temperature from the thermometer in the center vent, the intake temperature near the blower unit, and the 8. To complete the charts: z Mark the delivery temperature along the vertical line. z Mark the intake temperature (ambient air temperature) along the bottom line. z Draw a line straight up from the air temperature to the humidity. z Mark a point 10% above and 10% below the humidity level. z From each point, draw a horizontal line across the delivery temperature. z The delivery temperature should fall between the two lines. z Complete the low-side pressure test and high-side pressure test in the same way. z Any measurements outside the line may indicate the need for further inspection. Example Intake temperature (dry): 86°F (30°C) Humidity level 70% (wet): 77.9°F (25.5°C) Intake pressure: 215 kPa (2.2 kgf/cm 2 ) (31.3 psi)
Delivery temperature: 56.5°F (13.6°C) Delivery pressure: 1604 kPa (16.3 kgf/cm 2 ) (231.8 psi)
Results: within normal range