Both classes 3C3 and 3C4 for hydrogen sulphide gas (H

2

S) at a gas concentration of 25ppm for 1200 hours. 

b)  Both classes 3C1 (rural) and 3C2 (urban) for all nine defined substances as defined in table 4. 
Classes 3C1 and 3C2 are valid for both storage and transportation purposes. 

 

Note - Product was tested and validated with a hydrogen sulphide environment of 25ppm for a continuous period of 1200 hours 
and validated throughout the test period without failure.  

Vibration 

Test Fc of EN60068-2-6 
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude 
57Hz<=f<=150Hz sinusoidal 1g 
10 sweep cycles per axis on each of three mutually perpendicular axis 

Safety 

 

 

Overvoltage Category  Overvoltage Category III (numeral defining an impulse withstand level) 

Pollution Degree  Pollution Degree II (non-conductive pollution, except for temporary condensation)  for control electronics 

Pollution Degree III (dirty air rating) for through-panel mounted parts 

North America/Canada  

 

Complies with the requirements of UL508C as an open-type drive.  

 

Technical Specifications 

F-6

 

EARTHING/SAFETY DETAILS  

Earthing 

Permanent earthing is mandatory on all units. 

 

Use a copper protective earth conductor 10mm² minimum cross-section, or install a second conductor in parallel with the 
protective conductor to a separate protective earth terminal 

 

The conductor itself must meet local requirements for a protective earth conductor 

Input Supply Details 
(TN) and (IT) 

Drives without filters are suitable for earth referenced (TN) or non-earth referenced (IT) supplies. 
The drive is only suitable for earth referenced supplies (TN) when fitted with an internal filter. External filters are available for use 
on TN and IT (non-earth referenced) supplies. 

Prospective Short Circuit 
Current (PSCC) 

Refer to the appropriate Electrical Ratings table. 

Earth Leakage Current 

>10mA (all models) 

 

 

COOLING FANS 

The forced-vent cooling of the drive is achieved by 1, 2 or in some cases 3 fans. The Fan Rating gives the volume of air venting from the drive per fan. 

Product  

Main Cooling Fan Ratings 

Internal Cooling Fan Ratings 

FRAME D 

3kW, 4kW & 5.5kW models only 

1 off 27 cfm (45m³/hr) 

N/A 

FRAME E

  

All models 

1 off 33 cfm (56m³/hr) 

N/A 

FRAME F

  

15kW & 18.5kW models 

 

22kW model 

2 off 27 cfm (45m³/hr) 
2 off 33 cfm (56m³/hr) 

N/A 
1 off 5 cfm (8.5 m³/hr) 

FRAME G 

 

All models 

2 off 53 cfm (89 m³/hr) 

1 off 27 cfm (45 m³/hr) 

FRAME H 

45kW model 

2 off 27 cfm (45 m³/hr) 

1 off 27 cfm (45 m³/hr) 

 

55kW & 75kW models 

2 off 53 cfm (89 m³/hr) 

1 off 27 cfm (45 m³/hr) 

FRAME J

  

All Models 

3 off 80 cfm (133 m³/hr) 

2 off 27 cfm (45 m³/hr)

 

FRAME K 

All models 

1 off 518 cfm (880 m³/hr) 

N/A 

 

 

 

F-7 

Technical Specifications  

AC

 FED ELECTRICAL RATINGS (400V BUILD VARIANT) 

Power Supply =  380-480V ±10%, 50/60Hz 

±

5%

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME D : 

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 
5kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

710-4D0004… 

1.1kW 

3.5 

95% 

4   /  16 

2.4% 

1.5Hp 

3.0 

3.5 

710-4D0005… 

1.5kW 

4.5 

5.3 

96% 

4   /  16 

3.7% 

2Hp 

3.4 

4.5 

710-4D0006… 

2.2kW 

5.5 

7.6 

97% 

4   /  16 

4.5% 

3Hp 

4.8 

6.4 

710-4D0008… 

3kW 

7.5 

6.5 

97% 

4   /  16 

4.0% 

  

 

 

710-4D0010… 

4kW 

10.0 

8.0 

97% 

4   /  16 

3.9% 

5Hp 

7.6 

6.6 

710-4D0012… 

5.5kW 

12.0 

10.6 

97% 

4   /  16 

3.5% 

7.5Hp 

11 

9.4 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

710-4D0004… 

0.75kW 

2.5 

2.9 

95% 

4   /  16 

1.0% 

1Hp 

2.1 

2.4 

710-4D0005… 

1.1kW 

3.5 

4.0 

95% 

4   /  16 

3.1% 

1.5Hp 

3.0 

3.5 

710-4D0006… 

1.5kW 

4.5 

5.3 

96% 

4   /  16 

4.3% 

2Hp 

3.4 

4.5 

710-4D0008… 

2.2kW 

5.5 

5.2 

97% 

4   /  16 

3.8% 

3Hp 

4.8 

4.6 

710-4D0010… 

3kW 

7.5 

6.5 

97% 

4   /  16 

3.8% 

 

 

 

710-4D0012… 

4kW 

10.0 

8.0 

97% 

4   /  16 

3.3% 

5Hp 

7.6 

6.6 

Technical Specifications 

F-8

 

Power Supply =  380-480V ±10%, 50/60Hz 

±

5%

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME E: 

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 5kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

710-4E0016… 

7.5kW 

16 

14.5 

97% 

4   /  16 

5.5% 

10Hp 

14 

12.1 

710-4E0023… 

11kW 

23 

20.4 

97% 

4   /  16 

5.1% 

15Hp 

21 

18.0 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating) 

 

710-4E0016… 

5.5kW 

12 

10.7 

97% 

4   /  16 

4.9% 

7.5Hp 

11 

9.5 

710-4E0023… 

7.5kW 

16 

14.5 

97% 

4   /  16 

4.9% 

10Hp 

14 

12.7 

F-9 

Technical Specifications  

Power Supply =  380-480V ±10%, 50/60Hz 

±

5%

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME F : 

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 5kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

710-4F0032… 

15kW 

32 

28.5 

97% 

4   /  12 

6.3% 

20Hp 

27 

24.5 

710-4F0038… 

18.5kW 

38 

33.5 

97% 

4   /  12 

6.7% 

25Hp 

36 

30.2 

710-4F0045… 

22kW 

45 

40 

97% 

3   /  12 

6.7% 

30Hp 

40 

35.7 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

710-4F0032… 

11kW 

23 

21.7 

97% 

4   /  12 

6.0% 

15Hp 

21 

19.1 

710-4F0038… 

15kW 

32 

28.5 

97% 

4   /  12 

6.1% 

20Hp 

27 

24.5 

710-4F0045… 

18.5kW 

38 

34.3 

97% 

3   /  12 

6.1% 

25Hp 

36 

30.5 

Technical Specifications 

F-10

 

Power Supply =  380-480V ±10%, 50/60Hz 

±

5%

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME G : 

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 10kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

710-4G0045… 

22kW 

45 

40 

98% 

3   /  12 

5.7% 

30Hp 

40 

35.7 

710-4G0060… 

30kW 

60 

54.7 

98% 

3   /  12 

5.9% 

40Hp 

52 

48 

710-4G0073… 

37kW 

73 

66.2 

98% 

3   /  12 

5.6% 

50Hp 

65 

58.5 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

710-4G0045… 

18kW 

38 

34.3 

98% 

3   /  12 

5.3% 

25Hp 

36 

30.5 

710-4G0060… 

22kW 

45 

41.8 

98% 

3   /  12 

5.7% 

30Hp 

40 

37.5 

710-4G0073… 

30kW 

60 

54.7 

98% 

3   /  12 

5.2% 

40Hp 

52 

48 

F-11 

Technical Specifications  

Power Supply =  380-480V ±10%, 50/60Hz 

±

5%

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME H : 

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 10kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

710-4H0087… 

45kW 

87 

78.8 

98% 

2.5   /  8 

8.5% 

60Hp 

77 

69 

710-4H0105… 

55kW 

105 

95.8 

98% 

2.5   /  8 

7.8% 

75Hp 

96 

84.5 

710-4H0145… 

75kW 

145 

130 

98% 

2.5   /  8 

9.1% 

100Hp 

124 

113.5 

Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

710-4H0087… 

37kW 

73 

66 

98% 

2.5   /  8 

7.7% 

50Hp 

65 

58.5 

710-4H0105… 

45kW 

87 

79.5 

98% 

2.5   /  8 

6.9% 

60Hp 

77 

70 

710-4H0145… 

55kW 

105 

97.4 

98% 

2.5   /  8 

8.6% 

75Hp 

96 

87 

Technical Specifications 

F-12

 

Power Supply =  380-480V ±10%, 50/60Hz 

±

5%

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME J : 

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 10kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

710-4J0180… 

90kW 

180 

160 

98% 

2.5   /  8 

8.1% 

125Hp 

156 

147 

710-4J0205… 

110kW 

205 

198 

98% 

2.5   /  8 

8.4% 

150Hp 

180 

175 

710-4J0260… 

132kW 

260 

236 

98% 

2.5   /  8 

8.7% 

200Hp 

240 

231 

Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

710-4J0180… 

75kW 

145 

137 

98% 

2.5   /  8 

7.5% 

100Hp 

124 

119 

710-4J0205… 

90kW 

180 

164 

98% 

2.5   /  8 

8.6% 

125Hp 

156 

148 

710-4J0260… 

110kW 

205 

199 

98% 

2.5   /  8 

8.0% 

150Hp 

180 

177 

 
 

 

F-13 

Technical Specifications  

 

 

Power Supply =  380-480V ±10%, 50/60Hz 

±

5% 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  
Minimum repetitive power up  / power down cycle time = 10 mins 

Product Code 

Motor Power 

Output 

Current 

(A) 

Input 

Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz 

(applied above nominal 

switching frequency) 

FRAME K :  

Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit current 18kA. 

Normal Duty 

(Output Overload Motoring 110% for 60s) 

710-4K0315… 

160kW 

315 

276 

98% 

2   /  8 

8.5% 

250Hp 

302 

279 

710-4K0380… 

200kW 

380 

343 

98% 

2   /  8 

7.7% 

300Hp 

361 

333 

710-4K0440… 

250kW 

440 

428 

98% 

2   /  8 

8.3% 

350Hp 

414 

389 

Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating) 

710-4K0315… 

132kW 

260 

229 

98% 

2   /  8 

7.7% 

200Hp 

240 

225 

710-4K0380… 

160kW 

315 

276 

98% 

2   /  8 

6.9% 

250Hp 

302 

279 

710-4K0440… 

200kW 

380 

344 

98% 

2   /  8 

7.5% 

300Hp 

361 

334 

 

 

 

Technical Specifications 

F-14

 

DC

 FED ELECTRICAL RATINGS (400V BUILD VARIANT) 

Power Supply =  510V - 650V DC Average

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME D : 

Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4% 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

740-4D0004… 

1.1kW 

3.5 

3.5 

95% 

4   /  16 

2.4% 

1.5Hp 

3.0 

3.1 

740-4D0005… 

1.5kW 

4.5 

4.6 

96% 

4   /  16 

3.7% 

2Hp 

3.4 

3.9 

740-4D0006… 

2.2kW 

5.5 

6.3 

97% 

4   /  16 

4.5% 

3Hp 

4.8 

5.6 

740-4D0008… 

3kW 

7.5 

8.0 

97% 

4   /  16 

4.0% 

  

 

 

740-4D0010… 

4kW 

10.0 

9.8 

97% 

4   /  16 

3.9% 

5Hp 

7.6 

8.1 

740-4D0012… 

5.5kW 

12.0 

13.0 

97% 

4   /  16 

3.5% 

7.5Hp 

11 

11.5 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

740-4D0004… 

0.75kW 

2.5 

2.5 

95% 

4   /  16 

1.0% 

1Hp 

2.1 

2.2 

740-4D0005… 

1.1kW 

3.5 

3.5 

95% 

4   /  16 

3.1% 

1.5Hp 

3.0 

3.1 

740-4D0006… 

1.5kW 

4.5 

4.6 

96% 

4   /  16 

4.3% 

2Hp 

3.4 

3.9 

740-4D0008… 

2.2kW 

5.5 

6.4 

97% 

4   /  16 

3.8% 

3Hp 

4.8 

5.6 

740-4D0010… 

3kW 

7.5 

7.7 

97% 

4   /  16 

3.8% 

 

 

 

740-4D0012… 

4kW 

10.0 

9.8 

97% 

4   /  16 

3.3% 

5Hp 

7.6 

8.1 

F-15 

Technical Specifications  

Power Supply =  510V - 650V DC Average

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME E: 

Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4% 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

740-4E0016… 

7.5kW 

16 

18 

97% 

4   /  16 

5.5% 

10Hp 

14 

15 

740-4E0023… 

11kW 

23 

25 

97% 

4   /  16 

5.1% 

15Hp 

21 

22 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating) 

 

740-4E0016… 

5.5kW 

12 

13 

97% 

4   /  16 

4.9% 

7.5Hp 

11 

12 

740-4E0023… 

7.5kW 

16 

18 

97% 

4   /  16 

4.9% 

10Hp 

14 

16 

Technical Specifications 

F-16

 

Power Supply =  510V - 650V DC Average

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME F : 

Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4%

 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

740-4F0032… 

15kW 

32 

35 

97% 

4   /  12 

6.3% 

20Hp 

27 

30 

740-4F0038… 

18.5kW 

38 

41 

97% 

4   /  12 

6.7% 

25Hp 

36 

37 

740-4F0045… 

22kW 

45 

49 

97% 

3   /  12 

6.7% 

30Hp 

40 

46 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 0.3s short term rating)

 

740-4F0032… 

11kW 

23 

27 

97% 

4   /  12 

6.0% 

15Hp 

21 

23 

740-4F0038… 

15kW 

32 

35 

97% 

4   /  12 

6.1% 

20Hp 

27 

30 

740-4F0045… 

18.5kW 

38 

41 

97% 

3   /  12 

6.1% 

25Hp 

36 

37 

F-17 

Technical Specifications  

Power Supply =  510V - 650V DC Average

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME G : 

Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4%. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

740-4G0045… 

22kW 

45 

49 

98% 

3   /  12 

5.7% 

30Hp 

40 

46 

740-4G0060… 

30kW 

60 

67 

98% 

3   /  12 

5.9% 

40Hp 

52 

59 

740-4G0073… 

37kW 

73 

81 

98% 

3   /  12 

5.6% 

50Hp 

65 

72 

 Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

740-4G0045… 

18kW 

38 

42 

98% 

3   /  12 

5.3% 

25Hp 

36 

37 

740-4G0060… 

22kW 

45 

51 

98% 

3   /  12 

5.7% 

30Hp 

40 

46 

740-4G0073… 

30kW 

60 

67 

98% 

3   /  12 

5.2% 

40Hp 

52 

59 

Technical Specifications 

F-18

 

Power Supply =  510V - 650V DC Average

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME H : 

Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4%. 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

740-4H0087… 

45kW 

87 

97 

98% 

2.5   /  8 

8.5% 

60Hp 

77 

85 

740-4H0105… 

55kW 

105 

117 

98% 

2.5   /  8 

7.8% 

75Hp 

96 

104 

740-4H0145… 

75kW 

145 

159 

98% 

2.5   /  8 

9.1% 

100Hp 

124 

139 

Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

740-4H0087… 

37kW 

73 

81 

98% 

2.5   /  8 

7.7% 

50Hp 

65 

72 

740-4H0105… 

45kW 

87 

97 

98% 

2.5   /  8 

6.9% 

60Hp 

77 

86 

740-4H0145… 

55kW 

105 

119 

98% 

2.5   /  8 

8.6% 

75Hp 

96 

107 

F-19 

Technical Specifications  

Power Supply =  510V - 650V DC Average

 

Motor power, output current and input current must not be exceeded under steady state operating conditions.  

Product Code 

Motor Power  Output Current 

(A) 

Input Current  

(A) 

Estimated 
Efficiency 

Switching Frequency 

(kHz) 

nominal  /  maximum 

Output Current Derate %/kHz  

(applied above nominal switching 

frequency) 

FRAME J : 

Input currents for kW ratings are at 530V DC input and for Hp ratings at 620V DC input, with AC line choke equivalent to 4% 

Normal Duty 

(Output Overload Motoring 110% for 60s)

 

740-4J0180… 

90kW 

180 

198 

98% 

2.5   /  8 

8.1% 

125Hp 

156 

180 

740-4J0205… 

110kW 

205 

243 

98% 

2.5   /  8 

8.4% 

150Hp 

180 

214 

740-4J0260… 

132kW 

260 

289 

98% 

2.5   /  8 

8.7% 

200Hp 

240 

283 

Heavy Duty 

(Output Overload Motoring 150% for 60s, 180% for 3s short term rating)

 

740-4J0180… 

75kW 

145 

168 

98% 

2.5   /  8 

7.5% 

100Hp 

124 

146 

740-4J0205… 

90kW 

180 

201 

98% 

2.5   /  8 

8.6% 

125Hp 

156 

181 

740-4J0260… 

110kW 

205 

244 

98% 

2.5   /  8 

8.0% 

150Hp 

180 

217 

40Hp 

52 

59 

75Hp 

96 

107 

 

 

150Hp 

180 

217 

 

 

 
 

 

Technical Specifications 

F-20

 

LINE INPUT FUSE RATINGS (EUROPE) 

Product Code 

Input Fuse Rating (A) 

Product Code 

Input Fuse Rating (A) 

NORMAL DUTY 

NORMAL DUTY 

400V BUILD VARIANT 

380-480V ±10%, 50/60Hz +5%*

 

Frame D 

Frame G

 

710-4D0004… 

10A 

710-4G0045… 

63A 

710-4D0005… 

10A 

710-4G0060… 

80A 

710-4D0006… 

10A 

710-4G0073… 

100A 

710-4D0008… 

10A 

Frame H

 

710-4D0010… 

12A 

710-4H0087… 

125A 

710-4D0012… 

16A 

710-4H0105… 

150A 

Frame E

 

710-4H0145… 

200A 

710-4E0016… 

20A 

Frame J

 

710-4E0023… 

25A 

710-4J0180… 

250A 

Frame F

 

710-4J0205… 

315A 

710-4F0032… 

32A 

710-4J0260… 

400A 

710-4F0038… 

40A 

Frame K 

710-4F0045… 

63A 

710-4K0315…

 

400A

 

 

 

710-4K0380… 

500A 

 

 

710-4K0440… 

630A 

 
 
Type:  Semiconductor protection fuses 500V AC, Mersen type A50QSX or equivalent. 

 

 

 

 

 

 

 